ABB S-ARC1 B13 (2CSA255901R9135) arc fault detection device with integrated MCB: 1P+N, B curve, 13 A, 6 kA breaking capacity.
£141.74
The ABB S-ARC1 B13 is a compact arc fault detection device (AFDD) with integrated miniature circuit breaker (MCB) designed to provide enhanced protection for single-phase final circuits. As part of the ABB S-ARC1 series, it combines arc fault detection with thermal-magnetic overload and short-circuit protection within a single two-module DIN rail device.
The S-ARC1 is designed to protect against earth, parallel and series arc faults as well as conventional short-circuit currents and overloads. This integrated approach enables potentially hazardous electrical arcing to be detected while retaining the familiar overcurrent protection functions of an MCB, helping simplify protection within residential and commercial distribution boards.
With a rated current of 13 A, a B tripping characteristic and a rated operational voltage of 230–240 V AC, the S-ARC1 B13 is designed for 1P+N single-phase circuits. Its 6 kA breaking capacity and compact construction make it suitable for final circuits requiring combined arc fault, overload and short-circuit protection.
Arc fault detection devices monitor electrical circuits for characteristic conditions associated with potentially dangerous electrical arcing. The ABB S-ARC1 is designed to detect earth, parallel and series arc faults while its integrated miniature circuit breaker provides thermal-magnetic protection against overloads and short circuits.
Combining AFDD and MCB functionality within a compact two-module device helps simplify distribution board design while providing protection against electrical faults that conventional MCBs alone are not designed to detect. The S-ARC1 range is designed for use in modern residential and commercial electrical installations where enhanced final-circuit protection is required.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 13 A | |
| Trip Curve | B curve | |
| Breaking Capacity | 6 kA | |
| Phase | Single Phase | |
| Manufacturer | ABB | |
| Series | S-ARC1 | |
| Model | S-ARC1 B13 | |
| Order code / MPN | 2CSA255901R9135 | |
| EAN | 8012542750031 | |
| Product type | Arc fault detection device with integrated MCB | |
| Rated current | 13 A | |
| Tripping characteristic | B | |
| Rated operational voltage | 230–240 V AC | |
| Number of poles | 1P+N | |
| Breaking capacity | 6 kA | |
| Rated insulation voltage (Ui) | 500 V | |
| Rated impulse withstand voltage (Uimp) | 4 kV | |
| Dielectric test voltage | 2.5 kV | |
| Voltage drop | 166 mV | |
| Internal resistance | 12.8 mΩ | |
| Power loss | 2.2 W | |
| Internal consumption | 0.5 W | |
| Protection rating | IP20 terminals / IP40 housing | |
| Tripping mechanism | Thermal-magnetic | |
| Mounting type | DIN rail | |
| Terminal type | Screw terminals | |
| Reset actuator type | Toggle switch | |
| Modular width | 2 modules | |
| Dimensions (H × W × D) | 85 × 35 × 69 mm | |
| Weight | 180 g | |
| Standards | IEC/EN 62606, IEC/EN 60898-1 |
The ABB S-ARC1 B13 is used to protect single-phase final circuits against earth, parallel and series arc faults, overloads and short circuits using an integrated AFDD and miniature circuit breaker.
The S-ARC1 B13 has a rated current of 13 A and uses a B tripping characteristic.
No. The S-ARC1 B13 combines an arc fault detection device with an MCB. Where residual current protection is required, suitable additional RCD protection must be provided in accordance with the applicable electrical installation requirements.
The S-ARC1 B13 has a rated operational voltage of 230–240 V AC and is designed for 1P+N single-phase electrical circuits.
The ABB S-ARC1 B13 has a 6 kA short-circuit breaking capacity, providing integrated overcurrent protection alongside its arc fault detection functionality.
ABB S-ARC1 devices combine arc fault detection with thermal-magnetic overcurrent protection in a compact DIN rail format, providing enhanced protection against electrical arcing, overloads and short circuits in residential and commercial installations.