ABB S-ARC1 C40 (2CSA255901R9404) arc fault detection device with integrated MCB: 1P+N, C curve, 40 A, 6 kA breaking capacity.
£148.81
The ABB S-ARC1 C40 is a compact arc fault detection device (AFDD) with integrated miniature circuit breaker (MCB) designed to provide enhanced protection for single-phase final circuits. As part of the ABB S-ARC1 series, it combines arc fault detection with thermal-magnetic overload and short-circuit protection within a single two-module DIN rail device.
The S-ARC1 is designed to protect end-user circuits against earth, parallel and series arc faults as well as conventional overloads and short-circuit currents. By detecting potentially hazardous electrical arcing that conventional MCB protection alone is not designed to identify, the device provides an additional level of protection against electrical faults associated with damaged conductors, deteriorated insulation and poor connections.
With a rated current of 40 A, a C tripping characteristic and a rated operational voltage of 230–240 V AC, the S-ARC1 C40 is designed for 1P+N single-phase circuits. It provides a 6 kA rated service short-circuit breaking capacity and a 7.5 kA rated ultimate short-circuit breaking capacity, making it suitable for compatible residential and commercial final circuits.
Arc fault detection devices monitor electrical circuits for characteristics associated with potentially dangerous electrical arcing. The ABB S-ARC1 is designed to protect end-user single-phase circuits against earth, parallel and series arc faults, while its integrated miniature circuit breaker provides thermal-magnetic protection against overloads and short-circuit currents.
Combining AFDD and MCB functionality within a compact two-module device helps simplify distribution board design while providing protection against electrical faults that conventional MCBs alone are not designed to detect. The C tripping characteristic of the S-ARC1 C40 also makes it suitable for compatible circuits where moderate starting or inrush currents may occur.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 40 A | |
| Trip Curve | C curve | |
| Breaking Capacity | 6 kA | |
| Phase | Single Phase | |
| Manufacturer | ABB | |
| Series | S-ARC1 | |
| Model | S-ARC1 C40 | |
| Order code / MPN | 2CSA255901R9404 | |
| EAN | 8012542373919 | |
| Product type | Arc fault detection device with integrated MCB | |
| Rated current | 40 A | |
| Tripping characteristic | C | |
| Rated operational voltage | 230–240 V AC | |
| Number of poles | 1P+N | |
| Number of protected poles | 1 | |
| Rated service short-circuit breaking capacity (Ics) | 6 kA | |
| Rated ultimate short-circuit breaking capacity (Icu) | 7.5 kA | |
| Dielectric test voltage | 2.5 kV | |
| Energy limiting class | 3 | |
| Electrical endurance | 10,000 cycles | |
| Mechanical endurance | 20,000 cycles | |
| Contact position indication | Red ON / green OFF | |
| Power supply connection | Top or bottom | |
| Neutral terminal position | Right | |
| Actuator type | Toggle, orange RAL 2004, sealable in ON/OFF positions | |
| Busbar connection capacity | 10 mm² | |
| Rigid conductor capacity | 1–25 mm² | |
| Flexible conductor capacity | 1–16 mm² | |
| Wire stripping length | 12 mm | |
| Mounting type | DIN rail | |
| Terminal type | Screw terminals | |
| Tightening torque | 2.8 N·m | |
| Modular width | 2 modules | |
| Dimensions (H × W × D) | 85 × 35 × 69 mm | |
| Weight | 180 g | |
| Standards | IEC/EN 62606, IEC/EN 60898-1 |
The ABB S-ARC1 C40 is designed to protect compatible single-phase final circuits against earth, parallel and series arc faults, overloads and short circuits using an integrated AFDD and miniature circuit breaker.
The S-ARC1 C40 has a rated current of 40 A and uses a C tripping characteristic, making it suitable for compatible circuits that can experience moderate starting or inrush currents.
No. The S-ARC1 C40 combines an arc fault detection device with an MCB. Where residual current protection is required, suitable additional residual current protection must be provided in accordance with the applicable electrical installation requirements.
The ABB S-ARC1 C40 has a rated operational voltage of 230–240 V AC and uses a 1P+N configuration for single-phase electrical circuits.
The S-ARC1 C40 has a 6 kA rated service short-circuit breaking capacity (Ics) and a 7.5 kA rated ultimate short-circuit breaking capacity (Icu).
ABB S-ARC1 devices combine arc fault detection with thermal-magnetic overcurrent protection in a compact DIN rail format, providing enhanced protection against electrical arcing, overloads and short circuits in residential and commercial installations.