Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato P1RD2P25AC300 is a 2-pole 25 A Type AC residual current circuit breaker with 300 mA sensitivity, a 230 V AC operational rating and a 10 kA conditional short-circuit current rating for residual current protection.
£71.63
The Lovato P1RD2P25AC300 is a 2-pole residual current circuit breaker (RCCB) designed to provide reliable earth leakage and residual current protection in electrical installations. As part of the Lovato P1RD series, it combines a compact two-module format with IEC compliance, making it suitable for distribution boards, industrial control panels and electrical systems requiring dependable residual current protection.
Rated at 25 A with a rated residual operating current of 300 mA, the P1RD2P25AC300 is designed to detect Type AC residual currents. Its Type AC residual operating characteristic responds to sinusoidal alternating residual currents, making it suitable for appropriately specified circuits where protection against earth leakage and associated fault risks is required.
The P1RD2P25AC300 operates at 230 V AC and 50/60 Hz, with a 10 kA conditional short-circuit current rating. Its two-pole, two-module construction mounts directly onto a standard 35 mm DIN rail, providing straightforward integration into electrical distribution equipment, machinery and control cabinets.
Residual current circuit breakers such as the Lovato P1RD2P25AC300 monitor the balance of current flowing through the conductors of an electrical circuit and disconnect the supply when residual current exceeds the specified threshold. This provides an important protective measure against earth leakage faults and helps reduce risks associated with insulation failure and leakage currents.
The Type AC characteristic is designed to detect sinusoidal alternating residual currents. With its 300 mA sensitivity, 25 A current rating and two-pole configuration, the P1RD2P25AC300 is suited to appropriately designed installations requiring residual current protection at this threshold. As an RCCB, it should be coordinated with suitable overcurrent and short-circuit protection according to the requirements of the installation.
Tick the specs you need, then view products that match.
| Poles | 2-pole | |
|---|---|---|
| Device Type | RCD | |
| Residual Current | 300 mA | |
| RCD Type | Type AC | |
| Manufacturer | Lovato Electric | |
| Series | P1RD | |
| Model | P1RD2P25AC300 | |
| Product type | Residual current circuit breaker (RCCB) | |
| Number of poles | 2P | |
| Number of DIN modules | 2 | |
| Rated current In | 25 A | |
| Residual operation characteristic | Type AC | |
| Rated residual current IΔn | 300 mA | |
| Rated operational voltage | 230 V AC | |
| Rated insulation voltage Ui | 400 V | |
| Rated impulse withstand voltage Uimp | 4 kV | |
| Rated frequency | 50/60 Hz | |
| Short-circuit rating (IEC) | 10 kA | |
| Rated conditional short-circuit current Inc | 10 kA | |
| Compliance | IEC | |
| Electrical life | 10,000 cycles | |
| Mechanical life | 20,000 cycles | |
| Operating temperature | -35 to +70 °C | |
| Storage temperature | -40 to +80 °C | |
| Maximum altitude | 2,000 m | |
| Operating position | Vertical plane | |
| Mounting type | 35 mm DIN rail | |
| Maximum terminal tightening torque | 2 Nm | |
| Terminal tool | PZ2 | |
| IEC conductor cross-section | 2.5–35 mm² | |
| Conductor size | AWG 14 to 2 | |
| Weight | 185 g | |
| Frontal protection rating | IP20 | |
| Pollution degree | 2 | |
| EAN | 8013975269237 | |
| HS code | 85363030 |
The P1RD2P25AC300 is a 2-pole residual current circuit breaker designed to detect residual current and disconnect the electrical supply when leakage exceeds its specified 300 mA operating threshold.
The Lovato P1RD2P25AC300 has a rated current of 25 A and a rated residual operating current of 300 mA.
Type AC means the RCCB is designed to respond to sinusoidal alternating residual currents. The suitability of Type AC protection should be assessed against the characteristics of the connected loads and the requirements of the electrical installation.
The P1RD2P25AC300 has a rated operational voltage of 230 V AC, a rated insulation voltage of 400 V and a rated frequency of 50/60 Hz.
The RCCB occupies two DIN modules and is designed for mounting onto a standard 35 mm DIN rail. As an RCCB, it should be coordinated with suitable overcurrent and short-circuit protection according to the requirements of the electrical installation.
Lovato Electric P1RD residual current circuit breakers provide dependable earth leakage protection for electrical distribution applications, combining residual current detection, compact DIN rail installation and robust electrical performance for professional industrial and commercial electrical systems.