Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202CR M C32 APR30 two-pole Type A AP-R RCBO with 32 A rated current, 30 mA residual current sensitivity, C tripping characteristic and 10 kA breaking capacity for 230 V AC residential, commercial and industrial circuit protection.
£194.46
The ABB DS202CR M C32 APR30 is a compact two-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents. As part of the ABB DS202CR range within the DS200 / DSH200 RCBO product group, it combines residual current and overcurrent protection in a space-saving two-module DIN-rail device.
This RCBO features Type A AP-R residual current protection, providing protection against sinusoidal alternating and pulsating direct residual currents while offering increased immunity to unwanted tripping. ABB's AP-R design provides a strong balance between electrical safety and continuity of service, particularly in installations where transient disturbances may otherwise cause unnecessary operation.
With a rated current of 32 A, a rated residual operating current of 30 mA, a 230 V AC rated voltage and a 10 kA short-circuit breaking capacity, the DS202CR M C32 APR30 provides comprehensive protection for higher-current final circuits. Its C tripping characteristic accommodates moderate starting and inrush currents, making it suitable for residential, commercial and industrial electrical installations.
RCBOs combine the functions of a miniature circuit breaker and residual current protection device within a single unit. The ABB DS202CR M C32 APR30 therefore protects single-phase circuits against excessive current caused by overloads and short circuits while simultaneously detecting residual earth leakage currents, providing protection against indirect contact and additional protection against direct contact.
The Type A AP-R characteristic is designed to balance electrical safety with continuity of service. Its increased immunity to unwanted tripping and 3,000 A surge-current withstand help reduce unnecessary operation caused by transient disturbances while retaining sensitive 30 mA residual current protection.
| Series | DS202CR |
|---|---|
| Product group | DS200 / DSH200 RCBO |
| Manufacturer material ID | DS202CRMC32APR30 |
| ABB order code | 2CSR772440R1324 |
| EAN | 4022903035312 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 32 A |
| Rated residual current | 30 mA |
| Residual current type | Type A AP-R |
| Tripping characteristic | C |
| Rated voltage | 230 V AC |
| Rated frequency | 50 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Resistance to unwanted tripping | 3,000 A (8/20 µs waveform) |
| Protection rating | IP20 |
| Dimensions (W × H × D) | 36 × 86 × 72 mm |
| Mounting type | DIN rail |
| Module width | 2 modules |
| Standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Applications | Residential, commercial and industrial electrical installations |
| Weight | approx. 0.245 kg |
This RCBO provides combined protection against overloads, short circuits and residual earth fault currents in residential, commercial and industrial single-phase final circuits.
The RCBO has a rated current of 32 A and uses a C tripping characteristic, making it suitable for circuits with moderate starting or inrush currents.
AP-R identifies ABB residual current protection designed with increased immunity to unwanted tripping. The DS202CR M C32 APR30 provides 3,000 A resistance to unwanted tripping with an 8/20 µs surge waveform, helping improve continuity of service.
The DS202CR M C32 APR30 has a rated residual operating current of 30 mA and provides Type A AP-R protection against sinusoidal alternating and pulsating direct residual currents.
The DS202CR M C32 APR30 has a rated short-circuit breaking capacity of 10 kA.
ABB DS202CR M AP-R RCBOs combine overcurrent and residual current protection with increased immunity to unwanted tripping, providing dependable protection and improved continuity of service in residential, commercial and industrial electrical installations.