ABB DS-ARC1 M C10 A30 (2CSA275103R1104) arc fault detection device with integrated RCBO: 1P+N, C curve, 10 A, 10 kA breaking capacity, 30 mA Type A residual current.
£242.50
The ABB DS-ARC1 M C10 A30 is a compact arc fault detection device (AFDD) with integrated RCBO protection designed to provide comprehensive protection for single-phase electrical circuits. As part of the ABB DS-ARC1 M series, it combines arc fault detection, residual current protection, overload protection and short-circuit protection within a single three-module DIN rail device.
The DS-ARC1 M monitors electrical circuits for potentially dangerous arc faults while its integrated Type A RCBO provides protection against residual currents and overcurrents. The series also provides protection against overvoltage conditions, while LED indication, dedicated AFDD and residual current test functions, and continuous internal self-testing support reliable operation and straightforward troubleshooting.
With a rated current of 10 A, a C tripping characteristic, 30 mA Type A residual current sensitivity and a rated operational voltage of 230–240 V AC, the DS-ARC1 M C10 A30 provides enhanced protection for 1P+N circuits. The M version offers a 10 kA rated ultimate short-circuit breaking capacity, while the C-curve characteristic makes it suitable for circuits that can experience moderate starting or inrush currents.
Arc fault detection devices monitor electrical circuits for conditions associated with potentially dangerous electrical arcs. The ABB DS-ARC1 M combines AFDD functionality with Type A residual current and thermal-magnetic overcurrent protection, enabling a single device to address arc faults, residual currents, overloads and short circuits.
The DS-ARC1 M series provides a higher short-circuit breaking capacity than the standard DS-ARC1 range while retaining a compact three-module format. LED troubleshooting indication, dedicated AFDD and residual current test functions, continuous internal self-testing, flexible top or bottom supply connection and compatibility with ABB System pro M compact accessories support straightforward installation and maintenance.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 10 A | |
| Trip Curve | C curve | |
| Breaking Capacity | 10 kA | |
| Phase | Single Phase | |
| Residual Current | 30 mA | |
| RCD Type | Type A | |
| Manufacturer | ABB | |
| Series | DS-ARC1 M | |
| Model | DS-ARC1 M C10 A30 | |
| Order code / MPN | 2CSA275103R1104 | |
| EAN | 8012542733416 | |
| Product type | Arc fault detection device with integrated RCBO | |
| Rated current | 10 A | |
| Tripping characteristic | C | |
| Rated residual current | 30 mA | |
| Residual current type | Type A | |
| Rated operational voltage | 230–240 V AC | |
| Rated frequency | 50–60 Hz | |
| Number of poles | 1P+N | |
| Number of protected poles | 1 | |
| Rated service short-circuit breaking capacity (Ics) | 7.5 kA | |
| Rated ultimate short-circuit breaking capacity (Icu) | 10 kA | |
| Rated insulation voltage (Ui) | 500 V | |
| Rated impulse withstand voltage (Uimp) | 4 kV | |
| Power loss | 1.8 W | |
| Protection rating | IP20 terminals / IP40 housing | |
| Pollution degree | 2 | |
| Operating temperature | -25 to +55 °C | |
| Contact position indication | Red ON / green OFF | |
| Actuator type | Toggle, orange RAL 2004, sealable in ON/OFF position | |
| Mounting type | DIN rail | |
| Terminal type | Screw terminals | |
| Tightening torque | 2.8 N·m | |
| Modular width | 3 modules | |
| Dimensions (H × W × D) | 85 × 52.5 × 69 mm | |
| Weight | 240 g | |
| Standards | IEC/EN 62606, IEC/EN 61009-1, IEC/EN 61009-2-1 |
The ABB DS-ARC1 M C10 A30 is used to protect single-phase electrical circuits against arc faults, residual currents, overloads and short circuits using one integrated AFDD and RCBO device.
The device has a rated current of 10 A and uses a C tripping characteristic, making it suitable for circuits that can experience moderate starting or inrush currents.
The DS-ARC1 M C10 A30 provides Type A residual current protection with a rated residual current of 30 mA.
The DS-ARC1 M C10 A30 has a rated operational voltage of 230–240 V AC and is designed for 1P+N single-phase electrical circuits.
The DS-ARC1 M C10 A30 has a 7.5 kA rated service short-circuit breaking capacity (Ics) and a 10 kA rated ultimate short-circuit breaking capacity (Icu).
ABB DS-ARC1 M devices combine arc fault detection with residual current and overcurrent protection in a compact DIN rail format, providing comprehensive circuit protection with enhanced short-circuit breaking capacity for modern electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.