ABB S-ARC1 M C25 (2CSA275901R9254) arc fault detection device with integrated MCB: 1P+N, C curve, 25 A, 10 kA breaking capacity.
£177.47
The ABB S-ARC1 M C25 is a compact and reliable arc fault detection device (AFDD) with integrated miniature circuit breaker (MCB) designed to protect low-voltage electrical circuits against dangerous arc faults, overloads and short circuits. As part of the ABB S-ARC1 M series, it combines advanced arc fault detection with conventional overcurrent protection in a space-saving two-module device for residential, commercial and other building electrical installations.
The S-ARC1 M C25 monitors the electrical circuit for characteristics associated with hazardous series, parallel and earth arc faults and disconnects the affected circuit when necessary. Its integrated MCB provides overload and short-circuit protection, while continuous internal self-testing and LED indication support reliable operation and make troubleshooting easier following a trip.
With a rated current of 25 A, a C tripping characteristic and a 10 kA breaking capacity, the S-ARC1 M C25 is suitable for circuits where moderate starting or inrush currents may occur. It operates at 230–240 V AC and its compact 1P+N configuration occupies only two modules within a standard DIN rail distribution board.
Arc faults can develop as a result of damaged conductors, deteriorated insulation, loose electrical connections and other installation faults. Because some dangerous arcing conditions may not draw sufficient current to operate conventional overcurrent protection, an AFDD monitors the circuit for electrical characteristics associated with hazardous arcs and disconnects the affected circuit when required.
The ABB S-ARC1 M series combines arc fault detection technology with an integrated miniature circuit breaker. The S-ARC1 M C25 therefore provides protection against series, parallel and earth arc faults as well as overloads and short circuits within a compact two-module enclosure, helping simplify modern electrical distribution-board design.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 25 A | |
| Trip Curve | C curve | |
| Breaking Capacity | 10 kA | |
| Phase | Single Phase | |
| Manufacturer | ABB | |
| Series | S-ARC1 M | |
| Model | S-ARC1 M C25 | |
| Order code | 2CSA275901R9254 | |
| Product type | Arc fault detection device (AFDD) with integrated MCB | |
| Rated current | 25 A | |
| Tripping characteristic | C | |
| Rated voltage | 230–240 V AC | |
| Rated frequency | 50 / 60 Hz | |
| Minimum operating voltage | 170 V AC | |
| Number of poles | 1P+N | |
| Rated breaking capacity | 10 kA | |
| Ultimate short-circuit breaking capacity (Icu) | 10 kA | |
| Service short-circuit breaking capacity (Ics) | 7.5 kA | |
| Rated insulation voltage | 500 V AC | |
| Overvoltage category | III | |
| Overvoltage protection threshold | 275 V | |
| Rated impulse withstand voltage | 4 kV | |
| Pollution degree | 2 | |
| Standards | IEC/EN 62606, IEC/EN 60898-1 | |
| Mounting type | DIN rail mounting | |
| Maximum cable connection | 25 mm² | |
| Maximum busbar connection | 10 mm² | |
| Width | 2 modules / 35 mm | |
| Dimensions (H × W × D) | 85 × 35 × 69 mm | |
| Weight | 0.18 kg |
The ABB S-ARC1 M C25 is used to protect low-voltage electrical circuits against arc faults, overloads and short circuits in residential, commercial and other building electrical installations.
The device has a rated current of 25 A and uses a C tripping characteristic.
The ABB S-ARC1 M C25 has a rated breaking capacity of 10 kA, with a service short-circuit breaking capacity of 7.5 kA.
Yes. The S-ARC1 M C25 combines an arc fault detection device (AFDD) with an integrated miniature circuit breaker (MCB), providing arc fault detection together with overload and short-circuit protection.
The device is designed for DIN rail mounting and occupies two modules, with an overall width of 35 mm. The power supply can be connected from either the top or bottom.
ABB S-ARC1 M arc fault detection devices combine advanced arc fault monitoring with proven miniature circuit breaker technology, providing compact protection against arc faults, overloads and short circuits in modern low-voltage electrical installations.