Lovato DM2T0200 solid-core current transformer with a 200/5 A transformation ratio, 23 mm opening, class 1 accuracy and 2 VA burden for industrial current measurement.
£16.84
The Lovato DM2T0200 is a high-quality solid-core current transformer designed for accurate current measurement in industrial switchboards, commercial distribution panels and energy-monitoring systems. Featuring a 200/5 A transformation ratio, it converts primary currents up to 200 A into a standard 5 A secondary output suitable for energy meters, multifunction power analysers, ammeters and protection devices.
Its solid-core construction provides a durable and reliable solution for new electrical installations where the primary conductor can be routed through the transformer during assembly. Suitable for both round conductors and rectangular busbars, the DM2T0200 delivers dependable performance in demanding industrial and commercial applications.
Designed for 50/60 Hz operation, the transformer provides a 2 VA burden at accuracy class 1 and features Faston secondary terminals with DIN rail or screw mounting options. Its compact dimensions make it easy to integrate into modern electrical panels while maintaining reliable current measurement.
Current transformers safely reduce high primary currents into proportional secondary currents suitable for measuring equipment. The Lovato DM2T0200 converts currents up to 200 A into a standard 5 A output, allowing accurate electrical monitoring without connecting measuring devices directly to high-current conductors.
Its solid-core construction makes it ideal for new switchboard assemblies where conductors are installed through the transformer during panel construction. Combined with its compact size and flexible mounting options, it provides dependable long-term performance in industrial power-distribution systems.
Tick the specs you need, then view products that match.
| Mounting Type | DIN rail, Panel / base | |
|---|---|---|
| Rated Primary Current (A) | 200 A | |
| Secondary Current / Output | 5 A | |
| Aperture (mm) | 23 mm | |
| Accuracy Class | Class 1 | |
| Rated Burden (VA) | 2 VA | |
| Device Type | Solid-core CT | |
| Current | 5 A | |
| Manufacturer | Lovato Electric | |
| Series | DM2T | |
| Model | DM2T0200 | |
| Product type | Solid-core current transformer | |
| Primary current | 200 A | |
| Secondary current | 5 A | |
| Transformation ratio | 200/5 A | |
| Opening diameter | 23 mm | |
| Compatible busbars | 30 × 10 mm, 25 × 12.5 mm and 20 × 15 mm | |
| Accuracy class | Class 1 | |
| Rated burden | 2 VA | |
| Operating frequency | 50/60 Hz | |
| Overload withstand | 120% of rated primary current | |
| Rated insulation voltage | 720 V | |
| Insulation class | Class E | |
| Terminal type | Faston | |
| Mounting | DIN rail or screw fixing | |
| Protection rating | IP30 | |
| Operating temperature | -25°C to +50°C | |
| Weight | approx. 130 g | |
| Dimensions | 52 × 46.5 × 56.5 mm | |
| Conformity | IEC/EN/BS 61869-1 and IEC/EN/BS 61869-2 | |
| Certification | CE, UKCA and EAC | |
| EAN | 8013975121801 | |
| HS Code | 85389091 |
The DM2T0200 measures primary currents up to 200 A and provides a standard 5 A secondary output for compatible electrical measuring instruments.
The transformer has a 200/5 A transformation ratio.
No. The DM2T0200 uses a solid-core design, so the conductor must pass through the transformer during installation. For retrofit installations, a split-core transformer is generally more suitable.
The transformer accepts round conductors up to 23 mm diameter and rectangular busbars measuring 30 × 10 mm, 25 × 12.5 mm or 20 × 15 mm.
The transformer can be installed using either DIN rail mounting or screw fixing, providing flexibility for different panel layouts.
Lovato Electric current transformers are trusted by panel builders, electrical contractors and industrial engineers for reliable current measurement, dependable performance and straightforward integration into modern electrical distribution systems.