1SCA152718R1001 ABB 16 A 4-Pole IP65 ATEX EMC Enclosed Switch-Disconnector

1SCA152718R1001 ABB 16 A 4-Pole IP65 ATEX EMC Enclosed Switch-Disconnector

ABB OTA16S4BX is a 16 A 4-pole IP65 ATEX EMC enclosed switch-disconnector with a 7.5 kW AC-23A motor rating at 415 V, Ex tc III T70°C Dc classification, 1NO auxiliary contact and top and bottom cable entries.

SKU: 1SCA152718R1001Alt SKU: OTA16S4BXMPN: 1SCA152718R1001
Price
List Price £516.31 ex VAT
Your Price (ex VAT) Save 35%
£335.60 35% OFF
You save £180.71 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £335.60
Trade pricing is personalised to your account

Manufacturer Lead Time

£335.60

Why Choose the ABB OTA16S4BX 16 A ATEX EMC Enclosed Switch?

The ABB OTA16S4BX, order number 1SCA152718R1001, is a specialist 16 A, 4-pole ATEX EMC enclosed switch-disconnector designed for dependable load breaking and electrical isolation in potentially explosive industrial environments. It combines ABB switch-disconnector technology with a rigid die-cast aluminium enclosure, IP65 protection and a black I-O / ON-OFF operating handle.

Designed for four-pole electrical isolation, the OTA16S4BX provides an AC-23A operational rating of 16 A / 7.5 kW at 380–415 V. At 690 V, its AC-23A rating is 10 A / 7.5 kW. The four-pole arrangement enables four conductors to be switched simultaneously, making it suitable for applications where complete four-pole isolation is required.

The OTA16S4BX is designed in accordance with the ATEX framework for potentially explosive atmospheres and carries an Ex tc III T70°C Dc classification for Zone 22 applications. It is EMC approved and supplied with a 1NO auxiliary contact, PE terminal, threaded top and bottom cable entries, cable glands, cable-entry plugs and safety-switch identification.

Key Advantages

  • 16 A, 4-pole ATEX enclosed switch-disconnector for hazardous-area applications.
  • 7.5 kW / 16 A AC-23A rating at 380–415 V.
  • 7.5 kW / 10 A AC-23A rating at 690 V.
  • Four-pole configuration enables simultaneous switching of four conductors.
  • Designed for ATEX Zone 22 combustible-dust environments.
  • Ex tc III T70°C Dc hazardous-area classification.
  • IP65 rigid die-cast aluminium enclosure.
  • EMC approved for installations requiring electromagnetic compatibility.
  • 1NO auxiliary contact included for signalling or control functions.
  • Top and bottom cable entries provide flexible installation options.

Key Features

  • ABB OTA16S4BX ATEX EMC enclosed switch-disconnector.
  • 16 A equipment rating.
  • 4-pole switching configuration.
  • 16 A AC-22A operational current at 380–415 V, 500 V and 690 V.
  • 16 A AC-23A operational current at 380–415 V and 500 V.
  • 10 A AC-23A operational current at 690 V.
  • 7.5 kW motor switching capability at 415 V and 690 V.
  • IP65 protection rating.
  • Rigid die-cast aluminium enclosure.
  • ATEX Zone 22 application suitability.
  • Ex tc III T70°C Dc classification.
  • EMC approved construction.
  • Black I-O / ON-OFF operating handle.
  • Interlocked enclosure cover.
  • 1NO auxiliary contact included.
  • Maximum auxiliary-contact capacity of 2NO+2NC.
  • PE terminal included.
  • Threaded cable entries at the top and bottom.
  • Cable glands and cable-entry plugs included.

Reliable Four-Pole ATEX Isolation

The ABB OTA16S4BX provides four-pole electrical isolation for installations where combustible dust can create a potentially explosive atmosphere. Its Ex tc III T70°C Dc classification supports use in Zone 22 applications, while the rigid aluminium enclosure provides IP65 protection for the enclosed switching mechanism.

The switch is also EMC approved and can be integrated into EMC-sensitive installations with suitable EMC cable glands. Threaded top and bottom cable entries provide flexible incoming and outgoing cable routing, while the interlocked cover, included auxiliary contact and clearly defined I-O / ON-OFF operation support dependable local machinery isolation.

Typical Applications

  • ATEX Zone 22 industrial installations.
  • Four-pole isolation in potentially explosive atmospheres.
  • Dusty industrial environments.
  • Mills and material processing plants.
  • Hazardous-area conveyor systems.
  • Industrial motor isolation within the specified AC-23A ratings.
  • Powder and bulk-material handling equipment.
  • Processing and manufacturing machinery.
  • Industrial installations requiring EMC-compatible isolation.

Technical Specifications

Tick the specs you need, then view products that match.

Material Aluminium
Device Type EMC safety switch
Series OTA ATEX Enclosed Switch-Disconnectors
Order number 1SCA152718R1001
Product group 311019 – Metal Enclosed (Loadbreak)
Product type ATEX EMC enclosed switch-disconnector
Equipment rating 16 A
Number of poles 4
Rated operational current AC-22A at 380–415 V 16 A
Rated operational current AC-22A at 500 V 16 A
Rated operational current AC-22A at 690 V 16 A
Rated operational current AC-23A at 380–415 V 16 A
Rated operational current AC-23A at 500 V 16 A
Rated operational current AC-23A at 690 V 10 A
Motor output AC-23A at 415 V 7.5 kW
Motor output AC-23A at 690 V 7.5 kW
Protection rating IP65
Enclosure material Rigid die-cast aluminium
ATEX classification Ex tc III T70°C Dc
Hazardous area Zone 22
Special function EMC
Handle colour Black
Handle operation I-O / ON-OFF
Cover interlock Included
Auxiliary contacts included 1NO
Maximum auxiliary contacts 2NO+2NC
PE terminal Included
Cable-entry position Top and bottom
Cable outlets per side 2 × M25 + M20
Enclosure dimensions (H × W × D) 165 × 130 × 103 mm
Weight approx. 1.3 kg
ATEX directive 2014/34/EU

Frequently Asked Questions

What is the ABB OTA16S4BX used for?

The ABB OTA16S4BX is a 16 A, 4-pole ATEX EMC enclosed switch-disconnector designed for local load breaking and electrical isolation in industrial applications where combustible dust may create a potentially explosive atmosphere.

What motor rating does the ABB OTA16S4BX support?

The OTA16S4BX has an AC-23A motor rating of 7.5 kW / 16 A at 380–415 V. At 690 V, its AC-23A rating is 7.5 kW / 10 A.

How many poles does the ABB OTA16S4BX have?

The OTA16S4BX has a 4-pole switching configuration, enabling four conductors to be switched and isolated simultaneously.

What ATEX classification does the OTA16S4BX have?

The OTA16S4BX is classified Ex tc III T70°C Dc and is designed for ATEX Zone 22 applications involving potentially explosive dust atmospheres.

What cable entry arrangement does the OTA16S4BX use?

The OTA16S4BX has threaded cable entries at the top and bottom, with 2 × M25 + M20 cable outlets per side. Cable glands and cable-entry plugs are supplied with the enclosed switch.

Trusted ATEX Switching from ABB

ABB OTA ATEX enclosed switch-disconnectors combine dependable electrical isolation, EMC capability and hazardous-area protection with robust aluminium enclosures and practical four-pole switching for demanding industrial applications.