ABB DS-ARC1 C13 A30 (2CSA255103R1134) arc fault detection device with integrated RCBO: 1P+N, C curve, 13 A, 6 kA breaking capacity, 30 mA Type A residual current.
£210.39
The ABB DS-ARC1 C13 A30 is a compact and highly reliable arc fault detection device (AFDD) with integrated RCBO protection designed to provide comprehensive protection for single-phase electrical circuits. As part of the advanced ABB DS-ARC1 series, it combines arc fault detection, residual current protection, overload protection and short-circuit protection within a single three-module DIN rail device.
This integrated protection solution detects potentially dangerous series, parallel and earth arc faults while also providing Type A residual current protection and thermal-magnetic overcurrent protection. The DS-ARC1 series features LED fault indication, dedicated test functions and continuous internal self-testing, helping simplify troubleshooting and verify correct operation of the protective functions.
With a rated current of 13 A, a C tripping characteristic and 30 mA Type A residual current sensitivity, the DS-ARC1 C13 A30 is designed for single-phase electrical circuits. Its C-curve characteristic makes it suitable for circuits with moderate inrush currents, while the compact DIN rail format enables straightforward integration into residential and commercial distribution boards.
Arc fault detection devices monitor electrical circuits for characteristic conditions associated with potentially dangerous electrical arcs. The ABB DS-ARC1 detects series, parallel and earth arc faults and combines this functionality with residual current and thermal-magnetic overcurrent protection, enabling one device to protect against multiple electrical fault conditions.
The DS-ARC1 series is designed for residential and commercial electrical installations where comprehensive final-circuit protection is required. Its continuous internal self-test, LED troubleshooting indication, bi-directional connection capability and compact three-module DIN rail construction help simplify installation, operation and fault identification.
Tick the specs you need, then view products that match.
| Device Type | AFDD | |
|---|---|---|
| Poles | 1-pole + N | |
| Current | 13 A | |
| Trip Curve | C curve | |
| Breaking Capacity | 6 kA | |
| Phase | Single Phase | |
| Residual Current | 30 mA | |
| RCD Type | Type A | |
| Manufacturer | ABB | |
| Series | DS-ARC1 | |
| Model | DS-ARC1 C13 A30 | |
| Order code | 2CSA255103R1134 | |
| EAN | 8012542748311 | |
| Product type | Arc fault detection device with integrated RCBO | |
| Rated current | 13 A | |
| Tripping characteristic | C | |
| Rated residual current | 30 mA | |
| Residual current type | Type A | |
| Rated frequency | 50–60 Hz | |
| Number of poles | 1P+N | |
| Short-circuit breaking capacity | 6 kA | |
| Rated ultimate short-circuit breaking capacity | 7.5 kA | |
| Rated impulse withstand voltage | 4 kV | |
| Power loss | 2.0 W | |
| Contact position indication | Red ON / green OFF | |
| Electrical endurance | 10,000 cycles | |
| Mechanical endurance | 20,000 cycles | |
| Busbar connecting capacity | 10 mm² | |
| Rigid conductor capacity | 1–25 mm² | |
| Flexible conductor capacity | 1–16 mm² | |
| Wire stripping length | 12 mm | |
| Mounting type | DIN rail | |
| Terminal type | Screw terminals | |
| Tightening torque | 2.8 N·m | |
| Modular width | 3 modules | |
| Dimensions (H × W × D) | 85 × 52.5 × 69 mm | |
| Weight | 240 g | |
| Standards | IEC/EN 62606, IEC/EN 61009-1, IEC/EN 61009-2-1 |
The ABB DS-ARC1 C13 A30 is used to protect single-phase electrical circuits against arc faults, earth leakage currents, overloads and short circuits using one integrated AFDD and RCBO device.
The device has a rated current of 13 A and uses a C tripping characteristic, making it suitable for circuits that can experience moderate starting or inrush currents.
The DS-ARC1 C13 A30 provides Type A residual current protection with a rated residual current of 30 mA.
The DS-ARC1 is designed to provide protection against series arc faults, parallel arc faults and earth arc faults, helping reduce the risks associated with dangerous electrical arcing.
The DS-ARC1 C13 A30 has a 6 kA short-circuit breaking capacity and is designed as a compact 1P+N protective device for residential and commercial electrical circuits.
ABB DS-ARC1 devices combine arc fault detection with residual current and overcurrent protection in a compact DIN rail format, providing comprehensive circuit protection for modern residential and commercial electrical installations.