Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS203 M AC-B25/0.03 is a 25 A 3-pole Type AC 30 mA RCBO with B-curve overcurrent protection and 10 kA short-circuit breaking capacity for commercial and industrial three-phase electrical circuits.
£206.95
The ABB DS203 M AC-B25/0.03, order code 2CSR273001R1255, is a high-performance 3-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, it combines residual-current and overcurrent protection in a factory-assembled device for commercial and industrial electrical installations.
This DS200 M series RCBO uses Type AC residual-current protection together with a B tripping characteristic. It provides protection against indirect contact and, with its 30 mA rated residual operating current, additional protection against direct contact. The B-curve characteristic is suited to circuits with relatively low starting and inrush currents.
With a rated current of 25 A, 30 mA residual-current sensitivity and 10 kA rated short-circuit breaking capacity, the DS203 M AC-B25/0.03 provides robust combined protection for three-pole circuits. Its DIN rail construction makes it suitable for professional distribution boards and control panels where dependable three-phase residual-current and overcurrent protection is required.
An RCBO combines residual-current protection with overload and short-circuit protection within a single device. The ABB DS203 M AC-B25/0.03 protects three-pole circuits against excessive current while also detecting sinusoidal alternating earth leakage currents, providing coordinated protection for commercial and industrial three-phase electrical distribution systems.
The DS203 M AC-B25/0.03 combines its 25 A B-curve overcurrent characteristic with 30 mA Type AC residual-current protection and a 10 kA rated short-circuit breaking capacity. This combination makes it suitable for three-phase circuits with comparatively low inrush currents where combined overload, short-circuit and Type AC earth fault protection is required.
| Product group | DS200 / DSH200 RCBO |
|---|---|
| Series | DS200 M |
| ABB order code | 2CSR273001R1255 |
| EAN | 8012542933700 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 3 |
| Protected poles | 3 |
| Rated current | 25 A |
| Tripping characteristic | B curve |
| Rated residual current (IΔn) | 30 mA |
| Residual current type | Type AC |
| Rated short-circuit breaking capacity (Icn) | 10 kA |
| Standards | IEC/EN 61009-1; IEC/EN 61009-2-1 |
| Terminal type | Screw terminals |
| Application | Commercial and industrial electrical installations |
| Mounting | DIN rail |
| Weight | approx. 0.61 kg |
The ABB DS203 M AC-B25/0.03 is a 3-pole RCBO used to protect three-phase electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents in commercial and industrial installations.
The RCBO has a rated current of 25 A and uses a B-curve tripping characteristic.
The DS203 M AC-B25/0.03 has a rated residual operating current of 30 mA and uses Type AC residual-current protection.
The DS203 M AC-B25/0.03 has a rated short-circuit breaking capacity (Icn) of 10 kA, providing robust short-circuit protection for suitable commercial and industrial three-phase installations.
Type AC means the RCBO is designed to detect sinusoidal alternating residual currents, providing residual-current protection for applications where this type of earth leakage current is expected.
ABB DS200 M RCBOs combine residual-current and overcurrent protection in factory-assembled devices designed for reliable commercial and industrial electrical distribution, with the DS203 M range providing three-pole protection and high short-circuit breaking capacity for three-phase applications.