B10R2040-30-A-110 IMO RCD 10KA, 30mA 2 Pole + N, 40 Amp, 110VAC

B10R2040-30-A-110 IMO RCD 10KA, 30mA 2 Pole + N, 40 Amp, 110VAC

SKU: B10R2040-30-A-110Alt SKU: B10R204030A110MPN: B10R2040-30-A-110
Price
List Price £68.68 ex VAT
Your Price (ex VAT) Save 30%
£48.08 30% OFF
You save £20.60 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £48.08
Trade pricing is personalised to your account

Manufacturer Lead Time

Sold in packs of 120

£48.08

Why Choose the IMO B10R2040-30-A-110 Type A Residual Current Device?

The IMO B10R2040-30-A-110 is a high-performance Type A Residual Current Device (RCD/RCCB) designed to provide reliable protection against earth leakage faults in 110 V AC electrical installations. Manufactured by IMO Precision Controls, it forms part of the trusted B10R RCCB series, delivering dependable protection for construction sites, temporary power systems, industrial equipment and commercial electrical installations.

The device continuously monitors the balance between live and neutral conductors. If a residual current fault exceeds the rated operating threshold, the RCD disconnects the electrical supply, helping reduce the risk of electric shock and protecting equipment from earth leakage faults. Its Type A characteristic enables detection of both alternating residual currents and pulsating DC residual currents generated by modern electronic equipment.

With a 40 A rated current, 30 mA residual operating current, 1 Pole + Neutral configuration and 110 V AC operating voltage, the B10R2040-30-A-110 provides dependable protection while allowing straightforward installation on standard DIN rail systems.

Key Advantages

  • Reliable Type A residual current protection for 110 V electrical installations.
  • 40 A rated current suitable for higher-load circuits.
  • 30 mA residual operating current for enhanced personnel protection.
  • Detects both AC and pulsating DC residual currents.
  • 10 kA conditional short-circuit rating.
  • Compact DIN rail mounting for quick installation.

Key Features

  • IMO B10R residual current device series.
  • 40 A rated operational current.
  • 30 mA rated residual operating current.
  • Type A residual current characteristic.
  • 1 Pole + Neutral (2 Pole) configuration.
  • 110 V AC rated operating voltage.
  • 10 kA conditional short-circuit capacity.
  • DIN rail mounting to EN 60715.

Reliable Earth Leakage Protection for 110 V Systems

Residual current devices monitor the difference between outgoing and returning current. If current leaks to earth because of damaged insulation or equipment faults, the device disconnects the supply within milliseconds to improve electrical safety and reduce equipment damage.

The Type A characteristic enables the IMO B10R2040-30-A-110 to detect both sinusoidal AC and pulsating DC residual currents, making it suitable for modern electronic equipment, industrial machinery and site power distribution. As with all RCCBs, suitable overcurrent protection should be provided separately.

Typical Applications

  • 110 V site power distribution.
  • Construction and temporary electrical installations.
  • Industrial control panels.
  • Commercial electrical systems.
  • Portable power distribution equipment.
  • Industrial machinery and automation.

Technical Specifications

Tick the specs you need, then view products that match.

Phase Single Phase
Voltage 110 V
Poles 1-pole + N
Device Type RCD
Residual Current 30 mA
Manufacturer IMO Precision Controls
Series B10R
Model B10R2040-30-A-110
Alternative SKU B10R204030A110
Product type Residual Current Device (RCD/RCCB)
Rated current 40 A
Rated residual operating current 30 mA
Residual current characteristic Type A
Pole configuration 1 Pole + Neutral (2 Pole)
Rated voltage 110 V AC
Frequency 50 / 60 Hz
Conditional short-circuit rating 10 kA
Mounting type DIN rail
Protection rating IP20
Standard IEC 61008-1
HS Code 8536201090
Country of Manufacture China

Frequently Asked Questions

What is the IMO B10R2040-30-A-110 used for?

It provides residual current protection by disconnecting 110 V electrical circuits when earth leakage faults are detected.

What does Type A mean?

Type A RCDs detect both alternating residual currents and pulsating DC residual currents generated by many modern electronic devices.

What is the rated current?

The IMO B10R2040-30-A-110 has a rated operational current of 40 A.

What residual current sensitivity does it provide?

The device has a 30 mA residual operating current for enhanced personnel protection.

Does this RCD provide overload protection?

No. This device provides residual current protection only and should be used with a suitably rated miniature circuit breaker or fuse for overload and short-circuit protection.

Trusted Electrical Protection from IMO

IMO B10R residual current devices are trusted by electricians, panel builders and industrial engineers to provide dependable earth leakage protection in demanding commercial and industrial applications.