Lovato P1MBUH3PD12 is a 12 A three-pole D-curve miniature circuit breaker rated for 480Y/277 V AC under UL with a 10 kA short-circuit rating for industrial branch-circuit protection.
£114.14
The Lovato P1MBUH3PD12 is a high-performance three-pole miniature circuit breaker (MCB) designed for branch-circuit protection in industrial electrical installations. Part of the Lovato P1 MB series, this circuit breaker combines thermal-magnetic overcurrent protection with a D tripping characteristic for circuits where higher starting or inrush currents may occur.
Designed for compliance with UL 489 requirements, the P1MBUH3PD12 provides dependable protection against overload and short-circuit conditions. Its three-pole configuration enables simultaneous protection of three-phase circuits, while its modular construction allows straightforward installation on standard 35 mm DIN rail inside electrical distribution boards and control panels.
With a rated current of 12 A, a D tripping curve and a 10 kA short-circuit rating, the P1MBUH3PD12 is suitable for demanding industrial branch circuits. It is rated at 480Y/277 V AC under UL and operates at 50/60 Hz, making it suitable for a wide range of industrial electrical protection applications.
Miniature circuit breakers such as the Lovato P1MBUH3PD12 provide automatic protection by disconnecting a circuit when excessive current occurs due to an overload or short circuit. Thermal-magnetic operation combines time-dependent overload protection with rapid magnetic operation during severe fault-current conditions.
The D tripping characteristic is particularly useful where equipment can produce significant short-duration inrush currents during start-up. Combined with its three-pole construction, 10 kA interrupting capability and UL 489 compliance, the P1MBUH3PD12 provides a practical protection solution for industrial three-phase branch circuits.
Tick the specs you need, then view products that match.
| Certification | UL 489 | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCB | |
| Trip Curve | D curve | |
| HS Code | 85362010 | |
| Manufacturer | Lovato Electric | |
| Series | P1 MB | |
| Model | P1MBUH3PD12 | |
| Product type | Miniature circuit breaker (MCB) | |
| Number of poles | 3P | |
| Protected poles | 3 | |
| Rated current | 12 A | |
| Tripping characteristic | Curve D | |
| Rated operational voltage (UL) | 480Y/277 V AC | |
| Rated operational voltage (IEC) | 230/400 V AC | |
| Rated frequency | 50/60 Hz | |
| Short-circuit rating (UL) | 10 kA | |
| Short-circuit rating (IEC) | 10 kA | |
| Rated impulse withstand voltage | 4 kV | |
| Number of DIN modules | 3 | |
| Protection rating | IP20 | |
| Mounting | 35 mm DIN rail | |
| Operating temperature | -40 to +70 °C | |
| Electrical life | 10,000 cycles | |
| Compliance | UL 489 / IEC |
The P1MBUH3PD12 is a three-pole miniature circuit breaker designed to provide overload and short-circuit protection for industrial branch circuits and electrical equipment.
The Lovato P1MBUH3PD12 has a rated current of 12 A.
The D tripping characteristic allows comparatively high short-duration starting currents before instantaneous magnetic operation, making this type of breaker useful for suitable industrial loads with significant inrush current.
The circuit breaker is rated for 480Y/277 V AC under UL and 230/400 V AC under IEC operating conditions.
The P1MBUH3PD12 has a 10 kA short-circuit rating, providing robust fault-current interruption for appropriately designed electrical installations.
Lovato Electric P1 MB miniature circuit breakers provide compact and dependable circuit protection for industrial control, distribution and machine-building applications, combining modular DIN rail installation with established electrical protection technology.