Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato P1RE1NB10A030 is a 10 A 1P+N Type A RCBO with B tripping curve, 30 mA residual current sensitivity and 10 kA short-circuit breaking capacity for combined earth-leakage and overcurrent protection.
£94.85
The Lovato P1RE1NB10A030 is a compact and reliable 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect electrical circuits against earth leakage, overloads and short circuits. As part of the Lovato P1RE MCB and RCD device range, it combines residual current and overcurrent protection within a single DIN rail-mounted device.
This RCBO features a 10 A rated current, B tripping curve and 30 mA rated residual operating current. Its Type A residual current characteristic enables detection of sinusoidal AC and pulsating DC residual currents, making it suitable for modern circuits supplying electrical and electronic equipment.
With a 230 V AC rated operational voltage and 10 kA short-circuit breaking capacity, the P1RE1NB10A030 provides comprehensive protection in a compact 1P+N configuration. Its DIN rail format makes it suitable for distribution boards, control panels and electrical installations where dependable combined circuit protection is required.
RCBOs such as the Lovato P1RE1NB10A030 combine the functions of a miniature circuit breaker and a residual current protective device. The RCBO disconnects the protected circuit when excessive current occurs because of an overload or short circuit, while simultaneously monitoring for residual current leakage to earth.
The P1RE series provides these protective functions in a compact DIN rail format, reducing the need for separate MCB and RCD devices. With its 30 mA Type A residual current protection, the P1RE1NB10A030 is particularly suitable for final circuits where additional protection against electric shock and compatibility with modern electronic loads are required.
Tick the specs you need, then view products that match.
| Phase | Single Phase | |
|---|---|---|
| Poles | 1-pole + N | |
| Device Type | RCBO | |
| Trip Curve | B curve | |
| Breaking Capacity | 10 kA | |
| Residual Current | 30 mA | |
| RCD Type | Type A | |
| HS Code | 85362010 | |
| Manufacturer | Lovato Electric | |
| Series | P1RE | |
| Model | P1RE1NB10A030 | |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) | |
| Number of poles | 1P+N | |
| Rated current In | 10 A | |
| Tripping curve | B | |
| Residual current type | Type A | |
| Rated residual operating current IΔn | 30 mA | |
| Short-circuit breaking capacity | 10 kA | |
| Rated operational voltage Ue | 230 V AC | |
| Rated frequency | 50/60 Hz | |
| Rated insulation voltage Ui | 400 V | |
| Rated impulse withstand voltage Uimp | 4 kV | |
| Mounting type | 35 mm DIN rail | |
| Standards | IEC/EN/BS 61009-1 and IEC/EN/BS 61009-2-1 |
The P1RE1NB10A030 is an RCBO designed to protect electrical circuits against earth leakage, overloads and short circuits using a single DIN rail-mounted protective device.
The P1RE1NB10A030 has a rated current of 10 A and uses a B tripping curve.
The RCBO has a rated residual operating current of 30 mA, providing additional residual current protection for electrical circuits.
Type A means the RCBO is designed to detect sinusoidal AC residual currents as well as pulsating DC residual currents that can be produced by modern electronic equipment.
The P1RE1NB10A030 has a 10 kA short-circuit breaking capacity, providing robust protection against high prospective fault currents.
Lovato Electric P1RE RCBOs provide electrical installers, panel builders and industrial engineers with compact combined protection against residual current faults, overloads and short circuits in modern electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.