Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S-ARC1 B10 (2CSA255901R9105) arc fault detection device with integrated MCB: 1P+N, B curve, 10 A, 6 kA breaking capacity.
£141.74
The ABB S-ARC1 B10 is a compact arc fault detection device (AFDD) with integrated miniature circuit breaker (MCB) designed to protect single-phase final circuits against electrical arc faults and overcurrents. As part of the ABB S-ARC1 series, it combines AFDD and thermal-magnetic circuit protection within a single two-module DIN rail device.
The S-ARC1 provides protection against series, parallel and earth arc faults as well as short circuits and overloads. By combining these protective functions in one device, it helps reduce the space required within distribution boards while providing enhanced protection against electrical faults that conventional miniature circuit breakers alone are not designed to detect.
With a rated current of 10 A, a B tripping characteristic and a rated operational voltage of 230–240 V AC, the S-ARC1 B10 is designed for 1P+N single-phase circuits. It provides a 6 kA rated service short-circuit breaking capacity and a 7.5 kA rated ultimate short-circuit breaking capacity, making it suitable for residential and commercial final-circuit protection.
Arc fault detection devices monitor electrical circuits for characteristic current patterns associated with potentially dangerous electrical arcing. The ABB S-ARC1 is designed to detect series, parallel and earth arc faults while its integrated miniature circuit breaker provides conventional thermal-magnetic protection against overloads and short circuits.
Combining AFDD and MCB functionality in a two-module device helps simplify distribution board design and provides enhanced protection for final circuits without requiring separate arc fault and overcurrent protection devices. The S-ARC1 range is designed for residential and commercial applications and complies with relevant AFDD and miniature circuit breaker standards.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 10 A | |
| Trip Curve | B curve | |
| Breaking Capacity | 6 kA | |
| Phase | Single Phase | |
| Manufacturer | ABB | |
| Series | S-ARC1 | |
| Model | S-ARC1 B10 | |
| Order code / MPN | 2CSA255901R9105 | |
| EAN | 8012542178132 | |
| Product type | Arc fault detection device with integrated MCB | |
| Rated current | 10 A | |
| Tripping characteristic | B | |
| Rated operational voltage | 230–240 V AC | |
| Rated frequency | 50–60 Hz | |
| Number of poles | 1P+N | |
| Number of protected poles | 1 | |
| Rated service short-circuit breaking capacity (Ics) | 6 kA | |
| Rated ultimate short-circuit breaking capacity (Icu) | 7.5 kA | |
| Rated insulation voltage (Ui) | 500 V | |
| Rated impulse withstand voltage (Uimp) | 4 kV | |
| Power loss | 2 W | |
| Protection rating | IP20 terminals / IP40 housing | |
| Pollution degree | 2 | |
| Operating temperature | -25 to +55 °C | |
| Contact position indication | Red ON / green OFF | |
| Actuator type | Toggle, orange RAL 2004, sealable in ON/OFF position | |
| Mounting type | DIN rail | |
| Terminal type | Screw terminals | |
| Tightening torque | 2.8 N·m | |
| Modular width | 2 modules | |
| Dimensions (H × W × D) | 85 × 35 × 69 mm | |
| Weight | 180 g | |
| Standards | IEC/EN 62606, IEC/EN 60898-1 |
The ABB S-ARC1 B10 is used to protect single-phase final circuits against series, parallel and earth arc faults, overloads and short circuits using an integrated AFDD and miniature circuit breaker.
The S-ARC1 B10 has a rated current of 10 A and uses a B tripping characteristic.
No. The S-ARC1 B10 combines an arc fault detection device with an MCB. Where residual current protection is required, the installation must use suitable additional residual current protection in accordance with the applicable electrical installation requirements.
The S-ARC1 B10 has a rated operational voltage of 230–240 V AC and is designed for 1P+N single-phase electrical circuits.
The S-ARC1 B10 has a 6 kA rated service short-circuit breaking capacity (Ics) and a 7.5 kA rated ultimate short-circuit breaking capacity (Icu).
ABB S-ARC1 devices combine arc fault detection with thermal-magnetic overcurrent protection in a compact DIN rail format, providing enhanced protection against electrical arcing, overloads and short circuits in residential and commercial installations.