ABB S201MT-K16NAH10 miniature circuit breaker with switched neutral, 16 A K characteristic and 10 kA breaking capacity for railway, traction and industrial circuit protection.
The ABB S201MT-K16NAH10 is a high-performance miniature circuit breaker with switched neutral, designed to provide dependable overload and short-circuit protection for railway, traction and demanding industrial electrical systems. As part of the ABB S200MT series, it combines compact installation, robust construction and reliable protection for specialist electrical applications.
Featuring a K tripping characteristic, this MCB is ideal for circuits with higher inrush currents, including motors, transformers, inductive loads and auxiliary control circuits. The switched neutral configuration disconnects both the protected conductor and neutral simultaneously, improving circuit isolation and simplifying maintenance procedures.
With a 16 A rated current, 10 kA rated short-circuit breaking capacity and DIN rail mounting, the ABB S201MT-K16NAH10 is well suited to railway systems, industrial automation, OEM machinery and control panels where reliable electrical protection is essential.
The ABB S200MT range has been developed specifically for traction and railway applications while also meeting the requirements of demanding industrial installations. Its current limiting design incorporates delayed thermal overload protection together with an electromechanical short-circuit tripping mechanism, delivering reliable protection for modern electrical systems.
The K characteristic allows the S201MT-K16NAH10 to operate reliably on circuits with elevated starting currents while reducing nuisance tripping. Combined with its switched neutral configuration and compatibility with ABB System pro M Compact accessories, it provides an excellent solution for panel builders, OEMs and railway engineers.
Tick the specs you need, then view products that match.
| Phase | Single Phase | |
|---|---|---|
| Current | 16 A | |
| Poles | 1-pole + N | |
| Device Type | MCB | |
| Trip Curve | K curve | |
| Breaking Capacity | 10 kA | |
| Manufacturer | ABB | |
| Series | S200MT | |
| Model | S201MT-K16NAH10 | |
| Manufacturer Part Number | 2CDV271106R0467 | |
| Product type | Miniature Circuit Breaker (MCB) | |
| Rated current | 16 A | |
| Number of poles | 1 protected pole + switched neutral | |
| Tripping characteristic | K | |
| Rated operational voltage | 230 V AC | |
| Input voltage type | AC/DC | |
| Rated insulation voltage | 440 V | |
| Rated impulse withstand voltage | 4 kV | |
| Frequency | 50 / 60 Hz | |
| Breaking capacity | 10 kA | |
| Rated ultimate breaking capacity (Icu) | 15 kA | |
| Protection rating | IP20 | |
| Mounting type | DIN rail | |
| Dimensions (H × W × D) | approx. 88 × 35 × 69 mm | |
| Weight | approx. 0.25 kg |
It provides overload and short-circuit protection for railway, traction, industrial and auxiliary electrical circuits.
The 16 A rated current means the breaker is designed to protect circuits carrying up to 16 amps under normal operating conditions.
The switched neutral disconnects the neutral conductor together with the protected pole, providing improved circuit isolation and increased maintenance safety.
The K curve is designed for circuits with higher inrush currents, making it suitable for motors, transformers, inductive loads and specialist industrial equipment.
Yes. It is designed for standard DIN rail mounting inside electrical control panels and distribution boards.