Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
£215.65
The ABB DSE203NMC13A10 is a compact and dependable electronic residual current circuit breaker with overcurrent protection (eRCBO) designed to protect three-phase electrical circuits against overloads, short circuits and earth leakage faults. Part of the ABB DSE203N M series, it combines residual current and overcurrent protection within a single DIN rail device, helping simplify electrical distribution-board design.
This electronic RCBO is suitable for commercial, industrial and machine-building installations where reliable circuit protection and efficient use of panel space are important. Its 3P+N configuration allows it to protect three-phase circuits incorporating a neutral conductor, while electronic residual current monitoring supports accurate detection of potentially hazardous leakage currents.
With a rated current of 13 A, a Type C tripping characteristic, 10 mA Type A residual current sensitivity and a 10 kA short-circuit breaking capacity, the DSE203NMC13A10 is suitable for circuits supplying equipment with moderate starting currents while providing enhanced protection against electric shock.
The ABB DSE203NMC13A10 monitors the protected circuit for excessive current and leakage to earth. When an overload, short circuit or residual current fault occurs, the RCBO disconnects the affected circuit to help reduce the risk of equipment damage, electrical fire and electric shock.
Its Type C operating characteristic is suitable for circuits supplying equipment with moderate inrush currents, including selected motors, lighting systems and control equipment. The sensitive 10 mA residual current threshold provides enhanced additional protection where a lower leakage-current trip level is required.
Tick the specs you need, then view products that match.
| Poles | 3-pole + N | |
|---|---|---|
| Current | 13 A | |
| Phase | Three Phase | |
| Device Type | RCBO | |
| Trip Curve | C curve | |
| Residual Current | 10 mA | |
| RCD Type | Type A | |
| Function | 3P+N electronic residual current circuit breaker with overcurrent protection (eRCBO). | |
| Poles | 3 poles plus neutral (neutral unswitched). | |
| Residual Current Type | Type A with 30 mA version for additional direct contact protection. | |
| Operating Characteristic | Instantaneous trip for short-circuit and overload protection. | |
| Connecting Capacity | Busbar and terminals accept rigid conductors 1–25 mm² and flexible conductors 1–16 mm². | |
| Electrical Endurance | 10,000 cycles; Mechanical Endurance: 20,000 cycles. | |
| Position of Neutral Terminals | Left side. |
The ABB DSE203NMC13A10 protects three-phase electrical circuits against overloads, short circuits and earth leakage faults.
The DSE203NMC13A10 has a rated current of 13 A.
A Type C tripping characteristic is suitable for circuits with moderate starting currents, including selected motors, lighting systems and control equipment.
This model provides 10 mA Type A residual current protection, detecting sinusoidal AC and pulsating DC leakage currents.
It is designed for DIN rail installation within commercial or industrial electrical distribution boards and control panels.
ABB DSE203N M electronic RCBOs are widely specified by electrical contractors, panel builders and industrial engineers for compact installation, dependable fault protection and reliable performance in modern electrical systems.