Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OTA80S4YX (1SCA152741R1001) is an 80 A ATEX enclosed safety switch for Zone 22 combustible-dust environments with three-phase switching and switchable neutral, 37 kW AC-23A motor-load capability at 415 V AC, IP65 aluminium enclosure, EMC-compatible installation capability, a red/yellow handle and one normally open auxiliary contact.
£521.90
The ABB OTA80S4YX (ABB product ID 1SCA152741R1001) is an 80 A ATEX-rated enclosed safety switch designed for reliable manual load switching and electrical isolation in industrial environments where combustible dust may create a potentially explosive atmosphere. Part of ABB's specialist OTA enclosed safety switch range, this assembly combines a robust aluminium enclosure, red/yellow operating handle, IP65 ingress protection and an integrated normally open auxiliary contact.
Designed for demanding industrial machinery applications, the OTA80S4YX provides an 80 A conventional thermal current rating, a 75 A AC-23A operational current rating at 380–415 V AC and a corresponding 37 kW motor-load switching rating. Its three-phase switching arrangement incorporates a switchable neutral, giving the assembly four main switching poles. The included 1 NO auxiliary contact provides an additional signalling connection for compatible monitoring and control circuits.
The OTA80S4YX is designed for ATEX Zone 22 combustible-dust environments, with an equipment classification of Ex tc III T70°C Dc. Its aluminium enclosure is suitable for EMC-sensitive applications when used with appropriate EMC cable glands. Supplied with ATEX cable glands, the switch offers a practical enclosed isolation solution for mills, conveyors, industrial processing equipment and other appropriately classified hazardous-area installations.
The ABB OTA80S4YX is designed for industrial electrical installations where safe manual switching and isolation must be combined with equipment suitability for potentially explosive dust atmospheres. Its ATEX Ex tc III T70°C Dc classification identifies the product as suitable for appropriately assessed Zone 22 applications, subject to the manufacturer's installation requirements and the site's hazardous-area classification.
ATEX Zone 22 environments are locations where an explosive atmosphere in the form of combustible dust is not likely to occur during normal operation and, if it does occur, persists only for a short period. Typical industrial applications include grain processing, milling, conveying, material handling and other processes where combustible dust may be present.
The OTA80S4YX provides an 80 A rated permanent current and a 75 A AC-23A operational current rating at 380–415 V AC. Its 37 kW AC-23A operational power rating supports compatible three-phase motor switching applications. These electrical ratings must be considered alongside the motor's full-load current, starting characteristics and required switching duty.
Although the product is commonly described as a three-phase enclosed safety switch, its actual main circuit configuration comprises four switching poles, including a switchable neutral. This arrangement enables simultaneous switching of the three phase conductors and neutral in compatible electrical systems. The neutral switching arrangement must be assessed against the installation's earthing and supply configuration.
The IP65 aluminium enclosure provides dust-tight protection and resistance to water jets when correctly installed. Its IK08 impact resistance rating offers additional mechanical protection, while the compact enclosure dimensions make the switch suitable for mounting near industrial machinery and processing equipment.
The OTA80S4YX also supports electromagnetic compatibility applications. ABB specifies that the switch can be used in EMC environments when installed with suitable EMC cable glands. These glands help maintain the intended electromagnetic shielding arrangement for screened power cables. Standard ATEX cable glands and EMC cable glands are not interchangeable without confirming their suitability for the hazardous-area and EMC requirements.
The switch is supplied with ATEX cable glands and provides top and bottom cable entry positions. Its main circuit uses screw-clamp terminals suitable for conductors within the specified 1.5–35 mm² connection range. Cable gland selection, protective bonding, conductor termination and enclosure sealing must follow the manufacturer's instructions and the relevant hazardous-area installation standards.
A red/yellow operating handle provides a highly visible means of manual switching. The integrated 1 NO auxiliary contact can be used for compatible indication or control circuits, while the maximum supported auxiliary contact configuration is 2 normally open and 2 normally closed contacts.
