Chint V9 undervoltage release accessory for compatible Chint NB1, NBH8, NB1L and NBH8LE miniature circuit breakers and RCBOs, designed to trip during undervoltage conditions.
£18.27
The Chint V9 is a compact and reliable undervoltage release accessory designed to protect electrical loads by automatically tripping compatible Chint miniature circuit breakers and RCBOs when the supply voltage drops below a safe operating level. It helps prevent unsafe operation, equipment damage and unexpected restart conditions caused by voltage loss or significant voltage reduction.
Designed for use with compatible Chint NB1, NBH8, NB1L and NBH8LE series protective devices, the V9 mounts to the left-hand side of the MCB or RCBO using a dedicated pin interface. It is suitable for residential, commercial and industrial distribution boards where undervoltage protection and positive safety operation are required.
With a rated control voltage of AC 230 V 50/60 Hz, the Chint V9 prevents breaker closing when the voltage is too low, trips the connected device during undervoltage conditions and allows reliable operation when the voltage returns to the normal operating range.
Undervoltage releases such as the Chint V9 are used to open a connected protective device when the supply voltage falls below an acceptable level. This helps prevent motors, control equipment and connected electrical loads from operating under unsafe voltage conditions.
The V9 also provides positive safety by preventing the connected breaker from being closed when the voltage is too low. This makes it particularly useful in control panels, building services systems and distribution boards where safe restart behaviour and undervoltage protection are important.
Tick the specs you need, then view products that match.
| Device Type | Accessory | |
|---|---|---|
| Manufacturer | Chint | |
| Series | V9 | |
| Model | V9 | |
| Product type | Undervoltage release accessory | |
| Function | Trips compatible breaker during undervoltage conditions | |
| Compatible devices | NB1, NBH8, NB1L and NBH8LE series MCBs and RCBOs | |
| Rated operating voltage | AC 230 V, 50/60 Hz | |
| Operating characteristic | 85% to 110% Ue allows reliable operation | |
| Rated insulation voltage | 500 V | |
| Rated impulse withstand voltage | 4 kV | |
| Dielectric test voltage | 2 kV for 1 minute | |
| Protection degree | IP20 | |
| Pollution degree | 2 | |
| Electrical life | 4,000 operations minimum | |
| Mechanical life | 4,000 operations minimum | |
| Terminal connection | Cable connection | |
| Terminal capacity | 2.5 mm² | |
| Tightening torque | 0.8 N·m | |
| Mounting position | Left side of compatible MCB or RCBO | |
| Mounting type | DIN rail accessory installation | |
| Operating temperature | -5°C to +40°C | |
| Storage temperature | -25°C to +70°C | |
| Dimensions (H × W × D) | approx. 82 × 18 × 49.5 mm | |
| Standard | IEC/EN 60947-5-1 |
The Chint V9 is used to trip compatible Chint MCBs and RCBOs when the supply voltage drops below a safe level, helping protect connected electrical loads.
The V9 is designed for use with compatible Chint NB1, NBH8, NB1L and NBH8LE series miniature circuit breakers and RCBOs.
The Chint V9 is rated for AC 230 V operation at 50/60 Hz.
The V9 trips the connected device when the supply voltage falls within the undervoltage range, typically between 70% and 35% of rated voltage.
The V9 mounts on the left side of a compatible Chint MCB or RCBO using the dedicated pin interface.
Chint V9 undervoltage releases are used by electricians, panel builders and maintenance engineers to provide dependable undervoltage protection and safer operation within low voltage electrical distribution systems.