The IMO B6CR1N40-30-A is a compact and dependable Residual Current Circuit Breaker with Overcurrent Protection (RCBO) designed to protect electrical circuits against earth leakage, overload and short-circuit faults. By combining residual current and overcurrent protection within one device, it helps simplify installation and reduce the amount of space required inside consumer units, distribution boards and electrical control panels.
As part of the established IMO B6 RCBO range, this model provides Type A residual current protection. It can detect sinusoidal AC and pulsating DC residual currents, making it suitable for modern installations containing electronic appliances, LED drivers, switched-mode power supplies and other equipment incorporating semiconductor components.
With a rated current of 40 A, a residual operating current of 30 mA and a Type C tripping characteristic, the B6CR1N40-30-A is suitable for higher-load final circuits and equipment that may produce moderate starting currents. Its DIN rail mounting format enables straightforward installation in residential, commercial and light industrial electrical systems.
The IMO B6CR1N40-30-A continuously monitors the connected circuit for excessive current and current leaking to earth. When a qualifying overload, short circuit or residual current fault occurs, the RCBO rapidly disconnects the electrical supply to help reduce the risk of electric shock, damaged equipment and electrical fires.
Type A residual current protection is particularly useful in contemporary installations because many electronic devices can produce pulsating DC leakage currents. The Type C operating characteristic also enables the RCBO to accommodate the moderate inrush currents associated with pumps, transformers, lighting systems and small motors.
Tick the specs you need, then view products that match.
| Voltage | 230 V | |
|---|---|---|
| Phase | Single Phase | |
| Poles | 1-pole + N | |
| Device Type | RCBO | |
| Trip Curve | C curve | |
| Breaking Capacity | 10 kA | |
| Residual Current | 30 mA | |
| Manufacturer | IMO Precision Controls | |
| Series | B6 RCBO | |
| Model | B6CR1N40-30-A | |
| Product type | Residual Current Circuit Breaker with Overcurrent Protection | |
| Rated current | 40 A | |
| Residual operating current | 30 mA | |
| Residual current classification | Type A | |
| Tripping characteristic | Type C | |
| Short-circuit breaking capacity | 10 kA | |
| Pole configuration | 1P+N | |
| Rated operational voltage | 230 V AC | |
| Rated frequency | 50 / 60 Hz | |
| Applicable standard | IEC/EN 61009-1 | |
| Mounting type | 35 mm DIN rail | |
| Installation type | Fixed installation | |
| Application | Circuit, equipment and personnel protection | |
| HS Code | 8536201090 | |
| Country of Manufacture | China |
It provides combined protection against earth leakage, overload and short-circuit faults in residential, commercial and light industrial electrical circuits.
The IMO B6CR1N40-30-A has a rated current of 40 A.
Type A protection detects sinusoidal AC and pulsating DC residual currents, making it suitable for circuits supplying many modern electronic devices.
The 30 mA value is the rated residual operating current at which the RCBO is designed to disconnect the circuit, providing additional protection against electric shock.
It is designed for mounting on a standard 35 mm DIN rail within a suitable consumer unit, distribution board or electrical control panel.
IMO circuit protection products are used by electricians, panel builders and automation engineers seeking compact, practical and dependable protection for modern electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.