Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202CRMC32A300 is a 2-pole Type A RCBO with a 32 A C-curve rating, 300 mA residual current sensitivity and 10 kA breaking capacity for combined overcurrent and earth fault protection.
£181.97
The ABB DS202CRMC32A300 is a compact and highly reliable 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents. As part of the ABB DS202CR M series, it combines overcurrent and residual current protection within a space-saving two-module device for residential, commercial and industrial electrical installations.
This RCBO uses Type A residual current detection, providing protection against the effects of sinusoidal alternating and pulsating DC earth fault currents. Its Type C tripping characteristic makes it suitable for circuits where moderate inrush currents may occur, while its DIN-rail format enables straightforward integration into modular distribution boards and electrical panels.
With a rated current of 32 A, rated residual operating current of 300 mA and rated short-circuit breaking capacity of 10 kA, the DS202CRMC32A300 delivers comprehensive protection in a compact format. ABB order code 2CSR772140R3324 identifies this specific DS202CR M C32 Type A configuration.
RCBOs such as the ABB DS202CRMC32A300 combine miniature circuit breaker and residual current protection functions within a single device. The RCBO disconnects the protected circuit when overload or short-circuit conditions occur while also detecting residual earth fault currents, providing comprehensive protection without requiring separate MCB and residual-current devices.
The DS202CR series is designed for end-user single-phase circuits where dependable protection and efficient use of distribution-board space are important. Its Type A residual current characteristic responds to sinusoidal alternating and pulsating DC earth fault currents, while the Type C overcurrent characteristic accommodates the moderate starting currents encountered with many common electrical loads.
| Series | DS202CR M |
|---|---|
| ABB order code | 2CSR772140R3324 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 32 A |
| Tripping characteristic | C |
| Residual current type | Type A |
| Rated residual operating current | 300 mA |
| Rated voltage | 230 V AC |
| Rated frequency | 50 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 10 kA |
| Protection rating | IP20 |
| Reference standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Mounting type | DIN rail |
| Module width | 2 modules |
| Dimensions (W × H × D) | 36 × 86 × 72 mm |
| Weight | approx. 0.22 kg |
The DS202CRMC32A300 provides combined protection against overloads, short circuits and residual earth fault currents in end-user single-phase electrical circuits.
The ABB DS202CRMC32A300 has a rated current of 32 A and uses a Type C tripping characteristic.
The DS202CRMC32A300 has a rated residual operating current of 300 mA and uses Type A residual current detection for sinusoidal AC and pulsating DC earth fault currents.
The DS202CRMC32A300 has a rated short-circuit breaking capacity of 10 kA.
The DS202CRMC32A300 provides 2-pole protection in only two modules, allowing combined residual current and overcurrent protection within a compact DIN-rail installation.
ABB DS202CR RCBOs combine residual current and overcurrent protection in a compact two-module format, providing dependable circuit protection for residential, commercial and industrial electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.