ABB OT630KLAA4C (1SCA022475R1180) 630 A-class four-pole manual changeover switch in an IP54 steel sheet enclosure. Features I-0-II operation, 570 A AC-22A rating up to 690 V, 570 A AC-23A rating up to 415 V, open top-and-bottom cable entries and a black pistol-type operating handle.
£4,961.22
The ABB OT630KLAA4C, manufacturer order number 1SCA022475R1180, is a heavy-duty 630 A-class, four-pole enclosed changeover switch designed for manual selection between two electrical supplies. Part of ABB's Metal Enclosed (Loadbreak) product group, this industrial switching assembly combines a high-capacity changeover mechanism, protective steel sheet enclosure and flexible open cable-entry arrangement.
Unlike a conventional ON/OFF safety isolator, the OT630KLAA4C provides three-position I–0–II operation. This allows an operator to select Supply I, move to the central OFF position, or select Supply II. Its four-pole configuration makes it suitable for appropriately designed three-phase installations requiring switching of an additional conductor, commonly the neutral.
ABB specifies a 570 A rated operational current for AC-22A duties up to 690 V and AC-23A duties up to 415 V. The switch is housed in an IP54 steel sheet enclosure measuring 800 × 1000 × 330 mm, with open top and bottom cable-entry positions. It is supplied with a black pistol-type I–0–II operating handle and protective earth terminals.
The ABB OT630KLAA4C enclosed changeover switch is particularly relevant to industrial power distribution, generator changeover arrangements and other applications requiring manual transfer between two separately engineered electrical sources.
The ABB OT630KLAA4C is designed for electrical installations requiring a manually operated changeover between two supply sources. Its I–0–II operating sequence provides three distinct positions: Supply I connected, both supplies disconnected, and Supply II connected. The intermediate OFF position is an important feature of its open-transition switching arrangement.
The four-pole configuration enables four conductors to be switched together. In many three-phase installations, these are the three phase conductors and a neutral conductor. However, neutral switching requirements depend on the electrical earthing arrangement, source configuration and applicable installation regulations. The suitability of the switch must therefore be established through the overall electrical system design.
Although designated as a 630 A-class changeover switch, the OT630KLAA4C has a published 570 A AC-22A operational current rating up to 690 V and a 570 A AC-23A rating up to 415 V. These utilisation categories represent different electrical load characteristics. Engineers should select the switch using the operational rating applicable to the actual voltage and connected load, rather than relying on the 630 A model classification alone.
The IP54 steel sheet enclosure provides protection against limited dust ingress and water splashes. It is intended for industrial environments where a substantial enclosed switching assembly is required. IP54 does not provide the same level of dust or water protection as IP65, so the installation environment must be assessed accordingly.
A distinguishing feature is the open top-and-bottom cable-entry arrangement. ABB supplies the enclosure without completed cable-entry fittings, allowing the installer to select suitable C-flanges or ring-flanges separately. The selected cable-entry components also contribute to securing the enclosed assembly and maintaining its intended protection rating. Any required parallel connection bars must likewise be ordered separately.
The switch is supplied with a black pistol-type operating handle marked I–0–II and protective earth terminals. Its manual operating mechanism is particularly useful for planned supply transfers and maintenance procedures where an operator needs direct control of the selected source.
The OT630KLAA4C is not an automatic transfer switch and does not independently detect supply failure or initiate a transfer. It also does not replace appropriate overload, short-circuit or other protective devices. Generator and alternative-source installations require correctly engineered source interlocking, earthing, neutral arrangements and protection to prevent unsafe backfeeding or unintended supply paralleling.
Tick the specs you need, then view products that match.
| Device Type | Enclosed changeover switch | |
|---|---|---|
| Voltage | 1000 V AC | |
| Material | Steel |
The ABB OT630KLAA4C is a four-pole manual enclosed changeover switch used to select between two electrical supplies. Typical applications include industrial power distribution and appropriately engineered mains-to-generator changeover systems.
The manufacturer order number is 1SCA022475R1180. The corresponding ABB model is OT630KLAA4C, within product group 311019 – Metal Enclosed (Loadbreak).
The OT630KLAA4C belongs to ABB's 630 A-class OT630 range. Its published rated operational current is 570 A for AC-22A duties up to 690 V and 570 A for AC-23A duties up to 415 V. The applicable operational rating must be used when selecting the switch.
The OT630KLAA4C has four switched poles. In an appropriately designed three-phase installation, these may be used to switch the three phase conductors and the neutral.
I–0–II indicates three operating positions: Supply I connected, both supplies disconnected in the central OFF position, and Supply II connected. This provides manual open-transition changeover between two sources.
The OT630KLAA4C is supplied with an IP54-rated steel sheet enclosure. This provides protection against limited dust ingress and water splashes when the enclosure and cable-entry accessories are correctly installed.
The OT630KLAA4C has open cable-entry positions at both the top and bottom of its enclosure. Compatible C-flanges or ring-flanges must be selected and ordered separately to suit the cable installation.
Yes. The OT630KLAA4C includes a black pistol-type operating handle marked I–0–II for manual source selection.
No. The OT630KLAA4C is a manually operated changeover switch. It does not automatically monitor supply conditions or transfer the load when a power source fails.
ABB's enclosed changeover switch catalogue lists enclosure dimensions of 800 mm wide, 1000 mm high and 330 mm deep, with a catalogue weight of 48 kg.
The ABB OT630KLAA4C combines 630 A-class four-pole switching, a three-position I–0–II manual changeover mechanism, an IP54 steel enclosure and flexible open top-and-bottom cable entries. It provides a substantial enclosed changeover solution for electrical contractors, industrial engineers, panel builders and facilities maintenance teams designing reliable alternative-supply arrangements.