ABB DS-ARC1 C6 A30 (2CSA255103R1064) arc fault detection device with integrated RCBO: 1P+N, C curve, 6 A, 6 kA breaking capacity, 30 mA Type A residual current.
£210.39
The ABB DS-ARC1 C6 A30 is a compact and highly reliable arc fault detection device (AFDD) with integrated RCBO protection designed to provide comprehensive protection for single-phase electrical circuits. As part of the advanced ABB DS-ARC1 series, it combines arc fault detection, residual current protection, overload protection and short-circuit protection within a single three-module DIN rail device.
This integrated protection solution detects potentially dangerous electrical arc faults while also providing Type A residual current protection and thermal-magnetic overcurrent protection. The DS-ARC1 series incorporates LED fault indication, separate test functions for the AFDD and residual current protection, and continuous internal self-testing to support reliable operation and straightforward troubleshooting.
With a rated current of 6 A, a C tripping characteristic, 30 mA Type A residual current sensitivity and a 230–240 V AC rated operational voltage, the DS-ARC1 C6 A30 is suitable for lower-current single-phase circuits requiring enhanced protection. Its C-curve characteristic accommodates moderate inrush currents, while its compact DIN rail format enables straightforward integration into electrical distribution boards.
Arc fault detection devices monitor electrical circuits for characteristic conditions associated with potentially dangerous electrical arcs. The ABB DS-ARC1 combines arc fault detection with residual current and thermal-magnetic overcurrent protection, enabling a single device to provide protection against arc faults, earth leakage currents, overloads and short circuits.
The DS-ARC1 series is designed for modern electrical installations where comprehensive final-circuit protection is required. Its continuous internal self-test, LED troubleshooting indication, flexible top or bottom supply connection and compact three-module DIN rail construction help simplify installation, operation and fault identification.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 6 A | |
| Trip Curve | C curve | |
| Breaking Capacity | 6 kA | |
| Phase | Single Phase | |
| Residual Current | 30 mA | |
| RCD Type | Type A | |
| Manufacturer | ABB | |
| Series | DS-ARC1 | |
| Model | DS-ARC1 C6 A30 | |
| Order code | 2CSA255103R1064 | |
| Product type | Arc fault detection device with integrated RCBO | |
| Rated current | 6 A | |
| Tripping characteristic | C | |
| Rated residual current | 30 mA | |
| Residual current type | Type A | |
| Rated operational voltage | 230–240 V AC | |
| Rated frequency | 50–60 Hz | |
| Number of poles | 1P+N | |
| Number of protected poles | 1 | |
| Short-circuit breaking capacity | 6 kA | |
| Rated insulation voltage (Ui) | 500 V | |
| Rated impulse withstand voltage (Uimp) | 4 kV | |
| Power loss | 2.5 W | |
| Protection rating | IP20 terminals / IP40 housing | |
| Pollution degree | 2 | |
| Operating temperature | -25 to +55 °C | |
| Contact position indication | Red ON / green OFF | |
| Mounting type | DIN rail | |
| Terminal type | Screw terminals | |
| Tightening torque | 2.8 N·m | |
| Modular width | 3 modules | |
| Dimensions (H × W × D) | 85 × 52.5 × 69 mm | |
| Weight | 240 g | |
| Standards | IEC/EN 62606, IEC/EN 61009-1, IEC/EN 61009-2-1 |
The ABB DS-ARC1 C6 A30 is used to protect single-phase electrical circuits against arc faults, earth leakage currents, overloads and short circuits using one integrated AFDD and RCBO device.
The device has a rated current of 6 A and uses a C tripping characteristic, making it suitable for lower-current circuits that can experience moderate starting or inrush currents.
The DS-ARC1 C6 A30 provides Type A residual current protection with a rated residual current of 30 mA.
The DS-ARC1 C6 A30 has a rated operational voltage of 230–240 V AC and is designed for 1P+N single-phase electrical circuits.
The DS-ARC1 C6 A30 has a 6 kA short-circuit breaking capacity and combines this protection with AFDD and 30 mA Type A residual current functionality.
ABB DS-ARC1 devices combine arc fault detection with residual current and overcurrent protection in a compact DIN rail format, providing comprehensive circuit protection for modern residential and commercial electrical installations.