ABB DS201MC13APR30 (DS201 M C13 APR30) is a 1P+N APR RCBO rated at 13 A with C-curve overcurrent protection, 30 mA residual current sensitivity, 240 V AC operation and 10 kA breaking capacity for dependable single-phase circuit protection with enhanced resistance to unwanted tripping.
£111.10
The ABB DS201MC13APR30, manufacturer type DS201 M C13 APR30, is a compact 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase circuits against overloads, short circuits and residual earth fault currents. As part of the ABB DS201 M / System pro M compact series, it combines overcurrent and residual current protection within a two-module DIN-rail device.
This RCBO features ABB's APR residual current characteristic, developed to improve continuity of service through enhanced resistance to unwanted tripping while maintaining residual current protection. Its 30 mA sensitivity provides additional protection against direct contact, while the C-curve overcurrent characteristic makes the device suitable for resistive and inductive loads with moderate starting currents.
With a rated current of 13 A, 30 mA residual current sensitivity, 240 V AC rated operational voltage and 10 kA rated short-circuit breaking capacity, the DS201 M C13 APR30 provides comprehensive protection for suitable residential, commercial and industrial single-phase circuits.
RCBOs combine miniature circuit breaker and residual current protection functions within a single device. The ABB DS201 M series protects single-phase circuits against overload and short-circuit currents while also detecting residual earth fault currents, providing comprehensive protection without requiring separate MCB and RCD devices for the protected circuit.
The APR characteristic is designed to provide an effective balance between electrical safety and continuity of service through increased resistance to unwanted tripping. Combined with 30 mA residual current sensitivity and a C-curve overcurrent characteristic, the DS201 M C13 APR30 is well suited to appropriate resistive and inductive loads where dependable circuit protection and operational continuity are important.
| Series | DS201 M / DS200 |
|---|---|
| SKU | DS201MC13APR30 |
| ABB order code | 2CSR275480R1134 |
| EAN | 8012542580119 |
| Product group | DS200 / DSH200 RCBO |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Rated current | 13 A |
| Tripping characteristic | C curve |
| Rated residual current | 30 mA |
| Residual current characteristic | APR |
| Rated operational voltage | 240 V AC |
| Rated frequency | 50/60 Hz |
| Poles | 1P+N |
| Protected poles | 1 |
| Rated short-circuit breaking capacity | 10 kA |
| Rated service short-circuit breaking capacity (Ics) | 11.2 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 15 kA |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Operating temperature | -25 to +55 °C |
| Protection rating | IP20 device / IP40 in enclosure |
| Dimensions (H × W × D) | 85 × 35 × 69 mm |
| Weight | 0.2 kg |
| Mounting type | DIN rail |
| Terminal type | Screw terminals |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 |
The ABB DS201MC13APR30 is an RCBO designed to protect single-phase electrical circuits against overloads, short circuits and residual earth fault currents, while its APR characteristic provides enhanced resistance to unwanted tripping.
The RCBO has a rated current of 13 A with a C-curve tripping characteristic.
The APR characteristic is designed to improve continuity of service by providing increased resistance to unwanted residual current tripping while maintaining the required protective function.
The DS201 M C13 APR30 has a rated residual operating current of 30 mA, providing residual current protection for suitable single-phase circuits.
The ABB manufacturer order code is 2CSR275480R1134.
ABB DS201 M APR RCBOs combine residual current and overcurrent protection with enhanced resistance to unwanted tripping, supporting reliable circuit protection and continuity of service across residential, commercial and industrial electrical installations.
We use cookies