£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DSE201 M B40 AC30 is a 1P+N 40 A B-curve Type AC RCBO with 30 mA residual-current sensitivity and 10 kA short-circuit breaking capacity for single-phase final-circuit protection.
£86.75
The ABB DSE201 M B40 AC30 is a compact 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and sinusoidal AC earth fault currents. Part of the ABB DSE201 M 10 kA RCBO series, it combines residual-current and overcurrent protection within a single modular device for efficient electrical distribution installations.
This RCBO has a 40 A rated current, B tripping characteristic and 30 mA Type AC residual-current sensitivity. The B-curve characteristic is suited to circuits with relatively low inrush currents, while the 30 mA residual-current protection provides additional protection against direct contact as well as protection against indirect contact and earth fault currents.
With a rated operational voltage of 230–240 V AC and a rated short-circuit breaking capacity of 10 kA to EN/IEC 61009, the DSE201 M B40 AC30 provides robust circuit protection in a compact DIN-rail format. ABB order code 2CSR275051R1405 identifies this specific 40 A, B-curve, Type AC 30 mA version.
An RCBO combines the functions of a miniature circuit breaker and residual-current protective device. The ABB DSE201 M B40 AC30 disconnects a protected circuit in response to overload or short-circuit conditions while also detecting sinusoidal AC residual currents that can arise from earth faults.
Its 30 mA residual-current sensitivity provides additional protection against direct contact as well as protection against indirect contact. The B tripping characteristic is intended for circuits without significant starting-current peaks, while the compact DSE201 M format enables individual final circuits to receive dedicated residual-current and overcurrent protection.
| Series | DSE201 M |
|---|---|
| ABB order code | 2CSR275051R1405 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 1P+N |
| Number of protected poles | 1 |
| Rated current | 40 A |
| Tripping characteristic | B |
| Residual-current type | Type AC |
| Rated residual current | 30 mA |
| Rated voltage | 230–240 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Rated short-circuit breaking capacity | 10 kA |
| Current limiting class | 3 |
| Pollution degree | 2 |
| Overvoltage category | III |
| Operating ambient temperature | −25 to +55 °C |
| Mounting type | DIN rail |
| Width | approx. 17.6–18 mm |
| Height | approx. 115 mm |
| Depth | approx. 68.9–69 mm |
| Weight | approx. 0.20 kg |
| Standards | IEC 61009-1, IEC 61009-2-2, BS EN 61009-1 |
It is an RCBO designed to protect single-phase final circuits against overloads, short circuits and AC earth fault currents, while its 30 mA sensitivity also provides additional protection against direct contact.
The RCBO has a rated current of 40 A with a B tripping characteristic.
The DSE201 M B40 AC30 has a rated residual operating current of 30 mA and is a Type AC device for sinusoidal alternating residual currents.
The device has a rated short-circuit breaking capacity of 10 kA according to EN/IEC 61009.
The ABB order code is 2CSR275051R1405.
ABB DSE201 M RCBOs provide compact combined protection against overloads, short circuits and residual currents, supporting reliable final-circuit protection in commercial and industrial electrical distribution systems.