Why Choose the ABB DSE203NMB13A10 RCBO?

The ABB DSE203NMB13A10 is a compact 3P+N electronic residual current circuit breaker with overcurrent protection (eRCBO) engineered to provide dependable protection against overloads, short circuits and earth leakage faults in three-phase electrical systems. As part of the advanced ABB DSE203N M series, it integrates multiple protection functions into a single three-module device, making it ideal for commercial, industrial and OEM electrical installations.

Designed to simplify panel construction while improving electrical safety, the DSE203NMB13A10 features electronic residual current monitoring, an unswitched neutral and a compact DIN rail mounted design. Its robust construction and reliable operating characteristics make it suitable for demanding applications where dependable circuit protection is essential.

With a 13 A Type B tripping characteristic, 10 kA breaking capacity and 10 mA Type A residual current sensitivity, the ABB DSE203NMB13A10 is well suited to protecting three-phase circuits supplying resistive and low inrush current loads while providing enhanced protection against electric shock.

Key Advantages

  • Compact 3P+N electronic RCBO combining overcurrent and residual current protection.
  • 13 A Type B characteristic for low inrush current circuits.
  • 10 mA Type A residual current protection for enhanced personnel safety.
  • 10 kA short-circuit breaking capacity for demanding installations.
  • Space-saving three-module DIN rail design.
  • Suitable for commercial, industrial and OEM electrical systems.

Key Features

  • ABB DSE203N M electronic RCBO series.
  • 3 poles + neutral (unswitched neutral).
  • 13 A rated current.
  • Type B tripping characteristic.
  • 10 mA Type A residual current protection.
  • 10 kA rated breaking capacity.
  • Electronic residual current detection.
  • DIN rail mounting for distribution boards and control panels.

Reliable Protection for Three-Phase Electrical Systems

The ABB DSE203NMB13A10 continuously monitors circuits for overloads, short circuits and earth leakage faults. If a fault is detected, the RCBO disconnects the circuit rapidly, helping protect equipment, reduce downtime and improve electrical safety for personnel.

Its Type B tripping characteristic makes it particularly suitable for circuits supplying resistive loads and other equipment with relatively low inrush currents. The integrated 10 mA Type A residual current protection provides enhanced protection by detecting both AC and pulsating DC leakage currents.

Typical Applications

  • Commercial electrical distribution boards.
  • Industrial control panels.
  • Machine building and OEM equipment.
  • Three-phase power distribution.
  • Manufacturing and automation systems.
  • Critical circuits requiring enhanced residual current protection.

Technical Specifications

Tick the specs you need, then view products that match.

Poles 3-pole + N
Current 13 A
Phase Three Phase
Device Type RCBO
Trip Curve B curve
Residual Current 10 mA
RCD Type Type A
Function 3P+N electronic residual current circuit breaker with overcurrent protection (eRCBO).
Number of Poles 3 poles plus neutral (neutral unswitched).
Residual Current Type Type A, 30 mA versions provide additional direct contact protection.
Connection Type Bottom power supply connection.
Terminal Capacity Busbar 10 mm², rigid wiring 1 to 25 mm², flexible wiring 1 to 16 mm².
Mechanical Endurance 20,000 cycles.
Electrical Endurance 10,000 cycles.
Operating Characteristic Instantaneous earth fault response.
Position of Neutral Terminals Left side.
Earthing Switch Type Undelayed for rapid fault disconnection.

Frequently Asked Questions

What is the ABB DSE203NMB13A10 used for?

It provides combined protection against overloads, short circuits and earth leakage faults on three-phase electrical circuits.

What is the rated current of this RCBO?

The ABB DSE203NMB13A10 has a 13 A rated current.

What does the Type B tripping characteristic mean?

Type B devices are intended for circuits with relatively low inrush currents, making them suitable for resistive loads and selected control circuits.

What residual current protection does this model provide?

This RCBO provides 10 mA Type A residual current protection capable of detecting AC and pulsating DC earth leakage currents.

Where is the ABB DSE203NMB13A10 typically installed?

It is designed for DIN rail installation within commercial and industrial distribution boards, switchboards and machine control panels.

Trusted by Electrical Professionals Worldwide

ABB DSE203N M electronic RCBOs are trusted by electrical contractors, panel builders and industrial engineers for dependable circuit protection, compact installation and reliable long-term performance in demanding electrical installations.