ABB S202M-B6 miniature circuit breaker from the S200M series, featuring 2-pole configuration, 6 A rated current, B trip characteristic and 10 kA short circuit breaking capacity.
£39.70
The ABB S202M-B6 is a compact and reliable 2-pole miniature circuit breaker (MCB) designed to provide dependable overload and short circuit protection for residential, commercial and industrial electrical installations. Part of the trusted ABB S200M System pro M Compact range, it delivers high performance protection in a space-saving DIN rail mounted format.
This miniature circuit breaker uses two proven tripping mechanisms: a delayed thermal trip for overload protection and an electromechanical trip for rapid short circuit interruption. Its robust construction and modular design make it suitable for distribution boards, control panels and electrical equipment where safe isolation and dependable circuit protection are required.
With a 6 A rated current, B characteristic trip curve and 10 kA breaking capacity at 230/400 V AC, the S202M-B6 is ideal for protecting lighting circuits, control circuits and other low inrush electrical loads. The 2-pole configuration allows simultaneous switching of both conductors for improved safety and isolation.
The ABB S200M range is designed to deliver dependable current limiting protection across a wide range of electrical installations. The S202M-B6 helps protect wiring and connected equipment from damage caused by overloads and short circuits, supporting safe operation and reliable electrical distribution.
The B curve characteristic makes this circuit breaker suitable for circuits with low inrush currents, such as lighting circuits, control circuits and general electrical loads. Its 2-pole design provides simultaneous disconnection of both poles, making it a practical choice where enhanced isolation is required.
Tick the specs you need, then view products that match.
| Current | 6 A | |
|---|---|---|
| Phase | Single Phase | |
| Poles | 2-pole | |
| Device Type | MCB | |
| Trip Curve | B curve | |
| Breaking Capacity | 10 kA | |
| Manufacturer | ABB | |
| Series | S200M | |
| Model | S202M-B6 | |
| Product ID | 2CDS272001R0065 | |
| EAN | 4016779549585 | |
| Product type | Miniature circuit breaker | |
| Rated current | 6 A | |
| Trip characteristic | B | |
| Number of poles | 2P | |
| Rated operational voltage | 230/400 V AC | |
| Voltage type | AC | |
| Rated frequency | 50 / 60 Hz | |
| Rated short circuit capacity | 10 kA | |
| Rated ultimate short circuit breaking capacity | 15 kA | |
| Rated service short circuit breaking capacity | 11.2 kA | |
| Rated insulation voltage | 440 V | |
| Rated impulse withstand voltage | 4 kV | |
| Energy limiting class | 3 | |
| Standards | IEC/EN 60898-1, IEC/EN 60947-2, UL 1077 | |
| Protection rating | IP20 | |
| Mounting type | DIN rail | |
| Dimensions (H × W × D) | 88 × 35 × 69 mm | |
| Weight | approx. 0.25 kg | |
| HS Code | 85362010 | |
| Country of Manufacture | Germany |
The S202M-B6 is used to protect electrical circuits against overloads and short circuits in residential, commercial and industrial installations.
The ABB S202M-B6 has a 6 A rated current.
The B trip characteristic is designed for circuits with low inrush currents, making it suitable for lighting, control and general resistive loads.
This miniature circuit breaker provides a 10 kA short circuit breaking capacity.
It is designed for DIN rail mounting inside electrical distribution boards, control panels and modular enclosures.
ABB S200M miniature circuit breakers are trusted by electricians, panel builders and industrial engineers worldwide for dependable circuit protection in residential, commercial and industrial electrical installations.