Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato P1RD2P63A300S is a 2-pole 63 A Type A selective residual current circuit breaker with 300 mA sensitivity, Type S time-delayed tripping, a 230 V AC operational rating and a 10 kA conditional short-circuit current rating.
£165.47
The Lovato P1RD2P63A300S is a 2-pole selective residual current circuit breaker (RCCB) designed to provide dependable earth leakage protection with time-delayed selective tripping. As part of the Lovato P1RD series, it combines Type A residual current detection with Type S selectivity, making it suitable for coordinated protection in industrial, commercial and electrical distribution systems.
Rated at 63 A with a selective rated residual current of 300 mA, the P1RD2P63A300S uses a Type A selective characteristic. Type A operation enables detection of sinusoidal alternating and pulsating DC residual currents, while its Type S time-delay characteristic is designed to support selectivity with downstream residual current protection devices.
The P1RD2P63A300S operates at 230 V AC and 50/60 Hz, with a 10 kA short-circuit rating and 10 kA rated conditional short-circuit current. Its two-pole, two-module construction mounts directly onto a standard 35 mm DIN rail, providing a compact solution for coordinated residual current protection in distribution boards and electrical control systems.
Selective residual current circuit breakers such as the Lovato P1RD2P63A300S provide time-delayed residual current protection for electrical distribution systems where coordination between upstream and downstream protective devices is required. The Type S selective characteristic delays operation so that an appropriately coordinated downstream residual current device can clear a localised earth leakage fault before the upstream RCCB disconnects a larger section of the installation.
The Type A characteristic enables detection of both sinusoidal alternating residual currents and pulsating DC residual currents that can occur with electronic equipment. Combined with its 300 mA selective sensitivity, 63 A current rating and Type S time delay, the P1RD2P63A300S is well suited to appropriately designed distribution systems requiring selective residual current protection. As an RCCB, it should be coordinated with suitable overcurrent and short-circuit protection.
Tick the specs you need, then view products that match.
| Poles | 2-pole | |
|---|---|---|
| Device Type | RCD | |
| Residual Current | 300 mA | |
| Manufacturer | Lovato Electric | |
| Series | P1RD | |
| Model | P1RD2P63A300S | |
| Product type | Selective residual current circuit breaker (RCCB) | |
| Number of poles | 2P | |
| Number of DIN modules | 2 | |
| Rated current In | 63 A | |
| Residual operation characteristic | Type A selective | |
| Time-delay tripping | Type S selective | |
| Rated residual current IΔn | 300 mA selective | |
| Rated operational voltage | 230 V AC | |
| Rated insulation voltage Ui | 400 V | |
| Rated impulse withstand voltage Uimp | 4 kV | |
| Rated frequency | 50/60 Hz | |
| Short-circuit rating (IEC) | 10 kA | |
| Rated conditional short-circuit current Inc | 10 kA | |
| Compliance | IEC | |
| Electrical life | 10,000 cycles | |
| Mechanical life | 20,000 cycles | |
| Operating temperature | -35 to +70 °C | |
| Storage temperature | -40 to +80 °C | |
| Maximum altitude | 2,000 m | |
| Operating position | Vertical plane | |
| Mounting type | 35 mm DIN rail | |
| Maximum terminal tightening torque | 2 Nm | |
| Terminal tool | PZ2 | |
| IEC conductor cross-section | 2.5–35 mm² | |
| Conductor size | AWG 14 to 2 | |
| Weight | 185 g | |
| Frontal protection rating | IP20 | |
| Pollution degree | 2 | |
| EAN | 8013975312919 | |
| HS code | 85362010 |
The P1RD2P63A300S is a 2-pole selective residual current circuit breaker designed for earth leakage protection in electrical distribution systems where time-delayed selective operation is required.
The Lovato P1RD2P63A300S has a rated current of 63 A and a selective rated residual operating current of 300 mA.
Type A means the RCCB detects sinusoidal alternating and pulsating DC residual currents. The selective version also incorporates Type S time-delayed tripping to support coordination with appropriately selected downstream residual current devices.
The P1RD2P63A300S has a rated operational voltage of 230 V AC, a rated insulation voltage of 400 V and a rated frequency of 50/60 Hz.
The selective RCCB occupies two DIN modules and mounts onto a standard 35 mm DIN rail. It should be coordinated with suitable downstream residual current devices and appropriate overcurrent and short-circuit protection according to the requirements of the installation.
Lovato Electric P1RD selective residual current circuit breakers provide dependable earth leakage protection for coordinated electrical distribution systems, combining Type A detection, Type S selective time-delay tripping and compact DIN rail installation for professional industrial and commercial applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.