As a switch disconnector, the OTA80S4YX provides manual load switching and electrical isolation rather than automatic overload or short-circuit protection. Suitable protective devices must be installed separately, and the complete electrical installation must comply with the applicable ATEX, electrical safety and hazardous-area requirements.
Tick the specs you need, then view products that match.
| Device Type | Enclosed safety switch / isolator | |
|---|---|---|
| Voltage | 750 V AC | |
| Material | Aluminium |
The ABB OTA80S4YX is an 80 A ATEX enclosed safety switch designed for manual load switching and electrical isolation in compatible industrial hazardous-dust environments, including appropriately classified Zone 22 installations.
The OTA80S4YX has an 80 A rated permanent current and a 75 A AC-23A operational current rating at 380–415 V AC. The correct rating depends on the connected load and utilisation category.
The switch has a 37 kW AC-23A operational power rating at 380–415 V AC. ABB also specifies 37 kW at 500 V AC and 18.5 kW at 690 V AC.
Yes. The OTA80S4YX is designed for appropriately classified ATEX Zone 22 combustible-dust environments, with an equipment classification of Ex tc III T70°C Dc. Installation suitability must be verified against the site's hazardous-area assessment.
Ex tc III T70°C Dc identifies equipment using protection by enclosure for combustible-dust atmospheres, with Group III classification, a specified maximum surface temperature of 70°C and equipment protection level Dc. It is intended for compatible Zone 22 applications.
The OTA80S4YX has four main switching poles, comprising three phase poles and a switchable neutral. It is designed for three-phase electrical installations requiring this switching arrangement.
The OTA80S4YX has an IP65 ingress protection rating, providing dust-tight protection and resistance to water jets when correctly installed with suitable cable glands and enclosure sealing.
The enclosure is manufactured from aluminium and uses ABB's Frontex2 enclosure design. It also has an IK08 impact resistance rating.
Yes. ABB specifies that the OTA80S4YX can be used in EMC environments when installed with suitable EMC cable glands. The complete cable screening and gland arrangement must be selected for the application.
Yes. ABB's OTA ATEX enclosed safety switch range is supplied with ATEX cable glands. Additional or alternative EMC-rated glands must be selected separately where required.
The OTA80S4YX has a red/yellow rotary operating handle for clearly visible manual ON/OFF switching and isolation.
Yes. The switch includes 1 normally open auxiliary contact. The maximum supported auxiliary contact configuration is 2 NO + 2 NC.
The main circuit screw-clamp terminals accommodate conductors within the specified 1.5–35 mm² range. The protective earth terminal accepts a conductor within the specified 6–35 mm² range.
The enclosure measures 230 mm high × 160 mm wide × 118 mm deep. The manufacturer's product data lists a net weight of approximately 2.15 kg.
The OTA80S4YX has a 13 kA rated conditional short-circuit current. Suitable protective devices and the manufacturer's coordination requirements must be considered when designing the installation.
No. The OTA80S4YX is a switch disconnector intended for manual load switching and isolation. Appropriate overload and short-circuit protective devices must be provided separately.
The OTA80S4YX is specifically designed for ATEX combustible-dust applications and supports EMC-compatible installation with suitable cable glands. A standard enclosed safety switch must not be assumed suitable for hazardous-area use without the appropriate certification.
ABB's product information identifies OTA63GS4YX as the replacement reference. The replacement's current ratings, pole configuration, ATEX classification and installation requirements should be checked before substitution.
ABB OTA ATEX enclosed safety switches provide dependable manual electrical isolation for industrial installations where combustible dust and electromagnetic compatibility requirements must be considered. With its 80 A thermal current rating, 37 kW AC-23A motor-load capability at 415 V AC, Ex tc III T70°C Dc classification, IP65 aluminium enclosure, red/yellow operating handle and integrated 1 NO auxiliary contact, the OTA80S4YX offers a practical solution for industrial electrical contractors, machinery manufacturers and hazardous-area maintenance engineers.
We use cookies