Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato P1RE1NB10A300 is a 10 A 1P+N type A RCBO with a type B overcurrent tripping curve, 300 mA residual-current rating and 10 kA IEC short-circuit breaking capacity.
£90.21
The Lovato P1RE1NB10A300 is a 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed to combine residual-current, overload and short-circuit protection in a single modular device. Part of the Lovato P1RE range, it is rated at 10 A with a 10 kA short-circuit breaking capacity.
This model features a type B tripping curve and type A residual-current characteristic, allowing it to detect sinusoidal AC residual currents as well as pulsating DC residual currents. Its rated residual operating current of 300 mA makes it suitable for appropriately designed installations requiring this residual-current threshold.
The P1RE1NB10A300 occupies two DIN modules and mounts on a standard 35 mm DIN rail. The 1P+N configuration switches the phase and neutral conductors, while dedicated indication and operating features help distinguish residual-current operation from overload or short-circuit tripping.
An RCBO combines the functions normally provided by a miniature circuit breaker and a residual current device. The Lovato P1RE1NB10A300 can disconnect the protected circuit in response to overloads and short circuits while also monitoring for residual current to earth, reducing the number of separate protective devices required within a distribution assembly.
The type B overcurrent curve provides the instantaneous tripping characteristics associated with B-curve circuit protection, while the type A residual-current characteristic responds to both sinusoidal AC and pulsating DC residual currents. Its 300 mA IΔn rating should be selected according to the protection requirements and applicable electrical regulations for the installation.
Tick the specs you need, then view products that match.
| Phase | Single Phase | |
|---|---|---|
| Poles | 1-pole + N | |
| Device Type | RCBO | |
| Trip Curve | B curve | |
| Breaking Capacity | 10 kA | |
| Residual Current | 300 mA | |
| HS Code | 85362010 | |
| Manufacturer | Lovato Electric | |
| Series | P1RE | |
| Model / order code | P1RE1NB10A300 | |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) | |
| Number of poles | 1P+N | |
| Rated current (In) | 10 A | |
| Tripping curve | B | |
| Residual-current characteristic | Type A | |
| Rated residual operating current (IΔn) | 300 mA | |
| IEC short-circuit breaking capacity (Icn) | 10 kA | |
| Number of DIN modules | 2 | |
| Mounting | 35 mm DIN rail | |
| Protection functions | Residual current, overload and short circuit | |
| Residual-current detection | Sinusoidal AC and pulsating DC residual currents | |
| Contact status indication | Yes | |
| Compliance | IEC |
The P1RE1NB10A300 is a 1P+N RCBO combining residual-current protection with overload and short-circuit protection in a two-module DIN-rail device.
The Lovato P1RE1NB10A300 has a rated current of 10 A.
The RCBO has a rated residual operating current of 300 mA.
Yes. The P1RE1NB10A300 has a type A residual-current characteristic, designed to respond to sinusoidal AC residual currents and pulsating DC residual currents.
The P1RE1NB10A300 uses a type B overcurrent tripping curve.
The P1RE1NB10A300 has an IEC short-circuit breaking capacity of 10 kA.
The device occupies two DIN modules and is designed for mounting on a standard 35 mm DIN rail.
Lovato Electric P1RE RCBOs combine residual-current monitoring with overload and short-circuit protection in compact DIN-rail devices, providing coordinated circuit protection for industrial, commercial and building electrical distribution systems.
We use cookies