ABB S-ARC1 B25 (2CSA255901R9255) arc fault detection device with integrated MCB: 1P+N, B curve, 25 A, 6 kA breaking capacity.
£156.24
The ABB S-ARC1 B25 is a compact arc fault detection device (AFDD) with integrated miniature circuit breaker (MCB) designed to provide enhanced protection for single-phase final circuits. As part of the ABB S-ARC1 series, it combines arc fault detection with thermal-magnetic overload and short-circuit protection within a single two-module DIN rail device.
The S-ARC1 protects end-user circuits against earth, parallel and series arc faults as well as conventional overloads and short-circuit currents. By detecting electrical arcing that conventional MCB protection alone may not identify, the device provides an additional level of protection against faults associated with damaged conductors, deteriorated insulation and poor electrical connections.
With a rated current of 25 A, a B tripping characteristic and a rated operational voltage of 230–240 V AC, the S-ARC1 B25 is designed for 1P+N single-phase circuits. It provides a 6 kA rated service short-circuit breaking capacity and a 7.5 kA rated ultimate short-circuit breaking capacity, making it suitable for residential and commercial final circuits requiring combined arc fault, overload and short-circuit protection.
Arc fault detection devices monitor electrical circuits for characteristic conditions associated with potentially dangerous electrical arcing. The ABB S-ARC1 is designed to protect against earth, parallel and series arc faults while its integrated miniature circuit breaker provides thermal-magnetic protection against overloads and short-circuit currents.
Combining AFDD and MCB functionality within a compact two-module device helps simplify distribution board design while providing protection against electrical faults that conventional MCBs alone are not designed to detect. The S-ARC1 series is designed for residential and commercial applications where enhanced protection of single-phase final circuits is required.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 25 A | |
| Trip Curve | B curve | |
| Breaking Capacity | 6 kA | |
| Phase | Single Phase | |
| Manufacturer | ABB | |
| Series | S-ARC1 | |
| Model | S-ARC1 B25 | |
| Order code / MPN | 2CSA255901R9255 | |
| EAN | 8012542341116 | |
| Product type | Arc fault detection device with integrated MCB | |
| Rated current | 25 A | |
| Tripping characteristic | B | |
| Rated operational voltage | 230–240 V AC | |
| Input voltage type | AC | |
| Number of poles | 1P+N | |
| Number of protected poles | 1 | |
| Rated service short-circuit breaking capacity (Ics) | 6 kA | |
| Rated ultimate short-circuit breaking capacity (Icu) | 7.5 kA | |
| Rated insulation voltage (Ui) | 500 V | |
| Rated impulse withstand voltage (Uimp) | 4 kV | |
| Dielectric test voltage | 2.5 kV | |
| Energy limiting class | 3 | |
| Electrical endurance | 10,000 cycles | |
| Mechanical endurance | 20,000 cycles | |
| Contact position indication | Red ON / green OFF | |
| Power supply connection | Arbitrary | |
| Actuator type | Toggle, orange RAL 2004, sealable in ON/OFF positions | |
| Busbar connection capacity | 10 mm² | |
| Rigid conductor capacity | 1–25 mm² | |
| Flexible conductor capacity | 1–16 mm² | |
| Wire stripping length | 12 mm | |
| Mounting type | DIN rail | |
| Terminal type | Screw terminals | |
| Tightening torque | 2.8 N·m | |
| Modular width | 2 modules | |
| Dimensions (H × W × D) | 85 × 35 × 69 mm | |
| Weight | 180 g | |
| Standards | IEC/EN 62606, IEC/EN 60898-1 |
The ABB S-ARC1 B25 is used to protect single-phase final circuits against earth, parallel and series arc faults, overloads and short circuits using an integrated AFDD and miniature circuit breaker.
The S-ARC1 B25 has a rated current of 25 A and uses a B tripping characteristic, making it suitable for compatible circuits with relatively low starting or inrush currents.
No. The S-ARC1 B25 combines an arc fault detection device with an MCB. Where residual current protection is required, suitable additional residual current protection must be provided in accordance with the applicable electrical installation requirements.
The S-ARC1 B25 has a rated operational voltage of 230–240 V AC and is designed for 1P+N single-phase electrical circuits.
The S-ARC1 B25 has a 6 kA rated service short-circuit breaking capacity (Ics) and a 7.5 kA rated ultimate short-circuit breaking capacity (Icu).
ABB S-ARC1 devices combine arc fault detection with thermal-magnetic overcurrent protection in a compact DIN rail format, providing enhanced protection against electrical arcing, overloads and short circuits in residential and commercial installations.