Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Mersen R075524 Limitor aSJB/D high voltage motor protection back-up fuse-link rated at 3.6 kV AC and 200 A, with a 60 kA breaking capacity and integrated 20 N striker.
£596.60
The Mersen R075524 is a dependable high voltage motor protection back-up fuse-link designed to protect medium voltage motors, switchgear and associated electrical equipment against damaging short-circuit currents. As part of the established Mersen Limitor® aSJB/D series, it is engineered specifically for motor circuits that experience repeated peak currents during starting.
The R075524 uses silver-plated copper fuse elements, silver-plated brass terminals and a durable melamine fibreglass insulating body. This robust construction provides reliable electrical performance, effective current limitation and dependable operation within demanding industrial and utility installations.
With a rated voltage of 3.6 kV AC, a rated current of 200 A and a maximum breaking capacity of 60 kA, the R075524 provides reliable protection for compatible medium voltage motor circuits. Its integrated 20 N striker supports fault indication and operation of suitable switching equipment following fuse operation.
Motor protection back-up fuse-links are designed to interrupt severe short-circuit currents rapidly while tolerating the repeated inrush currents generated during motor starting. Their current-limiting characteristics reduce the peak current and fault energy imposed on motors, cables, contactors and associated switchgear.
The Mersen R075524 combines a high breaking capacity with motor-specific operating characteristics and an integrated striker. When the fuse-link operates, the striker can provide fault indication or activate compatible switching equipment, supporting coordinated isolation and safer maintenance.
Tick the specs you need, then view products that match.
| Fuse Indication | Striker | |
|---|---|---|
| Device Type | Fuse link | |
| Fuse Type | High voltage | |
| Current | 200 A | |
| Voltage | 3600 V | |
| Manufacturer | Mersen | |
| Series | Limitor® aSJB/D | |
| Model | R075524 | |
| Catalogue number | 45ASB36V200P-2 | |
| Product type | High voltage motor protection back-up fuse-link | |
| Primary application | Medium voltage motor protection | |
| Rated voltage | 3.6 kV AC IEC | |
| Rated current | 200 A | |
| Current type | AC | |
| Maximum breaking capacity | 60 kA | |
| Minimum interrupting rating | 1,250 A | |
| Clearing I²t at rated voltage | 370 kA²s | |
| Power dissipation | 33 W at 0.7 × rated current | |
| Motor factor K | 0.51 | |
| Fuse body diameter | 67 mm | |
| Fuse body length | 292 mm | |
| Overall product length | 358 mm | |
| Mounting type | Clip mounting | |
| Indication system | Striker | |
| Striker force | 20 N | |
| Fuse-element material | Silver-plated copper | |
| Terminal material | Silver-plated brass | |
| Terminal type | Cylindrical | |
| Body material | Melamine fibreglass | |
| Product weight | Approx. 2.7 kg | |
| RoHS compliant | Yes | |
| EAN | 3605340009736 | |
| Applicable standards | IEC 60282-1 and IEC 60644 |
The Mersen R075524 is a high voltage back-up fuse-link designed to protect medium voltage motors and associated switchgear against damaging short-circuit currents.
The fuse-link has a rated voltage of 3.6 kV AC and a rated current of 200 A.
The Mersen R075524 has a maximum AC breaking capacity of 60 kA.
The fuse body measures 67 mm in diameter and 292 mm in length, with an overall product length of 358 mm.
Yes. It incorporates a 20 N striker for fault indication and operation of compatible switchgear following fuse operation.
Yes. The Limitor® aSJB/D fuse-link is specifically designed to support repeated peak currents generated during medium voltage motor starting.
Mersen Limitor® motor protection fuse-links are widely used by utilities, switchgear manufacturers, electrical contractors and industrial engineers for dependable protection of medium voltage motors and critical electrical infrastructure.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.