ABB F202 A S-63/0,3 RCD - 2P - Type A - 63A - 300mA - 1kA

ABB F202 A S-63/0,3 RCD – 2P – Type A – 63A – 300mA – 1kA

ABB F202 A S-63/0.3 selective 2-pole Type A residual current circuit breaker with 63 A rated current and 300 mA residual operating current.

SKU: F202 A S-63/0,3Alt SKU: F202 A S-63/0.3MPN: 2CSF202201R3630
Price
List Price £278.00 ex VAT
Your Price (ex VAT) Save 35%
£180.70 35% OFF
You save £97.30 per unit
Manufacturer Lead Time Estimated Delivery 4 - 5 Days
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £180.70
Trade pricing is personalised to your account

Manufacturer Lead Time

£180.70

Why Choose the ABB F202 A S-63/0.3 Residual Current Circuit Breaker?

The ABB F202 A S-63/0.3 is a selective 2-pole residual current circuit breaker (RCCB) designed to provide dependable protection against earth leakage faults in residential, commercial and industrial electrical installations. Identified by ABB product code 2CSF202201R3630, this device forms part of the trusted ABB F200 RCCB series, providing reliable protection for both people and equipment whilst ensuring excellent selectivity with downstream protective devices.

This Type A selective RCCB detects alternating residual currents and pulsating DC residual currents, making it suitable for modern electrical installations supplying electronic equipment. The selective operating characteristic introduces a controlled time delay, improving discrimination with downstream RCCBs and helping maintain continuity of service during fault conditions.

With a rated current of 63 A and a 300 mA residual operating current, the ABB F202 A S-63/0.3 is ideal for distribution boards, switchgear and industrial control panels where selective earth leakage protection and enhanced fire protection are required.

Key Advantages

  • High-quality 2-pole Type A selective RCCB.
  • 63 A rated current for higher-load distribution circuits.
  • 300 mA residual trip sensitivity for earth fault and fire protection.
  • Selective time-delayed operation for improved discrimination.
  • Detects AC and pulsating DC residual currents.
  • Compact DIN rail mounted residual current device.

Key Features

  • ABB F200 residual current circuit breaker series.
  • Product code: 2CSF202201R3630.
  • Model: F202 A S-63/0.3.
  • 2-pole RCCB configuration.
  • 63 A rated current.
  • 300 mA rated residual operating current.
  • Type A residual current detection.
  • Selective operating characteristic.
  • Screw terminal connection.
  • DIN rail mounting.

Selective Earth Leakage Protection for Electrical Installations

Residual current circuit breakers continuously monitor the balance between live and neutral conductors. If earth leakage exceeds the specified threshold, the RCCB disconnects the circuit, helping reduce the risk of electric shock and electrical fires caused by insulation faults.

The selective operating characteristic of the ABB F202 A S-63/0.3 introduces a controlled delay before tripping, allowing downstream RCCBs to clear local faults first. This improves system discrimination and reduces unnecessary interruption of healthy circuits.

Typical Applications

  • Main distribution boards.
  • Industrial switchgear.
  • Commercial electrical installations.
  • Building services infrastructure.
  • Control panels.
  • Installations requiring selective residual current protection.

Technical Specifications

Tick the specs you need, then view products that match.

Product Series ABB F200
Current 63 A
Poles 2-pole
Device Type RCD
Breaking Capacity 1 kA
Residual Current 300 mA
RCD Type Type A
Manufacturer ABB
Series F200
Model F202 A S-63/0.3
Product code 2CSF202201R3630
EAN 8012542784401
Product type Residual Current Circuit Breaker (RCCB)
Number of poles 2
Rated current 63 A
Rated residual operating current 300 mA
Residual current type Type A
Operating characteristic Selective
Rated voltage 230 V AC
Test voltage (Ut) 110-254 V
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Maximum surge current 5 kA
Rated conditional short-circuit current 10 kA
Rated service short-circuit breaking capacity 1 kA
Frequency 50 / 60 Hz
Mounting type DIN rail
Electrical endurance 10,000 cycles
Mechanical endurance 20,000 cycles
Dimensions (H × W × D) 85 × 35 × 69 mm
Weight approx. 0.20 kg
HS Code 85363030
Country of Manufacture Italy

Frequently Asked Questions

What is the ABB F202 A S-63/0.3 used for?

It provides selective residual current protection by disconnecting electrical circuits when dangerous earth leakage currents are detected.

What is the rated current of this RCCB?

The ABB F202 A S-63/0.3 has a 63 A rated current.

What residual current sensitivity does it provide?

The device has a 300 mA rated residual operating current, making it suitable for earth fault and fire protection applications.

What does the selective operating characteristic provide?

Selective RCCBs introduce a time delay that allows downstream protection devices to trip first, improving discrimination and reducing unnecessary supply interruptions.

How is the ABB F202 A S-63/0.3 installed?

The RCCB is designed for standard DIN rail mounting inside electrical distribution boards and modular switchgear assemblies.

Trusted by Electrical Professionals Worldwide

ABB F200 selective residual current circuit breakers are trusted by electricians, panel builders and industrial engineers for dependable earth leakage protection, excellent discrimination and long-term operational reliability.