Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
£246.24
The ABB DSE203NMC63A10 is a compact 3P+N electronic residual current circuit breaker with overcurrent protection (eRCBO) designed to protect three-phase electrical circuits against overloads, short circuits and earth leakage faults. As part of the ABB DSE203N M series, it combines overcurrent and residual current protection within a single modular device, helping reduce enclosure space while simplifying installation.
Developed for commercial, industrial and OEM applications, the DSE203NMC63A10 provides dedicated protection for individual three-phase circuits. Its electronic residual current monitoring, unswitched neutral and DIN rail mounting make it suitable for modern distribution boards and control panels.
Featuring a 63 A rated current, Type C tripping characteristic, 10 mA Type A residual current sensitivity and 10 kA short-circuit breaking capacity, this ABB RCBO is ideal for higher-load circuits with moderate starting currents where enhanced earth leakage protection is required.
The ABB DSE203NMC63A10 continuously monitors the protected circuit for overloads, short circuits and earth leakage currents. When a fault is detected, the RCBO disconnects the affected circuit quickly, helping protect equipment, reduce downtime and improve electrical safety.
Its integrated design allows overload and residual current protection to be provided by a single device, helping simplify panel layouts while enabling individual circuit isolation.
The Type C tripping characteristic is intended for circuits that experience moderate inrush currents during normal operation, including suitably designed motor circuits, pumps, transformers, lighting installations and industrial machinery.
The DSE203NMC63A10 incorporates Type A residual current protection, detecting both sinusoidal AC and pulsating DC earth leakage currents. Its 10 mA sensitivity provides enhanced protection where specified by the installation design and applicable wiring regulations.
The ABB DSE203NMC63A10 is designed for DIN rail installation inside compatible electrical enclosures. Installation should be carried out by a competent electrical professional in accordance with ABB instructions and the applicable wiring regulations.
Tick the specs you need, then view products that match.
| Current | 63 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 3-pole + N | |
| Device Type | RCBO | |
| Trip Curve | C curve | |
| Residual Current | 10 mA | |
| RCD Type | Type A | |
| Function | 3P+N electronic residual current circuit breaker with overcurrent protection (eRCBO). | |
| Residual Current Type | Type A, with 30 mA versions for direct contact protection. | |
| Poles | 3 protected poles plus neutral (neutral unswitched). | |
| Operating Characteristic | Instantaneous trip for short-circuit and overload protection. | |
| Connection Type | Bottom power supply connection with neutral terminals on the left. | |
| Connecting Capacity | Busbar 10 mm²; rigid cables 1–25 mm²; flexible cables 1–16 mm². | |
| Electrical Endurance | 10,000 cycles. | |
| Mechanical Endurance | 20,000 cycles. | |
| Weight | 0.549 kg. |
The ABB DSE203NMC63A10 provides combined overload, short-circuit and earth leakage protection for individual three-phase electrical circuits.
The DSE203NMC63A10 has a rated current of 63 A.
Type C devices are suitable for circuits with moderate inrush currents, including many commercial and industrial loads.
This RCBO provides 10 mA Type A residual current protection capable of detecting both AC and pulsating DC leakage currents.
The device has a rated short-circuit breaking capacity of 10 kA.
It is designed for DIN rail installation within commercial and industrial distribution boards, switchboards and electrical control panels.
The ABB DSE203NMC63A10 combines 63 A Type C overcurrent protection with sensitive 10 mA Type A residual current detection, delivering reliable protection for modern three-phase electrical installations.