Lovato P1RD4P25A030 is a four-pole 25 A Type A residual current circuit breaker with 30 mA residual-current sensitivity and a 230/400 V AC operational voltage rating for earth-leakage protection in electrical installations.
£164.13
The Lovato P1RD4P25A030 is a four-pole Type A residual current circuit breaker (RCCB) designed to provide residual-current protection in industrial, commercial and electrical distribution systems. Part of the Lovato P1RD range, it combines a 25 A rated current with a sensitive 30 mA rated residual operating current for dependable earth-leakage protection.
Its Type A residual-current characteristic enables detection of sinusoidal AC residual currents and pulsating DC residual currents, making the P1RD4P25A030 suitable for modern electrical installations containing compatible electronic equipment. The device is rated for 230/400 V AC at 50/60 Hz and has a 10 kA rated conditional short-circuit current when installed with the appropriate protective arrangement.
With a compact four-module, four-pole construction, 35 mm DIN rail mounting and IP20 frontal protection, the P1RD4P25A030 integrates efficiently into distribution boards and control panels where coordinated four-pole residual-current protection is required.
The Lovato P1RD4P25A030 monitors the current balance between the conductors passing through the RCCB and disconnects the protected circuit when residual current reaches the device's operating threshold. Its 30 mA sensitivity makes it suitable for applications requiring sensitive residual-current protection as part of a correctly designed electrical installation.
The Type A characteristic provides detection of sinusoidal AC and pulsating DC residual currents, while the four-pole arrangement supports coordinated disconnection in compatible multi-pole systems. As an RCCB, the P1RD4P25A030 is specifically intended for residual-current protection; appropriate overcurrent protective devices should also be provided where overload and short-circuit protection are required.
Tick the specs you need, then view products that match.
| Phase | Three Phase | |
|---|---|---|
| Poles | 4-pole | |
| Device Type | RCD | |
| Residual Current | 30 mA | |
| RCD Type | Type A | |
| Manufacturer | Lovato Electric | |
| Series | P1RD | |
| Model | P1RD4P25A030 | |
| Product type | Residual current circuit breaker (RCCB) | |
| Number of poles | 4P | |
| Number of DIN modules | 4 | |
| Rated current In | 25 A | |
| Residual operation characteristic | Type A | |
| Rated residual current IΔn | 30 mA | |
| Rated operational voltage | 230/400 V AC | |
| Rated insulation voltage Ui | 400 V | |
| Rated impulse withstand voltage Uimp | 4 kV | |
| Rated frequency | 50/60 Hz | |
| Short-circuit rating (IEC) | 10 kA | |
| Rated conditional short-circuit current Inc | 10 kA | |
| Electrical life | 10,000 cycles | |
| Mechanical life | 20,000 cycles | |
| Operating temperature | -35 to +70 °C | |
| Storage temperature | -40 to +80 °C | |
| Maximum altitude | 2,000 m | |
| Conductor section | 2.5–35 mm² | |
| Maximum terminal tightening torque | 2 Nm | |
| Terminal tool | PZ2 | |
| Mounting | 35 mm DIN rail | |
| Normal operating position | Vertical plane | |
| Frontal protection rating | IP20 | |
| Pollution degree | 2 | |
| Compliance | IEC | |
| ETIM classification | EC000003 – Residual current circuit breaker (RCCB) | |
| Weight | 326 g | |
| EAN | 8013975269329 | |
| HS code | 85363030 |
The P1RD4P25A030 is a four-pole Type A residual current circuit breaker (RCCB) rated at 25 A with a 30 mA rated residual operating current.
The Lovato P1RD4P25A030 has a rated current of 25 A.
The P1RD4P25A030 has a rated residual current IΔn of 30 mA.
Type A means the RCCB is designed to respond to sinusoidal AC residual currents and pulsating DC residual currents, making it suitable for compatible modern electrical loads and installations.
The P1RD4P25A030 has a rated operational voltage of 230/400 V AC and a rated frequency of 50/60 Hz.
No. The P1RD4P25A030 is an RCCB intended for residual-current protection. Appropriate overcurrent protection should be provided separately where overload and short-circuit protection are required.
The P1RD4P25A030 mounts on a standard 35 mm DIN rail and occupies four DIN modules within a suitable electrical distribution board or enclosure.
Lovato Electric residual current circuit breakers provide dependable earth-leakage protection for modern electrical installations, helping panel builders, machine manufacturers and electrical professionals create reliable industrial and commercial distribution systems.