Mersen P075522 Limitor aSJB/D high voltage back-up fuse-link rated at 3.6 kV AC and 125 A, with a 60 kA breaking capacity and integrated 20 N striker for medium voltage motor protection.
£517.41
The Mersen P075522 is a high voltage back-up fuse-link designed to protect medium voltage motors and associated electrical equipment against damaging short-circuit currents. Part of the established Mersen Limitor® aSJB/D series, it is engineered to withstand the repeated peak currents generated during motor starting while providing dependable current-limiting protection during serious electrical faults.
This fuse-link is manufactured using silver-plated copper fuse elements, silver-plated brass terminals and a robust melamine fibreglass body. These carefully selected materials provide reliable electrical conductivity, effective fault interruption and long operational life within demanding high voltage switchgear and controlgear installations.
Rated at 3.6 kV AC and 125 A, the Mersen P075522 provides a maximum breaking capacity of 60 kA. Its integrated 20 N striker can provide fault indication or operate compatible switching equipment after the fuse-link functions, helping support safe and coordinated motor protection.
High voltage motor fuse-links must tolerate the elevated current drawn during normal motor starting without unnecessary operation. During a severe short-circuit fault, however, the fuse-link must rapidly limit and interrupt the current before excessive thermal or mechanical stress damages the motor, cables or associated switchgear.
The Mersen P075522 is specifically designed for this demanding duty. Its motor protection characteristics, robust construction and integrated striker make it suitable for coordinated use within industrial motor starters and high voltage controlgear.
Tick the specs you need, then view products that match.
| Fuse Indication | Striker | |
|---|---|---|
| Device Type | Fuse link | |
| Fuse Type | High voltage | |
| Current | 125 A | |
| Voltage | 3600 V | |
| Manufacturer | Mersen | |
| Series | Limitor® aSJB/D | |
| Item number | P075522 | |
| Catalogue number | 45ASB36V125P-2 | |
| Product type | High voltage motor back-up fuse-link | |
| Primary application | Medium voltage motor protection | |
| Rated voltage | 3.6 kV AC IEC | |
| Rated current | 125 A | |
| Current type | AC | |
| Fuse body size | 50.8 mm diameter × 292 mm length | |
| Overall product diameter | 50.8 mm | |
| Overall product length | 358 mm | |
| Mounting type | Clip mounting | |
| Maximum breaking capacity | 60 kA | |
| Minimum interrupting rating | 830 A | |
| Clearing I²t at rated voltage | 160 kA²s | |
| Power dissipation | 20 W at 0.7 In | |
| Indication system | Striker | |
| Striker force | 20 N | |
| Motor protection coefficient K | 0.51 | |
| Terminal material | Silver-plated brass | |
| Terminal type | Cylindrical | |
| Fuse-element material | Silver-plated copper | |
| Body material | Melamine fibreglass | |
| Product weight | Approx. 1.6 kg | |
| RoHS compliant | Yes | |
| EAN | 3605340009712 | |
| Applicable standards | IEC 60282-1, IEC 60644 and DIN 43625 |
The Mersen P075522 is a high voltage back-up fuse-link designed to protect medium voltage motors and associated switchgear against damaging short-circuit currents.
The fuse-link has a rated voltage of 3.6 kV AC and a rated current of 125 A.
The Mersen P075522 has a maximum AC breaking capacity of 60 kA.
Yes. The P075522 is specifically designed to support the repeated peak currents associated with medium voltage motor starting while providing reliable short-circuit protection.
Yes. It incorporates a 20 N striker that can provide fault indication or operate compatible switchgear after the fuse-link functions.
The fuse body measures approximately 50.8 mm in diameter and 292 mm in length, with an overall product length of approximately 358 mm.
Mersen Limitor® high voltage motor fuse-links are widely used by switchgear manufacturers, electrical contractors, OEMs and industrial engineers for dependable protection of medium voltage motors and critical electrical equipment.