2CSR275180R0165 ABB DS201MB16A10 RCBO 1P+N B16 Type A 10 mA

2CSR275180R0165 ABB DS201MB16A10 RCBO 1P+N B16 Type A 10 mA

ABB DS201MB16A10 is a 1P+N 16 A B-curve Type A RCBO with 10 mA residual current sensitivity and 10 kA rated short-circuit breaking capacity for combined overload, short-circuit and earth fault protection.

SKU: 2CSR275180R0165Alt SKU: DS201MB16A10MPN: 2CSR275180R0165
Price
List Price £272.32 ex VAT
Your Price (ex VAT) Save 35%
£177.01 35% OFF
You save £95.31 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £177.01
Trade pricing is personalised to your account

Manufacturer Lead Time

£177.01

Why Choose the ABB DS201MB16A10 RCBO?

The ABB DS201MB16A10 is a compact 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase electrical circuits against overloads, short circuits and residual earth fault currents. With ABB order code 2CSR275180R0165, it forms part of the ABB DS200 / DS201 M RCBO range for residential, commercial and industrial electrical distribution applications.

Combining overcurrent and residual current protection within a single modular device, the DS201 M B16 A10 helps simplify circuit protection and distribution board design. Its Type A residual current detection responds to sinusoidal alternating and pulsating DC residual currents, while the B tripping characteristic is suited to circuits with relatively low inrush currents.

With a rated current of 16 A, a highly sensitive 10 mA rated residual operating current and a 230 V AC rated voltage, the DS201MB16A10 provides combined protection for suitable single-phase circuits. Its 10 kA rated short-circuit breaking capacity, compact 1P+N arrangement and DIN rail construction make it a robust solution for modular electrical distribution systems.

Key Advantages

  • Combined overload, short-circuit and residual current protection in one RCBO.
  • 16 A rated current for suitable single-phase electrical circuits.
  • 10 mA rated residual operating current for high-sensitivity residual current protection.
  • Type A residual current detection for sinusoidal AC and pulsating DC residual currents.
  • B tripping characteristic suited to circuits with relatively low inrush currents.
  • 1P+N configuration with one protected pole and switched neutral.
  • 10 kA rated short-circuit breaking capacity for dependable fault protection.
  • Compact two-module construction helps optimise distribution board space.

Key Features

  • ABB DS201 M RCBO series.
  • 16 A rated current.
  • 10 mA rated residual operating current.
  • 230 V AC rated voltage.
  • 1P+N pole configuration.
  • Type A residual current protection.
  • B-curve tripping characteristic.
  • 10 kA rated short-circuit breaking capacity (Icn).
  • 500 V rated insulation voltage (Ui).
  • 4 kV rated impulse withstand voltage (Uimp).
  • Integrated test function for checking residual current protection operation.
  • DIN rail mounting for modular electrical distribution boards.

Reliable Combined Circuit Protection

RCBOs such as the ABB DS201MB16A10 combine residual current and overcurrent protection within one modular device. The overcurrent section responds to overload and short-circuit conditions, while its Type A residual current function detects both sinusoidal alternating and pulsating DC earth fault currents, providing broader residual current detection than a Type AC device.

The DS201 M range provides compact protection for single-phase electrical distribution circuits. The DS201MB16A10 combines a 16 A B-curve overcurrent characteristic with sensitive 10 mA Type A residual current protection, making it suitable for appropriately designed residential, commercial and industrial circuits where these specific protection characteristics are required.

Typical Applications

  • Residential single-phase electrical circuits.
  • Commercial electrical distribution systems.
  • Industrial single-phase circuits.
  • Circuits requiring sensitive 10 mA residual current protection.
  • Lighting, control and auxiliary circuits with relatively low inrush currents.
  • Circuits supplying suitable electronic equipment capable of producing pulsating DC residual currents.
  • Applications requiring combined overcurrent and Type A residual current protection.

Technical Specifications

Series DS201 M / DS200 RCBO
Range System pro M compact
ABB order code 2CSR275180R0165
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Rated current 16 A
Rated residual current 10 mA
Residual current type Type A
Tripping characteristic B curve
Rated voltage 230 V AC
Poles 1P+N
Number of protected poles 1
Rated short-circuit breaking capacity (Icn) 10 kA
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 4 kV
Mounting type DIN rail mounting
Module width 2 modules
Dimensions (H × W × D) approx. 85 × 35 × 69 mm
Weight approx. 0.2 kg
Operating ambient temperature -25 to +55 °C
Standards IEC/EN 61009-1, IEC/EN 61009-2-1

Frequently Asked Questions

What is the ABB DS201MB16A10 used for?

The ABB DS201MB16A10 is an RCBO designed to provide combined overload, short-circuit and Type A residual current protection for suitable single-phase electrical circuits.

What is the current rating of the ABB DS201MB16A10?

The DS201MB16A10 has a rated current of 16 A and uses a B-curve tripping characteristic, making it suitable for appropriate circuits with relatively low inrush currents.

What residual current sensitivity does the DS201MB16A10 provide?

The DS201MB16A10 has a rated residual operating current of 10 mA, providing high-sensitivity residual current protection for appropriate applications.

What does Type A mean on the ABB DS201MB16A10?

Type A means the RCBO is designed to respond to sinusoidal alternating residual currents and pulsating DC residual currents, making it suitable for circuits where these residual current waveforms may occur.

What is the breaking capacity of the ABB DS201MB16A10?

The DS201MB16A10 has a rated short-circuit breaking capacity (Icn) of 10 kA. It is designed for DIN rail mounting and occupies two modular spaces.

Trusted ABB Circuit Protection

ABB DS200 and DS201 M RCBOs combine residual current and overcurrent protection in a compact modular format, supporting dependable circuit protection across residential, commercial and industrial electrical installations.