ABB DS201MB16A30 DS201 M B16 A30 is a 1P+N 16 A Type A RCBO with B-curve overcurrent protection, 30 mA residual current sensitivity and 10 kA rated short-circuit breaking capacity.
£113.65
The ABB DS201MB16A30, manufacturer type DS201 M B16 A30, is a compact residual current circuit breaker with overcurrent protection (RCBO) designed for protection of end-user single-phase circuits. Part of ABB's System pro M compact DS201 M range, it combines overload, short-circuit and residual current protection within a two-module DIN-rail device.
This RCBO has a 16 A rated current, B tripping characteristic and 10 kA rated short-circuit breaking capacity. Its Type A residual current function responds to sinusoidal alternating and pulsating direct residual currents, while the 30 mA rated residual operating current provides additional protection against electric shock in appropriately designed installations.
The 1P+N configuration provides one protected pole together with two-pole switching for single-phase installations. Operating at 230–240 V AC, 50/60 Hz, the DS201 M B16 A30 provides coordinated overcurrent and Type A residual current protection for residential, commercial and industrial electrical systems.
The ABB DS201 M B16 A30 combines the functions of a miniature circuit breaker and residual current device. Its thermal-magnetic overcurrent section protects wiring and connected equipment against overload and short-circuit currents, while its Type A residual current function responds to sinusoidal alternating and pulsating direct earth fault currents.
With 30 mA residual current sensitivity, the DS201MB16A30 provides protection against indirect contact and additional protection against direct contact in appropriate installations. Its 16 A B-curve characteristic is suited to appropriate circuits with relatively low starting and inrush currents, while its 10 kA Icn breaking capacity provides robust short-circuit protection.
| Range | System pro M compact |
|---|---|
| Series | DS201 M |
| Product family | DS200 / DSH200 RCBO |
| SKU | DS201MB16A30 |
| ABB order code | 2CSR275180R1165 |
| EAN | 8012542587217 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Pole configuration | 1P+N |
| Number of poles | 2 |
| Number of protected poles | 1 |
| Rated current | 16 A |
| Tripping characteristic | B |
| Residual current type | Type A |
| Rated residual current | 30 mA |
| Rated voltage | 230 V |
| Rated operational voltage | 230–240 V AC |
| Rated frequency | 50/60 Hz |
| Rated insulation voltage (Ui) | 500 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 15 kA |
| Rated service short-circuit breaking capacity (Ics) | 11.2 kA |
| Residual current operation | Voltage-independent |
| Contact-position indicator | Yes |
| Earth-fault indicator | Yes |
| Maximum conductor cross-section | 25 mm² |
| Maximum busbar cross-section | 10 mm² |
| Terminal tightening torque | 2.8 Nm |
| Protection rating | IP20 |
| Operating ambient temperature | -25 to +55 °C |
| Mounting | DIN rail |
| Module width | 2 modules |
| Width | 35 mm |
| Height | 85 mm |
| Depth | 69 mm |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 |
The ABB DS201MB16A30 is a 1P+N Type A RCBO designed to protect end-user single-phase circuits against overloads, short circuits and residual earth fault currents.
The RCBO has a rated current of 16 A and a B tripping characteristic, making it suitable for appropriate circuits with relatively low starting and inrush currents.
Type A means the RCBO responds to both sinusoidal alternating residual currents and pulsating direct residual currents, providing broader residual current detection than a Type AC device.
The DS201 M B16 A30 has a rated residual operating current of 30 mA, providing protection against indirect contact and additional protection against direct contact in appropriate installations.
The DS201 M B16 A30 has a rated short-circuit breaking capacity of 10 kA Icn, with a rated ultimate short-circuit breaking capacity of 15 kA Icu.