2CSR772140R3324 ABB DS202CRMC32A300 RCBO 2P Type A C32 300 mA 10 kA

2CSR772140R3324 ABB DS202CRMC32A300 RCBO 2P Type A C32 300 mA 10 kA

ABB DS202CRMC32A300 is a 2-pole Type A RCBO with a 32 A C-curve rating, 300 mA residual current sensitivity and 10 kA breaking capacity for combined overcurrent and earth fault protection.

SKU: 2CSR772140R3324Alt SKU: DS202CRMC32A300MPN: 2CSR772140R3324
Price
List Price £279.96 ex VAT
Your Price (ex VAT) Save 35%
£181.97 35% OFF
You save £97.99 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £181.97
Trade pricing is personalised to your account

Manufacturer Lead Time

£181.97

Why Choose the ABB DS202CRMC32A300 RCBO?

The ABB DS202CRMC32A300 is a compact and highly reliable 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents. As part of the ABB DS202CR M series, it combines overcurrent and residual current protection within a space-saving two-module device for residential, commercial and industrial electrical installations.

This RCBO uses Type A residual current detection, providing protection against the effects of sinusoidal alternating and pulsating DC earth fault currents. Its Type C tripping characteristic makes it suitable for circuits where moderate inrush currents may occur, while its DIN-rail format enables straightforward integration into modular distribution boards and electrical panels.

With a rated current of 32 A, rated residual operating current of 300 mA and rated short-circuit breaking capacity of 10 kA, the DS202CRMC32A300 delivers comprehensive protection in a compact format. ABB order code 2CSR772140R3324 identifies this specific DS202CR M C32 Type A configuration.

Key Advantages

  • Combined overload, short-circuit and residual current protection in one device.
  • 32 A rated current for higher-current end-user circuits.
  • Type C tripping characteristic suitable for circuits with moderate inrush currents.
  • 300 mA residual current sensitivity for earth leakage protection.
  • Type A residual current detection for sinusoidal AC and pulsating DC earth fault currents.
  • 10 kA rated short-circuit breaking capacity for robust fault protection.
  • Compact 2-pole protection in only two modules helps conserve distribution-board space.
  • Suitable for residential, commercial and industrial electrical installations.

Key Features

  • ABB DS202CR M series RCBO.
  • 2-pole configuration in a two-module format.
  • 32 A rated current.
  • 300 mA rated residual operating current.
  • Type A residual current characteristic.
  • Type C overcurrent tripping characteristic.
  • 10 kA rated short-circuit breaking capacity.
  • 230 V AC rated voltage.
  • 50 Hz rated frequency.
  • IP20 protection rating.
  • DIN-rail mounting for modular electrical distribution equipment.

Reliable Combined Protection for Electrical Circuits

RCBOs such as the ABB DS202CRMC32A300 combine miniature circuit breaker and residual current protection functions within a single device. The RCBO disconnects the protected circuit when overload or short-circuit conditions occur while also detecting residual earth fault currents, providing comprehensive protection without requiring separate MCB and residual-current devices.

The DS202CR series is designed for end-user single-phase circuits where dependable protection and efficient use of distribution-board space are important. Its Type A residual current characteristic responds to sinusoidal alternating and pulsating DC earth fault currents, while the Type C overcurrent characteristic accommodates the moderate starting currents encountered with many common electrical loads.

Typical Applications

  • Residential electrical distribution boards.
  • Commercial building electrical installations.
  • Industrial electrical distribution systems.
  • End-user single-phase circuits requiring combined protection.
  • Circuits requiring Type A residual current detection.
  • General-purpose circuits with moderate inrush currents.
  • DIN-rail mounted modular distribution equipment.

Technical Specifications

Series DS202CR M
ABB order code 2CSR772140R3324
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 2
Rated current 32 A
Tripping characteristic C
Residual current type Type A
Rated residual operating current 300 mA
Rated voltage 230 V AC
Rated frequency 50 Hz
Rated short-circuit breaking capacity (Icn) 10 kA
Rated ultimate short-circuit breaking capacity (Icu) 10 kA
Protection rating IP20
Reference standards IEC/EN 61009-1; IEC/EN 61009-2-1
Mounting type DIN rail
Module width 2 modules
Dimensions (W × H × D) 36 × 86 × 72 mm
Weight approx. 0.22 kg

Frequently Asked Questions

What is the ABB DS202CRMC32A300 used for?

The DS202CRMC32A300 provides combined protection against overloads, short circuits and residual earth fault currents in end-user single-phase electrical circuits.

What is the rated current of the DS202CRMC32A300?

The ABB DS202CRMC32A300 has a rated current of 32 A and uses a Type C tripping characteristic.

What residual current sensitivity does this RCBO provide?

The DS202CRMC32A300 has a rated residual operating current of 300 mA and uses Type A residual current detection for sinusoidal AC and pulsating DC earth fault currents.

What is the breaking capacity of the ABB DS202CRMC32A300?

The DS202CRMC32A300 has a rated short-circuit breaking capacity of 10 kA.

How much distribution-board space does the DS202CRMC32A300 require?

The DS202CRMC32A300 provides 2-pole protection in only two modules, allowing combined residual current and overcurrent protection within a compact DIN-rail installation.

Trusted ABB Protection for Electrical Installations

ABB DS202CR RCBOs combine residual current and overcurrent protection in a compact two-module format, providing dependable circuit protection for residential, commercial and industrial electrical distribution systems.