Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202CRMC13A300 is a 2-pole 13 A C-curve Type A RCBO with 300 mA residual current sensitivity, 230 V AC rating and 10 kA short-circuit breaking capacity for combined overcurrent and earth fault protection.
£181.97
The ABB DS202CRMC13A300 is a compact 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents. Part of the ABB DS202CR M series within the DS200 / DSH200 RCBO product group, it combines residual current and overcurrent protection in a space-saving two-module device.
This RCBO provides Type A residual current protection, responding to sinusoidal AC and pulsating DC residual currents. Its C tripping characteristic is suitable for circuits with moderate inrush currents, while the 300 mA rated residual operating current provides earth fault protection for installations where this sensitivity is specified.
With a rated current of 13 A, a rated operational voltage of 230 V AC and a 10 kA rated short-circuit breaking capacity, the DS202CRMC13A300 provides robust combined protection in a compact DIN rail format. Its two-pole, two-module construction makes it suitable for residential, commercial and industrial electrical installations.
RCBOs combine the functions of a miniature circuit breaker and residual current device in a single protective device. The ABB DS202CRMC13A300 protects end-user single-phase circuits against overload and short-circuit currents while also disconnecting the supply when residual earth fault current reaches the device's operating threshold.
The Type A characteristic provides protection against the effects of sinusoidal alternating and pulsating direct residual currents. With its 300 mA residual current sensitivity, C tripping characteristic and 10 kA short-circuit breaking capacity, the DS202CRMC13A300 provides dependable combined protection for installations where 300 mA residual current protection is specified.
| Series | DS202CR M |
|---|---|
| Product group | DS200 / DSH200 RCBO |
| ABB order code | 2CSR772140R3134 |
| EAN | 4022903034681 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 13 A |
| Tripping characteristic | C |
| Residual current type | Type A |
| Rated residual current | 300 mA |
| Rated operational voltage | 230 V AC |
| Rated frequency | 50 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Rated service short-circuit breaking capacity (Ics) | 7.5 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 10 kA |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Power loss | 8.92 W |
| Pollution degree | 3 |
| Protection rating | IP20 |
| Standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Mounting type | DIN rail |
| Module width | 2 modules |
| Tightening torque | 4 N·m |
| Operating temperature | -25 to +55 °C |
| Dimensions (H × W × D) | 86 × 36 × 72 mm |
| Weight | approx. 0.22 kg |
The ABB DS202CRMC13A300 is an RCBO designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents in residential, commercial and industrial installations where 300 mA residual current sensitivity is specified.
The DS202CRMC13A300 has a rated current of 13 A and uses a C tripping characteristic.
The DS202CRMC13A300 provides Type A residual current protection with a rated residual operating current of 300 mA, responding to sinusoidal AC and pulsating DC residual currents.
The DS202CRMC13A300 has a rated short-circuit breaking capacity (Icn) of 10 kA, a rated service short-circuit breaking capacity (Ics) of 7.5 kA and a rated ultimate short-circuit breaking capacity (Icu) of 10 kA.
The C tripping characteristic is suitable for circuits that can experience moderate inrush currents, making the RCBO appropriate for compatible residential, commercial and industrial electrical loads where a C-curve protective characteristic is specified.
ABB DS202CR M RCBOs combine residual current and overcurrent protection in a compact two-module format, providing dependable protection for end-user single-phase circuits across residential, commercial and industrial electrical installations.