2CSS255102R0064 ABB SN201-C6-L Miniature Circuit Breaker 1P+N Type C 6 A 6 kA Left Neutral

2CSS255102R0064 ABB SN201-C6-L Miniature Circuit Breaker 1P+N Type C 6 A 6 kA Left Neutral

ABB SN201-C6-L miniature circuit breaker, a 6 A 1P+N Type C MCB for 230 V AC circuits with left-hand neutral, 6 kA rated short-circuit capacity and compact single-module construction.

SKU: 2CSS255102R0064Alt SKU: SN201C6LMPN: 2CSS255102R0064
Price
List Price £35.47 ex VAT
Your Price (ex VAT) Save 45%
£19.51 45% OFF
You save £15.96 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £19.51
Trade pricing is personalised to your account

Manufacturer Lead Time

£19.51

Why Choose the ABB SN201-C6-L Miniature Circuit Breaker?

The ABB SN201-C6-L is a compact 1P+N miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits while providing simultaneous neutral switching. Part of the ABB System pro M compact SN201 range, it combines phase protection and neutral switching within a space-saving single-module format for residential and commercial final distribution applications.

Featuring a Type C tripping characteristic, the SN201-C6-L is suitable for general-purpose circuits and loads with moderate starting or inrush currents. This specific -L version positions the neutral terminal on the left, making it particularly useful in installations and distribution arrangements where a left-hand neutral configuration is required.

With a rated current of 6 A, rated voltage of 230 V AC and a rated short-circuit capacity of 6 kA, the SN201-C6-L provides dependable protection in an 18 mm-wide device. ABB order code 2CSS255102R0064 identifies this specific 6 A Type C, left-neutral model.

Key Advantages

  • Reliable overload and short-circuit protection for final distribution circuits.
  • 6 A rated current suitable for low-current electrical, control and auxiliary circuits.
  • Type C tripping characteristic accommodates moderate normal starting and inrush currents.
  • 1P+N configuration combines a protected phase pole with simultaneous neutral switching.
  • Neutral terminal positioned on the left for installations requiring a left-hand neutral arrangement.
  • 6 kA rated short-circuit capacity according to IEC/EN 60898-1.
  • Compact 18 mm single-module design helps conserve DIN-rail space.

Key Features

  • ABB System pro M compact SN201 series.
  • 6 A rated current.
  • 1P+N configuration.
  • 1 protected phase pole plus switched neutral.
  • Neutral terminal position: left.
  • Type C tripping characteristic.
  • Thermal protection against sustained overload currents.
  • Electromagnetic protection against short-circuit currents.
  • 6 kA rated short-circuit capacity (Icn).
  • 10 kA ultimate short-circuit breaking capacity (Icu).
  • Energy limiting class 3.
  • Single-module DIN-rail construction for space-efficient installation.

Compact Protection with Left-Hand Neutral

Miniature circuit breakers such as the ABB SN201-C6-L automatically disconnect the protected phase conductor when an overload or short circuit occurs. Thermal and electromagnetic tripping mechanisms provide protection against sustained overcurrents and short-circuit faults, helping protect conductors, equipment and connected loads.

The SN201-C6-L combines this protection with simultaneous neutral switching in a compact single-module arrangement. Its Type C characteristic makes it suitable for circuits with moderate normal inrush currents, while the left-hand neutral configuration provides a practical solution for distribution systems specifically requiring the neutral connection on the left.

Typical Applications

  • Residential final distribution circuits.
  • Commercial electrical installations.
  • Low-current control and auxiliary circuits.
  • Lighting and general-purpose circuits.
  • Distribution boards requiring a left-hand neutral connection.
  • Final distribution and long-cable applications in suitable TN and IT systems.
  • Installations where DIN-rail space is limited.

Technical Specifications

Series SN201
Product range System pro M compact
Product group S200 MCB
ABB order code 2CSS255102R0064
EAN/GTIN 8012542089353
Product type Miniature circuit breaker (MCB)
Pole configuration 1P+N
Number of protected poles 1
Neutral Switched neutral
Neutral terminal position Left
Rated current 6 A
Tripping characteristic Type C
Rated voltage 230 V AC
Rated short-circuit capacity (Icn) 6 kA
Ultimate short-circuit breaking capacity (Icu) 10 kA
Service short-circuit breaking capacity (Ics) 6 kA
Rated impulse withstand voltage 4 kV
Dielectric test voltage 2.5 kV
Energy limiting class 3
Overvoltage category III
Pollution degree 2
Protection rating IP40 housing, IP20 terminals
Mounting type DIN rail
Number of modular spaces 1
Terminal type Screw terminal
Rigid conductor capacity 0–16 mm²
Flexible conductor capacity 0–10 mm²
Tightening torque 1.2 N·m
Width 18 mm
Height 85 mm
Depth 69 mm
Net weight 0.11 kg
Power loss 2.3 W
Operating temperature -25 to +55 °C
Electrical endurance 10,000 cycles
Mechanical endurance 20,000 cycles
Standard IEC/EN 60898-1

Frequently Asked Questions

What is the ABB SN201-C6-L used for?

The ABB SN201-C6-L is a 1P+N miniature circuit breaker used to protect electrical circuits against overloads and short circuits while also switching the neutral conductor.

What is the current rating of the SN201-C6-L?

The SN201-C6-L has a rated current of 6 A and is designed for 230 V AC applications.

What does the Type C characteristic mean?

The Type C tripping characteristic is suitable for general-purpose circuits and equipment that can produce moderate starting or inrush currents during normal operation.

What is the breaking capacity of the ABB SN201-C6-L?

The SN201-C6-L has a rated short-circuit capacity of 6 kA and an ultimate short-circuit breaking capacity of 10 kA.

What does the “L” mean on the SN201-C6-L?

The “L” identifies the left-neutral version of the SN201-C6, meaning the neutral terminal is positioned on the left side of the device.

Trusted Circuit Protection from ABB

ABB SN201 miniature circuit breakers provide dependable overload and short-circuit protection in a compact single-module format, combining phase protection, neutral switching and established thermal and electromagnetic tripping technology.