Chint NB310L-3N-C10 3P+N RCBO with 10A rated current, C Curve characteristic, Type A residual current protection, 30mA sensitivity and 6kA short circuit breaking capacity for three-phase electrical installations.
£60.04
The Chint NB310L-3N-C10 is a reliable 3P+N RCBO (Residual Current Circuit Breaker with Overcurrent Protection) designed to provide combined protection against earth leakage, overload and short circuit faults in three-phase electrical installations. By integrating residual current protection and overcurrent protection into one compact DIN rail mounted device, it helps improve safety while reducing space requirements inside distribution boards and control panels.
As part of the Chint NB310L Series, this RCBO features a 10A rated current, C Curve tripping characteristic and Type A residual current protection. It is suitable for circuits with moderate inrush currents, including control equipment, small machinery, lighting circuits and commercial electrical distribution systems.
With a 230/400V AC rated voltage, 30mA residual operating current and 6kA short circuit breaking capacity, the NB310L-3N-C10 provides dependable circuit protection for modern low-voltage three-phase installations where safety, reliability and compact panel design are essential.
The Chint NB310L-3N-C10 helps protect personnel, cables and connected equipment by automatically disconnecting the circuit when earth leakage, overload or short circuit conditions are detected. This makes it a practical choice for electricians, panel builders and industrial engineers working with compact three-phase distribution systems.
Its Type A residual current protection makes it suitable for modern installations containing electronic equipment, power supplies, automation components and control circuits where pulsating DC residual currents may occur alongside standard AC leakage currents.
Tick the specs you need, then view products that match.
| Poles | 3-pole + N | |
|---|---|---|
| Current | 10 A | |
| Phase | Three Phase | |
| Trip Curve | C curve | |
| Breaking Capacity | 6 kA | |
| Residual Current | 30 mA | |
| RCD Type | Type A | |
| Device Type | RCD | |
| Manufacturer | Chint | |
| Series | NB310L | |
| Model | NB310L-3N-C10 | |
| Product type | Residual Current Circuit Breaker with Overcurrent Protection | |
| Configuration | 3P+N | |
| Rated current | 10A | |
| Trip Curve | C Curve | |
| Residual current type | Type A | |
| Rated residual operating current | 30mA | |
| Rated voltage | 230/400V AC | |
| Frequency | 50/60Hz | |
| Rated short circuit breaking capacity | 6kA | |
| Rated insulation voltage | 500V | |
| Rated impulse withstand voltage | 4kV | |
| Protection rating | IP20 | |
| Mounting type | 35mm DIN rail | |
| Standard | IEC/EN 61009-1 | |
| Dimensions (H × W × D) | approx. 86 × 72 × 77.5 mm |
The Chint NB310L-3N-C10 is used to protect three-phase circuits against earth leakage, overload and short circuit faults.
This model has a 10A rated current, making it suitable for low-current three-phase protection applications.
C Curve devices are designed for mixed resistive and inductive loads and typically trip between 5 and 10 times their rated current during magnetic fault conditions.
Type A protection detects sinusoidal AC residual currents and pulsating DC residual currents, making it suitable for many modern electrical installations.
The RCBO is designed for installation onto a standard 35mm DIN rail inside distribution boards and electrical control panels.
Chint NB310L RCBOs are trusted by electricians, panel builders and electrical contractors for dependable low-voltage circuit protection where safety, reliability and compact installation are essential.