2CSR275051R1325 ABB DSE201 M B32 AC30 32 A 30 mA Type AC 10 kA RCBO

2CSR275051R1325 ABB DSE201 M B32 AC30 32 A 30 mA Type AC 10 kA RCBO

ABB DSE201 M B32 AC30 is a 1P+N Type AC voltage-dependent RCBO with a 32 A B-curve rating, 30 mA residual current sensitivity and 10 kA short-circuit breaking capacity for commercial and industrial circuit protection.

SKU: 2CSR275051R1325Alt SKU: DSE201 M B32 AC30MPN: 2CSR275051R1325
Price
List Price £151.67 ex VAT
Your Price (ex VAT) Save 45%
£83.42 45% OFF
You save £68.25 per unit
Manufacturer Lead Time Estimated Delivery 4 - 5 Days
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £83.42
Trade pricing is personalised to your account

Manufacturer Lead Time

£83.42

Why Choose the ABB DSE201 M B32 AC30 RCBO?

The ABB DSE201 M B32 AC30 is a compact 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and sinusoidal alternating earth fault currents. Part of the ABB DSE201M 10 kA RCBO range, it combines residual current and overcurrent protection in a single DIN rail device for commercial and industrial electrical installations.

This RCBO has a 32 A rated current, B tripping characteristic and 30 mA rated residual operating current. Its Type AC residual current protection responds to sinusoidal alternating earth fault currents, while its overcurrent protection provides automatic disconnection when overload or short-circuit conditions occur.

With a rated short-circuit breaking capacity of 10 kA, the DSE201 M B32 AC30 provides robust circuit protection for installations with demanding prospective fault-current requirements. Its voltage-dependent 1P+N design with unswitched neutral combines multiple protection functions in a compact modular format suitable for compatible electrical distribution equipment.

Key Advantages

  • Combines residual current and overcurrent protection in one RCBO.
  • 32 A rated current for suitable single-phase final circuits.
  • B tripping characteristic for appropriate circuits with relatively low normal inrush currents.
  • 30 mA residual current sensitivity provides additional protection against electric shock.
  • Type AC detection for sinusoidal alternating residual currents.
  • 10 kA short-circuit breaking capacity for demanding commercial and industrial applications.
  • 1P+N configuration with unswitched neutral.
  • DIN rail construction for straightforward integration into modular distribution equipment.

Key Features

  • ABB DSE201M RCBO series.
  • 1P+N configuration for single-phase circuits.
  • 32 A rated current.
  • B characteristic overcurrent tripping curve.
  • 30 mA rated residual operating current.
  • Type AC residual current detection.
  • 10 kA rated short-circuit breaking capacity.
  • Protection against overload currents.
  • Protection against short-circuit currents.
  • Protection against sinusoidal alternating earth fault currents.
  • Protection against indirect contact.
  • Additional residual current protection at 30 mA.
  • Voltage-dependent RCBO operating principle.
  • Unswitched neutral configuration.
  • Designed for commercial and industrial applications.
  • DIN rail mounting for modular electrical distribution systems.

Combined Overcurrent and Residual Current Protection

An RCBO combines miniature circuit breaker and residual current protection functions within one device. The ABB DSE201 M B32 AC30 therefore protects its connected single-phase circuit against overload and short-circuit currents while also detecting sinusoidal alternating earth fault currents. Its 30 mA residual current sensitivity provides additional residual current protection alongside protection against indirect contact.

The B tripping characteristic is intended for suitable circuits where normal starting and inrush currents are comparatively low. Combined with its 10 kA short-circuit breaking capacity and Type AC residual current protection, the DSE201 M B32 AC30 provides comprehensive protection for appropriate commercial and industrial final circuits.

Typical Applications

  • Commercial electrical distribution boards.
  • Industrial electrical distribution systems.
  • Single-phase final circuit protection.
  • Lighting and power circuits with suitable load characteristics.
  • Control and auxiliary electrical circuits.
  • Circuits requiring 30 mA residual current protection.
  • DIN rail control panels and distribution equipment.
  • Installations requiring 10 kA short-circuit breaking capacity.

Technical Specifications

Series DSE201M
ABB order code / Product ID 2CSR275051R1325
Product group DSE201M / DSE203NM 10kA RCBO
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 1P+N
Rated current 32 A
Tripping characteristic B
Residual current type AC
Rated residual operating current 30 mA
Rated short-circuit breaking capacity (Icn) 10 kA
Protection functions Overload, short circuit and earth fault protection
Operating principle Voltage dependent
Neutral configuration Unswitched neutral
Application Commercial and industrial
Mounting type DIN rail
Standards IEC 61009-1, IEC 61009-2-2, BS EN 61009-1 and AS/NZS 61009.1

Frequently Asked Questions

What is the ABB DSE201 M B32 AC30 used for?

The ABB DSE201 M B32 AC30 is an RCBO for protecting suitable single-phase final circuits against overloads, short circuits and sinusoidal alternating earth fault currents in commercial and industrial electrical installations.

What is the rated current and trip curve of the ABB DSE201 M B32 AC30?

The DSE201 M B32 AC30 has a rated current of 32 A and uses a B tripping characteristic for overcurrent protection.

What residual current sensitivity does the DSE201 M B32 AC30 have?

The RCBO has a rated residual operating current of 30 mA and uses Type AC residual current detection for sinusoidal alternating earth fault currents.

What is the breaking capacity of the ABB DSE201 M B32 AC30?

The DSE201 M B32 AC30 has a rated short-circuit breaking capacity of 10 kA, providing robust fault protection for appropriate commercial and industrial installations.

What is the difference between the ABB DSE201 M B32 AC30 and C32 AC30?

Both versions provide 32 A overcurrent protection, 30 mA Type AC residual current protection and 10 kA short-circuit breaking capacity, but the B32 version uses a B tripping characteristic, while a C32 version uses a C characteristic with different instantaneous magnetic tripping behaviour.

Trusted Circuit Protection from ABB

ABB DSE201M RCBOs combine overload, short-circuit and residual current protection in a compact modular device, providing 10 kA breaking capacity and dependable protection for commercial and industrial single-phase electrical circuits.