Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato P1RE1NB32A030 is a 32 A 1P+N type A RCBO with a B tripping curve, 30 mA residual-current rating, 230 V AC operational voltage and 10 kA IEC short-circuit rating.
£94.85
The Lovato P1RE1NB32A030 is a 1P+N residual current circuit breaker with overcurrent protection (RCBO) that combines residual-current, overload and short-circuit protection in a single modular device. Part of the Lovato P1RE range, it has a rated current of 32 A and an IEC short-circuit rating of 10 kA.
This model combines a B tripping curve with a type A residual-current characteristic and a rated residual operating current of 30 mA. The type A characteristic is designed to respond to sinusoidal AC and pulsating DC residual currents, providing appropriate residual-current detection for suitably specified single-phase electrical circuits.
Rated for 230 V AC at 50/60 Hz, the P1RE1NB32A030 occupies two DIN modules and mounts on a standard 35 mm DIN rail. Its compact combined-protection design makes it suitable for distribution boards and control panels where individual circuit protection and efficient use of enclosure space are required.
An RCBO combines the protective functions of a miniature circuit breaker and a residual-current device within one unit. The P1RE1NB32A030 therefore provides protection against overloads and short circuits while simultaneously monitoring the circuit for residual current to earth, allowing combined protection to be provided by a single two-module device.
The 30 mA type A residual-current characteristic responds to sinusoidal AC and pulsating DC residual currents, while the B curve defines the device's overcurrent tripping behaviour. With its 32 A nominal current, 10 kA short-circuit rating and DIN-rail construction, the P1RE1NB32A030 provides a compact protection solution for suitably designed 230 V AC circuits.
Tick the specs you need, then view products that match.
| Phase | Single Phase | |
|---|---|---|
| Poles | 1-pole + N | |
| Device Type | RCBO | |
| Trip Curve | B curve | |
| Residual Current | 30 mA | |
| Manufacturer | Lovato Electric | |
| Series | P1RE | |
| Model / order code | P1RE1NB32A030 | |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) | |
| Number of poles | 1P+N | |
| Number of DIN modules | 2 | |
| Rated operational voltage | 230 V AC | |
| Rated insulation voltage (Ui) | 400 V | |
| Rated impulse withstand voltage (Uimp) | 4 kV | |
| Rated frequency | 50/60 Hz | |
| Rated current (In) | 32 A | |
| Tripping curve | B | |
| Residual operation characteristic | Type A | |
| Rated residual current (IΔn) | 30 mA | |
| IEC short-circuit rating | 10 kA | |
| Electrical life | 10,000 cycles | |
| Mechanical life | 20,000 cycles | |
| Mounting | 35 mm DIN rail | |
| Normal operating position | Vertical plane | |
| Maximum terminal tightening torque | 2 Nm | |
| Terminal tool | PZ2 | |
| IEC conductor cross-section | 1–16 mm² | |
| Operating temperature | -25 to +60 °C | |
| Storage temperature | -40 to +80 °C | |
| Maximum altitude | 2000 m | |
| Front protection rating | IP20 | |
| Pollution degree | 2 | |
| Weight | 205 g | |
| ETIM classification | EC000905 – Earth leakage circuit breaker | |
| Compliance | IEC/EN/BS 61009-1, IEC/EN/BS 61009-2-1 | |
| Package quantity | 1 | |
| Package dimensions | 115 × 40 × 80 mm | |
| EAN-13 | 8013975329146 | |
| HS code | 85363030 |
The P1RE1NB32A030 is a 1P+N RCBO combining residual-current, overload and short-circuit protection in a compact two-module DIN-rail device.
The Lovato P1RE1NB32A030 has a rated current of 32 A.
The P1RE1NB32A030 has a rated residual operating current of 30 mA.
Yes. It has a type A residual-current characteristic, designed to respond to sinusoidal AC residual currents and pulsating DC residual currents.
The P1RE1NB32A030 uses a B tripping curve for its overcurrent protection function.
The P1RE1NB32A030 has an IEC short-circuit rating of 10 kA.
The device has a rated operational voltage of 230 V AC and a rated frequency of 50/60 Hz.
The RCBO occupies two DIN modules and is designed for mounting on a standard 35 mm DIN rail.
Lovato Electric P1RE RCBOs provide compact combined residual-current and overcurrent protection for electrical distribution systems, helping panel builders, electrical contractors and industrial users create coordinated DIN-rail protection assemblies.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.