Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS202CRC16A30 is a 2-pole 16 A C-curve Type A RCBO with 30 mA residual current sensitivity, 230 V AC rating and 6 kA short-circuit breaking capacity for combined overcurrent and earth fault protection.
£161.80
The ABB DS202CRC16A30 is a compact and reliable 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and residual earth fault currents. Part of the ABB DS202CR series, it combines residual current and overcurrent protection in a space-saving two-module device for residential, commercial and industrial electrical installations.
This RCBO provides Type A residual current protection, detecting sinusoidal AC and pulsating DC residual currents. Its C tripping characteristic is suitable for circuits with moderate inrush currents, while the 30 mA rated residual operating current provides additional protection against direct contact as well as protection against indirect contact.
With a rated current of 16 A, a 230 V AC rated voltage and a 6 kA rated short-circuit breaking capacity, the DS202CRC16A30 provides comprehensive protection in a compact DIN rail format. Its two-pole configuration protects both poles and makes it suitable for a wide range of final circuit and electrical distribution applications.
RCBOs combine the functions of a miniature circuit breaker and residual current device in a single protective device. The ABB DS202CRC16A30 protects connected circuits against overload and short-circuit currents while also disconnecting the supply when potentially hazardous residual earth fault currents are detected.
The Type A residual current characteristic detects sinusoidal alternating and pulsating direct residual currents, making the DS202CR suitable for modern electrical installations containing electronic equipment. Its 30 mA sensitivity provides additional protection against direct contact, while the C characteristic makes the device suitable for circuits that may experience moderate starting or inrush currents during normal operation.
| Series | DS202CR |
|---|---|
| Product group | DS200 / DSH200 RCBO |
| ABB order code | 2CSR752140R1164 |
| EAN | 4022903033714 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Number of protected poles | 2 |
| Rated current | 16 A |
| Tripping characteristic | C |
| Residual current type | Type A |
| Rated residual current | 30 mA |
| Rated voltage | 230 V AC |
| Rated frequency | 50 Hz |
| Rated short-circuit breaking capacity (Icn) | 6 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 10 kA |
| Rated service short-circuit breaking capacity (Ics) | 6 kA |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Maximum surge current | 0.25 kA |
| Power loss | 4.2 W |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Operating characteristic | Instantaneous |
| Fault indication | Blue flag on window |
| Electrical endurance | 10,000 operations |
| Mechanical endurance | 20,000 operations |
| Protection rating | IP20 |
| Standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Mounting type | DIN rail |
| Module width | 2 modules |
| Tightening torque | 4 N·m |
| Solid conductor connection | 1–35 mm² |
| Flexible conductor connection | 1–25 mm² |
| Wire stripping length | 11 mm |
| Operating temperature | -25 to +55 °C |
| Dimensions (W × H × D) | 36 × 86 × 72 mm |
| Weight | approx. 0.245 kg |
The ABB DS202CRC16A30 is an RCBO designed to protect single-phase electrical circuits against overloads, short circuits and residual earth fault currents in residential, commercial and industrial installations.
The DS202CRC16A30 has a rated current of 16 A and uses a C tripping characteristic.
The DS202CRC16A30 provides Type A residual current protection with a rated residual operating current of 30 mA, detecting sinusoidal AC and pulsating DC residual currents.
The RCBO has a rated short-circuit breaking capacity (Icn) of 6 kA and a rated ultimate short-circuit breaking capacity (Icu) of 10 kA.
The C tripping characteristic is suitable for circuits that can experience moderate inrush currents, making the RCBO appropriate for a wide range of residential, commercial and industrial electrical loads.
ABB DS202CR RCBOs provide combined residual current and overcurrent protection in a compact two-module format, supporting dependable circuit and personnel protection across residential, commercial and industrial electrical installations.