ABB S-ARC1 M B32 (2CSA275901R9325) arc fault detection device with integrated MCB: 1P+N, B curve, 32 A, 10 kA breaking capacity.
£169.28
The ABB S-ARC1 M B32 is a compact and highly capable arc fault detection device (AFDD) with integrated miniature circuit breaker (MCB) designed to protect low-voltage electrical circuits against dangerous arc faults, overloads and short circuits. As part of the ABB S-ARC1 M series, it combines arc fault detection and overcurrent protection in a space-saving two-module device for residential, commercial and other building electrical installations.
The S-ARC1 M B32 monitors the electrical circuit for characteristics associated with hazardous series, parallel and earth arc faults and disconnects the affected circuit when a dangerous arc condition is detected. Its integrated thermal-magnetic MCB also provides conventional overload and short-circuit protection, allowing multiple protective functions to be incorporated within a single DIN rail device.
With a rated current of 32 A, a B tripping characteristic and a 10 kA rated short-circuit breaking capacity, the S-ARC1 M B32 is suitable for demanding low-voltage final circuits. It operates at a rated voltage of 230–240 V AC and its compact 1P+N configuration occupies only two modules within the distribution board.
Arc faults can develop as a result of damaged conductors, deteriorated insulation, loose electrical connections and other installation faults. Because some dangerous arcing conditions may not cause sufficient current to operate conventional overcurrent protection, an AFDD monitors the circuit for characteristic electrical signatures associated with hazardous arcs and disconnects the affected circuit when necessary.
The ABB S-ARC1 M series combines this arc fault detection technology with an integrated miniature circuit breaker. The S-ARC1 M B32 therefore provides protection against arc faults, overloads and short circuits within a compact two-module enclosure, helping simplify modern electrical distribution-board design while providing enhanced protection against electrically induced fires.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 32 A | |
| Trip Curve | B curve | |
| Breaking Capacity | 10 kA | |
| Phase | Single Phase | |
| Manufacturer | ABB | |
| Series | S-ARC1 M | |
| Model | S-ARC1 M B32 | |
| Order code | 2CSA275901R9325 | |
| Product type | Arc fault detection device (AFDD) with integrated MCB | |
| Rated current | 32 A | |
| Tripping characteristic | B | |
| Rated voltage | 230–240 V AC | |
| Minimum operating voltage | 170 V | |
| Rated frequency | 50 / 60 Hz | |
| Number of poles | 1P+N | |
| Rated short-circuit breaking capacity | 10 kA | |
| Insulation voltage | 500 V AC | |
| Overvoltage category | III | |
| Pollution degree | 2 | |
| Rated impulse withstand voltage | 4 kV | |
| Standards | IEC/EN 62606, IEC/EN 60898-1 | |
| Mounting type | DIN rail mounting | |
| Width | 2 modules / 35 mm | |
| Dimensions (H × W × D) | 85 × 35 × 69 mm | |
| Weight | approx. 0.18 kg | |
| Protection rating | IP40 | |
| Ambient operating temperature | -25 to +55 °C |
The ABB S-ARC1 M B32 is used to protect low-voltage electrical circuits against arc faults, overloads and short circuits in residential, commercial and other building installations.
The device has a rated current of 32 A and uses a B tripping characteristic.
The ABB S-ARC1 M B32 has a rated short-circuit breaking capacity of 10 kA.
Yes. The S-ARC1 M B32 combines an arc fault detection device (AFDD) with an integrated miniature circuit breaker (MCB), providing arc fault detection together with overload and short-circuit protection.
The device is designed for DIN rail mounting and occupies two modules, with an overall width of approximately 35 mm.
ABB S-ARC1 M arc fault detection devices combine advanced arc fault monitoring with miniature circuit breaker technology, providing compact protection against arc faults, overloads and short circuits in modern low-voltage electrical installations.