ABB DS202CRMB20A300 is a 2-pole 20 A B-curve Type A RCBO with 300 mA residual current sensitivity, 230 V AC rating and 10 kA short-circuit breaking capacity for combined overcurrent and earth fault protection.

SKU: 2CSR772140R3205Alt SKU: DS202CRMB20A300MPN: 2CSR772140R3205
Price
List Price £279.96 ex VAT
Your Price (ex VAT) Save 35%
£181.97 35% OFF
You save £97.99 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £181.97
Trade pricing is personalised to your account

Manufacturer Lead Time

£181.97

Why Choose the ABB DS202CRMB20A300 RCBO?

The ABB DS202CRMB20A300 is a compact 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents. Part of the ABB DS202CR M series within the DS200 / DSH200 RCBO product group, it combines residual current and overcurrent protection in a space-saving two-module device.

This RCBO provides Type A residual current protection, responding to sinusoidal AC and pulsating DC residual currents. Its B tripping characteristic is suited to circuits with relatively low inrush currents, while the 300 mA rated residual operating current provides earth fault protection for installations where this sensitivity is specified.

With a rated current of 20 A, a rated operational voltage of 230 V AC and a 10 kA rated short-circuit breaking capacity, the DS202CRMB20A300 provides robust combined protection in a compact DIN rail format. Its two-pole, two-module construction makes it suitable for residential, commercial and industrial electrical installations.

Key Advantages

  • Combined residual current and overcurrent protection in one compact RCBO.
  • 20 A rated current with B tripping characteristic.
  • 300 mA Type A residual current protection.
  • Responds to sinusoidal AC and pulsating DC residual currents.
  • 10 kA rated short-circuit breaking capacity for robust fault protection.
  • 2-pole design in only two modules for efficient use of distribution board space.

Key Features

  • ABB DS202CR M RCBO series.
  • 2-pole configuration.
  • 20 A rated current.
  • B tripping characteristic.
  • Type A residual current protection.
  • 300 mA rated residual operating current.
  • 230 V AC rated operational voltage.
  • 50 Hz rated frequency.
  • 10 kA rated short-circuit breaking capacity (Icn).
  • 7.5 kA rated service short-circuit breaking capacity (Ics).
  • 10 kA rated ultimate short-circuit breaking capacity (Icu).
  • 440 V rated insulation voltage (Ui).
  • 4 kV rated impulse withstand voltage (Uimp).
  • IP20 protection rating.
  • DIN rail mounting in a compact two-module format.

Reliable Combined Circuit and Residual Current Protection

RCBOs combine the functions of a miniature circuit breaker and residual current device in a single protective device. The ABB DS202CRMB20A300 protects end-user single-phase circuits against overload and short-circuit currents while also disconnecting the supply when residual earth fault current reaches the device's operating threshold.

The Type A characteristic provides protection against the effects of sinusoidal alternating and pulsating direct residual currents. With its 300 mA residual current sensitivity, B tripping characteristic and 10 kA short-circuit breaking capacity, the DS202CRMB20A300 provides dependable combined protection for installations where 300 mA residual current protection is specified.

Typical Applications

  • Residential electrical installations where 300 mA residual current protection is specified.
  • Commercial electrical distribution systems.
  • Industrial electrical installations.
  • End-user single-phase circuits.
  • General-purpose circuits with relatively low inrush currents.
  • Circuits requiring Type A residual current detection.
  • Distribution boards requiring combined 20 A overcurrent and 300 mA residual current protection.

Technical Specifications

Series DS202CR M
Product group DS200 / DSH200 RCBO
ABB order code 2CSR772140R3205
EAN 4022903034735
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 2
Rated current 20 A
Tripping characteristic B
Residual current type Type A
Rated residual current 300 mA
Rated operational voltage 230 V AC
Rated frequency 50 Hz
Rated short-circuit breaking capacity (Icn) 10 kA
Rated service short-circuit breaking capacity (Ics) 7.5 kA
Rated ultimate short-circuit breaking capacity (Icu) 10 kA
Rated insulation voltage (Ui) 440 V
Rated impulse withstand voltage (Uimp) 4 kV
Pollution degree 3
Protection rating IP20
Standards IEC/EN 61009-1; IEC/EN 61009-2-1
Mounting type DIN rail
Module width 2 modules
Tightening torque 4 N·m
Operating temperature -25 to +55 °C
Dimensions (H × W × D) 86 × 36 × 72 mm
Weight approx. 0.245 kg

Frequently Asked Questions

What is the ABB DS202CRMB20A300 used for?

The ABB DS202CRMB20A300 is an RCBO designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents in residential, commercial and industrial installations where 300 mA residual current sensitivity is specified.

What is the current rating of the ABB DS202CRMB20A300?

The DS202CRMB20A300 has a rated current of 20 A and uses a B tripping characteristic.

What residual current protection does this RCBO provide?

The DS202CRMB20A300 provides Type A residual current protection with a rated residual operating current of 300 mA, responding to sinusoidal AC and pulsating DC residual currents.

What is the breaking capacity of the ABB DS202CRMB20A300?

The DS202CRMB20A300 has a rated short-circuit breaking capacity (Icn) of 10 kA, a rated service short-circuit breaking capacity (Ics) of 7.5 kA and a rated ultimate short-circuit breaking capacity (Icu) of 10 kA.

What does the B characteristic mean on the DS202CRMB20A300?

The B tripping characteristic is suited to circuits with relatively low inrush currents, making the RCBO appropriate for compatible resistive and general-purpose electrical loads where a B-curve protective characteristic is specified.