Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB F204 A S-125/0.5 four-pole Type A selective residual current circuit breaker rated at 125 A with 500 mA sensitivity for three-phase electrical distribution systems.
£1,863.09
The ABB F204 A S-125/0.5 is a heavy-duty four-pole selective residual current circuit breaker (RCCB) designed to provide dependable earth fault protection in commercial, industrial and infrastructure electrical installations. As part of the trusted ABB F200 RCCB series, it helps protect people, equipment and installations by detecting residual current faults and disconnecting the circuit when leakage current exceeds the rated threshold.
This Type A selective RCCB detects alternating residual currents and pulsating DC residual currents generated by modern electrical equipment. Its 125 A rated current and 500 mA residual operating current make it suitable for upstream protection in higher-load three-phase distribution systems where selective coordination with downstream residual current devices is required.
With its four-pole DIN rail mounted design, robust screw terminal connections and compact modular construction, the F204 A S-125/0.5 is ideal for professional switchboards, distribution boards and control panels requiring reliable residual current protection with delayed selective tripping behaviour.
Residual current circuit breakers continuously monitor the balance between live conductors and the neutral conductor. If earth leakage is detected, the RCCB disconnects the protected circuit to help reduce the risk of electric shock, electrical fire and damage to connected equipment.
The selective operating characteristic of the ABB F204 A S-125/0.5 provides intentional delayed tripping, helping improve coordination with downstream residual current devices. This supports continuity of service by allowing downstream protection to operate first where appropriate.
Tick the specs you need, then view products that match.
| Product Series | ABB F200 | |
|---|---|---|
| Current | 125 A | |
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | RCD | |
| Residual Current | 500 mA | |
| RCD Type | Type A | |
| Manufacturer | ABB | |
| Series | F200 RCCB Series | |
| Model | F204 A S-125/0.5 | |
| Manufacturer Part Number | 2CSF204201R4950 | |
| EAN | 8012542968405 | |
| Product type | Residual Current Circuit Breaker (RCCB) | |
| Residual current type | Type A | |
| Operating characteristic | Selective | |
| Number of poles | 4P | |
| Rated current | 125 A | |
| Rated residual operating current | 500 mA | |
| Rated operational voltage | 230 / 400 V AC | |
| Rated insulation voltage | 500 V | |
| Rated impulse withstand voltage | 4 kV | |
| Test voltage | 100-250 V | |
| Standards | IEC / EN 61008 | |
| Protection rating | IP2X | |
| Pollution degree | 2 | |
| Mounting type | DIN rail | |
| Dimensions (H × W × D) | 85 × 72 × 69.5 mm | |
| Weight | Approx. 500 g |
The ABB F204 A S-125/0.5 is used to provide selective residual current protection in three-phase electrical installations, helping isolate earth leakage faults while coordinating with downstream protective devices.
The 125 A rated current indicates the maximum current the RCCB is designed to carry continuously under normal operating conditions.
The 500 mA residual operating current is the earth leakage threshold at which the RCCB is designed to disconnect the circuit.
A selective RCCB uses time-delayed tripping to improve discrimination with downstream residual current devices, helping reduce unnecessary upstream power interruptions.
The RCCB mounts directly onto a standard DIN rail within distribution boards, switchboards and electrical control panels.
ABB F200 series residual current circuit breakers are widely trusted by electrical contractors, panel builders and maintenance engineers for dependable earth fault protection across commercial and industrial installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.