Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DSN201E B20 A30 is a compact 1P+N Type A electronic RCBO with a 20 A B-curve rating, 30 mA residual current sensitivity and 6 kA breaking capacity for overload, short-circuit and earth leakage protection.
£131.46
The ABB DSN201E B20 A30 is a compact 1P+N electronic residual current circuit breaker with overcurrent protection (eRCBO) designed to protect electrical circuits against overloads, short circuits and earth leakage faults. As part of the ABB DSN201E RCBO series, it combines overcurrent and residual current protection within a space-saving single-module device for residential, commercial and industrial electrical installations.
This Type A RCBO detects sinusoidal AC and pulsating DC residual currents while providing a B-curve overcurrent characteristic. Its switched neutral configuration disconnects the neutral together with the protected pole, while the voltage-dependent electronic design and flexible top or bottom supply connection simplify integration into modern DIN-rail distribution systems.
With a rated current of 20 A, 30 mA residual current sensitivity and 6 kA breaking capacity, the DSN201E B20 A30 provides comprehensive protection for suitable final circuits. Its compact 17.8 mm single-module width and reduced 86 mm height help maximise available space inside electrical distribution boards and control panels.
RCBOs combine the functions of overcurrent and residual current protection within a single protective device. The ABB DSN201E B20 A30 protects its connected circuit against excessive current caused by overloads and short circuits while also responding to residual earth fault currents, helping provide comprehensive electrical protection without requiring separate MCB and residual current devices.
The Type A characteristic enables detection of both sinusoidal alternating and direct pulsating residual currents, while the B-curve overcurrent characteristic provides defined tripping behaviour for suitable final circuits. Its compact 1P+N construction, switched neutral and flexible top or bottom supply arrangement make the DSN201E series particularly suitable for modern space-conscious electrical distribution systems.
| Series | DSN201E |
|---|---|
| ABB order code | 2TAZ264114R2201 |
| Product type | Electronic residual current circuit breaker with overcurrent protection (eRCBO) |
| Number of poles | 1P+N |
| Protected poles | 1 |
| Rated current | 20 A |
| Tripping characteristic | B curve |
| Residual current type | Type A |
| Rated residual current | 30 mA |
| Breaking capacity | 6 kA |
| Rated voltage | 240 V AC |
| Frequency | 50/60 Hz |
| Neutral | Switched |
| Operating principle | Voltage dependent |
| Operating characteristic | Instantaneous |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Energy limiting class | 3 |
| Protection rating | IP40 housing / IP20 terminals |
| Mounting type | 35 mm DIN rail |
| Supply connection | Top or bottom |
| Conductor capacity | up to 16 mm² flexible / 25 mm² rigid |
| Busbar capacity | up to 10 mm² |
| Electrical endurance | 10,000 cycles |
| Mechanical endurance | 20,000 cycles |
| Dimensions (H × D × W) | 86 × 70 × 17.8 mm |
| Weight | approx. 0.119 kg |
| Standards | IEC 61009-1, IEC 61009-2-2, AS/NZS 61009.1 |
The ABB DSN201E B20 A30 is an RCBO designed to protect electrical circuits against overloads, short circuits and residual earth leakage currents in residential, commercial and industrial installations.
The RCBO has a rated current of 20 A and uses a B-curve tripping characteristic.
The DSN201E B20 A30 has a rated residual operating current of 30 mA and provides Type A residual current protection.
The DSN201E B20 A30 has a rated short-circuit breaking capacity of 6 kA.
The ABB order code for the DSN201E B20 A30 is 2TAZ264114R2201.
ABB DSN201E RCBOs provide compact combined residual current and overcurrent protection for residential, commercial and industrial electrical installations, helping protect circuits against earth leakage, overload and short-circuit conditions.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.