Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202CRMB32APR30 is a 2-pole APR Type A RCBO with a 32 A B-curve rating, 30 mA residual current sensitivity and 10 kA breaking capacity, offering increased resistance to unwanted tripping.
£194.46
The ABB DS202CRMB32APR30 is a compact 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents. Part of the ABB DS202CR M APR series, it combines overcurrent and residual current protection within a space-saving two-module device for residential, commercial and industrial electrical installations.
This RCBO features ABB's APR Type A residual current characteristic, providing protection against the effects of sinusoidal alternating and direct pulsating earth fault currents while offering increased resistance to unwanted tripping. Its Type B overcurrent tripping characteristic is suited to general circuits with relatively low inrush currents, while its 30 mA residual current sensitivity provides protection against indirect contact and additional protection against direct contact.
With a rated current of 32 A, rated residual operating current of 30 mA, rated voltage of 230 V and rated short-circuit breaking capacity of 10 kA, the DS202CRMB32APR30 delivers dependable combined protection in a compact DIN-rail format. ABB order code 2CSR772440R1325 identifies the DS202CR M B32 APR30 configuration.
The ABB DS202CRMB32APR30 combines miniature circuit breaker and residual current protection functions within a single compact device. It disconnects the protected circuit during overload or short-circuit conditions while also detecting sinusoidal alternating and direct pulsating earth fault currents, providing comprehensive protection without requiring separate MCB and residual current devices.
ABB's APR characteristic is designed to provide an effective balance between electrical safety and continuity of service through increased resistance to unwanted tripping caused by transient disturbances. With resistance to unwanted tripping of 3 kA on an 8/20 µs surge wave, the DS202CRMB32APR30 is particularly useful where improved continuity is required while retaining sensitive 30 mA residual current protection.
| Series | DS202CR M APR |
|---|---|
| Manufacturer type code | DS202CR M B32 APR30 |
| ABB order code | 2CSR772440R1325 |
| EAN | 4022903035329 |
| Product group | DS200 / DSH200 RCBO |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 32 A |
| Tripping characteristic | B |
| Residual current characteristic | APR Type A |
| Rated residual operating current | 30 mA |
| Rated voltage | 230 V |
| Rated frequency | 50 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 10 kA |
| Resistance to unwanted tripping (8/20 µs wave) | 3 kA |
| Protection rating | IP20 |
| Reference standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Mounting type | DIN rail |
| Module width | 2 modules |
| Dimensions (W × H × D) | 36 × 86 × 72 mm |
| Weight | approx. 0.245 kg |
The DS202CRMB32APR30 provides combined protection against overloads, short circuits and residual earth fault currents in end-user single-phase circuits, with an APR characteristic designed to increase resistance to unwanted tripping.
The ABB DS202CRMB32APR30 has a rated current of 32 A and uses a Type B overcurrent tripping characteristic.
The APR characteristic provides increased resistance to unwanted residual-current tripping, helping balance electrical safety and continuity of service while retaining Type A protection against sinusoidal AC and direct pulsating earth fault currents.
The DS202CRMB32APR30 has a rated residual operating current of 30 mA, providing protection against indirect contact and additional protection against direct contact.
The DS202CRMB32APR30 has a rated short-circuit breaking capacity of 10 kA.
ABB DS202CR M APR RCBOs combine residual current and overcurrent protection with enhanced resistance to unwanted tripping, providing dependable protection and improved continuity of service for residential, commercial and industrial electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.