Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB F202 A-100/0.03 AP-R 2-pole residual current circuit breaker with a 100 A rated current, 30 mA Type A residual current sensitivity and AP-R short-time delayed operation for improved resistance to unwanted tripping.
£229.44
The ABB F202 A-100/0.03 AP-R is a high-performance 2-pole residual current circuit breaker (RCCB) designed to protect people and electrical installations against earth leakage faults. Part of the proven ABB System pro M compact® F200 series, it provides sensitive residual current protection for high-current single-phase circuits in commercial, industrial and building-services applications.
Featuring Type A residual current detection, the F202 A-100/0.03 AP-R responds to both sinusoidal AC and pulsating DC residual currents. This makes it suitable for modern installations containing electronic equipment, switched-mode power supplies, appliance controls and other loads capable of producing pulsating DC earth leakage.
ABB's AP-R short-time delayed technology improves resistance to unwanted tripping caused by transient leakage currents, switching events and electrical disturbances. With a 100 A rated current and 30 mA residual current sensitivity, this RCCB offers an effective balance between personal protection and continuity of service.
The ABB F202 A-100/0.03 AP-R monitors the current flowing through the line and neutral conductors. When it detects an imbalance caused by current leaking to earth, it rapidly disconnects the circuit to reduce the risk of electric shock, fire and damage to electrical equipment.
Its AP-R operating characteristic introduces a short intentional delay and enhanced resistance to impulse currents. This helps prevent unnecessary disconnection during transient events while retaining sensitive 30 mA protection. The device must be used alongside appropriate overload and short-circuit protection because an RCCB does not provide overcurrent protection by itself.
Tick the specs you need, then view products that match.
| Product Series | ABB F200 | |
|---|---|---|
| Current | 100 A | |
| Poles | 2-pole | |
| Device Type | RCD | |
| Breaking Capacity | 1 kA | |
| Residual Current | 30 mA | |
| RCD Type | Type A | |
| Manufacturer | ABB | |
| Series | System pro M compact® F200 | |
| Model | F202 A-100/0.03 AP-R | |
| Product ID | 2CSF202401R1900 | |
| EAN | 8012542916505 | |
| Product type | Residual Current Circuit Breaker (RCCB) | |
| Number of poles | 2 | |
| Rated current | 100 A | |
| Rated residual operating current | 30 mA | |
| Residual current characteristic | Type A | |
| Operating characteristic | AP-R short-time delayed | |
| Rated operational voltage | 230 / 400–240 / 415 V AC | |
| Rated frequency | 50 / 60 Hz | |
| Rated insulation voltage | 500 V | |
| Rated impulse withstand voltage | 4 kV | |
| Rated conditional short-circuit current | 10 kA with suitable upstream protection | |
| Rated residual making and breaking capacity | 1 kA | |
| Protection rating | IP20 | |
| Mounting type | 35 mm DIN rail | |
| Mounting position | Any | |
| Supply connection | Top or bottom | |
| Module width | 2 modules | |
| Standards | IEC/EN 61008-1 and IEC/EN 61008-2-1 | |
| Dimensions (H × W × D) | Approx. 85 × 35 × 69 mm | |
| Weight | Approx. 0.20–0.23 kg | |
| HS Code | 85363030 | |
| Country of Manufacture | Italy |
The F202 A-100/0.03 AP-R detects earth leakage currents and disconnects the supply to help protect people and electrical installations against electric shock and earth-fault hazards.
No. The F202 A-100/0.03 AP-R provides residual current protection only and must be installed with a suitably rated fuse or circuit breaker for overload and short-circuit protection.
AP-R identifies ABB's short-time delayed RCCB technology, which provides enhanced resistance to transient leakage currents and helps reduce unwanted tripping while maintaining residual current protection.
A Type A RCCB detects sinusoidal alternating residual currents and pulsating DC residual currents generated by many modern electronic devices.
The ABB F202 A-100/0.03 AP-R has a rated residual operating current of 30 mA, making it suitable for additional personal protection applications.
Yes. The F202 A-100/0.03 AP-R supports supply connection from either the top or the bottom, providing greater installation flexibility.