Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202CRMB20A30 is a 20 A 2-pole Type A RCBO with B tripping characteristic and 30 mA residual-current sensitivity for combined overload, short-circuit and earth-fault protection.
£167.10
The ABB DS202CRMB20A30 is a 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to combine overload, short-circuit and residual-current protection within a single modular protective device. Part of the ABB DS200 / DSH200 RCBO range, the DS202CR M B20 A30 provides coordinated circuit and earth-fault protection for professional electrical distribution applications.
With a rated current of 20 A, B tripping characteristic and 30 mA rated residual operating current, this RCBO provides combined protection for electrical final circuits and connected equipment. Its Type A residual-current characteristic detects sinusoidal AC residual currents and pulsating DC residual currents, making it suitable for many modern circuits containing electronic equipment.
The 2-pole configuration provides switching of both circuit conductors, while the B characteristic is suitable for circuits with relatively low starting or inrush currents. Its 30 mA residual-current sensitivity supports additional protection against electric shock, making the DS202CRMB20A30 a practical solution where combined 20 A overcurrent and Type A residual-current protection is required.
An RCBO combines overcurrent and residual-current protection in one device, allowing the ABB DS202CRMB20A30 to respond to overloads and short circuits while also detecting leakage currents to earth. Its 30 mA residual-current sensitivity supports additional protection against electric shock while providing earth-fault protection for the connected circuit.
The Type A characteristic enables the DS202CRMB20A30 to detect sinusoidal alternating residual currents and pulsating DC residual currents. This capability makes Type A protection particularly relevant to modern installations containing electronic power supplies, controls and other equipment capable of producing pulsating DC residual-current components.
| Series | DS200 / DSH200 RCBO |
|---|---|
| Order code | 2CSR772140R1205 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 20 A |
| Tripping characteristic | B |
| Residual-current type | Type A |
| Rated residual current | 30 mA |
| Mounting type | DIN rail |
The DS202CRMB20A30 is a 2-pole RCBO used to protect electrical circuits against overloads, short circuits and residual earth fault currents.
The ABB DS202CRMB20A30 has a rated current of 20 A and uses a B tripping characteristic.
The DS202CRMB20A30 has a rated residual operating current of 30 mA, supporting additional protection against electric shock.
Type A means the RCBO is designed to detect sinusoidal AC residual currents as well as pulsating DC residual currents, making it suitable for many circuits containing modern electronic equipment.
The DS202CRMB20A30 is a 2-pole RCBO, providing switching of both circuit conductors.
ABB DS200 and DSH200 RCBOs combine overcurrent and residual-current protection in a compact modular format, providing dependable protection for modern electrical distribution and control installations.