2TAZ264114R1104 ABB DSN201E C10 A10 RCBO 1P+N 10 A Type A 10 mA 6 kA

2TAZ264114R1104 ABB DSN201E C10 A10 RCBO 1P+N 10 A Type A 10 mA 6 kA

ABB DSN201E C10 A10 electronic 1P+N RCBO with 10 A rated current, C tripping characteristic, Type A 10 mA residual current protection and 6 kA short-circuit capacity.

SKU: 2TAZ264114R1104Alt SKU: DSN201EC10A10MPN: 2TAZ264114R1104
Price
List Price £141.99 ex VAT
Your Price (ex VAT)
£141.99
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £141.99
Trade pricing is personalised to your account

Manufacturer Lead Time

£141.99

Why Choose the ABB DSN201E C10 A10 RCBO?

The ABB DSN201E C10 A10 is a compact 1P+N electronic residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and earth leakage faults. Combining residual current and overcurrent protection in a single one-module device helps simplify distribution-board design while providing comprehensive circuit protection.

This DSN201E variant combines a 10 A rated current, C tripping characteristic, 10 mA residual current sensitivity and Type A residual current detection. Type A protection detects sinusoidal alternating and pulsating DC residual currents, while the sensitive 10 mA trip level provides enhanced earth leakage protection for suitably selected applications.

With a 6 kA rated short-circuit capacity, switched neutral and compact 17.8 mm single-module width, the DSN201E C10 A10 provides space-efficient protection for residential, commercial and industrial installations. Its DIN-rail format, top or bottom supply capability and compatibility with ABB DSCC-series accessories support straightforward panel integration.

Key Advantages

  • Combines overload, short-circuit and residual current protection in one compact RCBO.
  • 10 A rated current for appropriately rated single-phase final circuits.
  • C tripping characteristic accommodates moderate starting and inrush currents.
  • Sensitive 10 mA residual operating current for enhanced earth leakage protection.
  • Type A residual current protection detects sinusoidal AC and pulsating DC earth fault currents.
  • 6 kA short-circuit capacity.
  • 1P+N configuration with switched neutral.
  • Compact 17.8 mm one-module width conserves distribution-board space.
  • Suitable for residential, commercial and industrial electrical installations.

Key Features

  • ABB DSN201E electronic RCBO.
  • 1P+N pole configuration.
  • 10 A rated current.
  • C tripping characteristic.
  • Type A residual current protection.
  • 10 mA rated residual operating current.
  • 6 kA rated short-circuit capacity.
  • 160–264 V AC test voltage range.
  • 50–60 Hz rated frequency.
  • Switched neutral.
  • Voltage-dependent electronic RCBO construction.
  • 2.5 kV dielectric test voltage and 4 kV impulse withstand voltage.

Type A Residual Current and Overcurrent Protection

The ABB DSN201E C10 A10 combines miniature circuit breaker and residual current protection functions in one compact device. It protects against overload and short-circuit currents while monitoring current balance between the live and neutral conductors to detect leakage to earth, providing individual protection for the connected final circuit.

Its Type A residual current characteristic responds to sinusoidal alternating and pulsating DC residual currents, making it suitable for circuits containing modern electronic equipment that may generate non-sinusoidal earth leakage. The 10 mA sensitivity provides a particularly sensitive residual current threshold, while the C characteristic accommodates moderate inrush currents from suitable connected loads.

Typical Applications

  • Residential single-phase final circuits.
  • Commercial electrical distribution boards.
  • Industrial low-voltage control and distribution panels.
  • Circuits supplying electronic equipment capable of producing pulsating DC residual currents.
  • Final circuits requiring sensitive 10 mA residual current protection.
  • Lighting and general-purpose circuits with moderate inrush currents.
  • Distribution boards requiring compact individual RCBO protection.
  • Applications requiring combined overload, short-circuit and earth leakage protection.

Technical Specifications

Series DSN201E
ABB order code 2TAZ264114R1104
Product group DSN201E RCBO
Product type Electronic residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 1P+N
Neutral Switched
Rated current 10 A
Tripping characteristic C
Residual current type A
Rated residual operating current (IΔn) 10 mA
Rated short-circuit capacity 6 kA
Input voltage type AC
Test voltage 160–264 V
Rated frequency 50–60 Hz
Dielectric test voltage 2.5 kV
Rated impulse withstand voltage (Uimp) 4 kV
Power loss 2.3 W
Overvoltage category III
Pollution degree 2
Electrical endurance 10,000 operating cycles
Mechanical endurance 20,000 operating cycles
Reference ambient temperature 30 °C
Ambient operating temperature -25 to +55 °C
Storage temperature -25 to +70 °C
Housing protection rating IP40
Terminal protection rating IP20
Flexible conductor capacity up to 16 mm²
Rigid conductor capacity up to 25 mm²
Busbar capacity up to 10 mm²
Terminal tightening torque 1.2 Nm
Wire stripping length 13 mm
Mounting 35 mm DIN rail to EN 60715
Mounting position Vertical or horizontal
Supply connection Top or bottom
Dimensions (H × D × W) 86 × 70 × 17.8 mm
Width 1 module
Product net weight 0.119 kg
EAN 6941593498277
Standards IEC 61009-1; IEC 61009-2-2; AS/NZS 61009.1

Frequently Asked Questions

What is the ABB DSN201E C10 A10?

The ABB DSN201E C10 A10 is a 1P+N electronic RCBO combining overload and short-circuit protection with 10 mA Type A residual current protection in a compact one-module DIN-rail device.

What is the rated current and tripping characteristic of the DSN201E C10 A10?

The DSN201E C10 A10 has a rated current of 10 A and a C tripping characteristic, making it suitable for appropriately rated circuits that may experience moderate starting or inrush currents.

What does Type A protection mean on the DSN201E C10 A10?

Type A residual current protection detects sinusoidal alternating residual currents as well as pulsating DC residual currents, providing protection for circuits where compatible electronic loads may be present.

What is the residual current sensitivity of the DSN201E C10 A10?

The RCBO has a rated residual operating current of 10 mA, providing a more sensitive earth leakage threshold than conventional 30 mA variants for applications where 10 mA protection is specified.

What is the breaking capacity of the ABB DSN201E C10 A10?

The DSN201E C10 A10 has a rated short-circuit capacity of 6 kA and should be selected and installed in accordance with the prospective fault current and applicable electrical installation requirements.

Trusted ABB Circuit Protection Technology

ABB DSN201E electronic RCBOs combine residual current, overload and short-circuit protection in a compact 1P+N format, providing space-efficient circuit protection for residential, commercial and industrial low-voltage electrical installations.